22
VIX IM MICROSTEPPER INDEXER DRIVE USER GUIDE
Large Motors
The largest recommended motor size is a 34-frame 3-stack. Please contact Parker if
you wish to use a larger frame motor.
Motor Connections at the Motor
Motor connections should be made directly between the drive and motor, the use of any
switching devices, such as contactors is not recommended.
In the majority of applications the drive will be used with an eight lead motor with the
windings connected in parallel or series, as shown in Figure 3-6. Motor connections will
need to be determined from the motors data sheet or Appendix B. These are normally
identified by wire colour or terminal markings, depending upon the make of the motor.
MOTOR CONNECTOR
PARALLEL
CONNECTIONS
SERIES
CONNECTIONS
A+
X1
1
2
3
4
5
A-
Gnd
B+
B-
+
+
+
+
-
-
-
-
MOTOR
Motor case
+
+
+
+
-
-
-
-
MOTOR
SAFETY
EARTH
SAFETY
EARTH
MOTOR CONNECTOR
A+
X1
1
2
3
4
5
A-
Gnd
B+
B-
Motor case
Figure 3-6. 8 Lead Motor Connection Options
WARNING - High Temperature
The motor case temperature may exceed 70°C and should be guarded from operator
contact.
Motor Safety Earth/Ground Connection
It is recommended that the motor is independently bonded to a local safety earth point. The
safety earth lead should be at least 2.5mm
2
in area.