Page 12
– Bulletin 100-50-5.2
APPENDIX E - Setpoint Parameters (continued)
PARAMETERS
LSHi
Low Superheat Integral Coefficient
1 to 255
Default is 10
Increase value to decrease valve response
to superheat over time, low Superheat
condition
C4ct
Cycle Time
1 to 10 seconds
Default is 1
StEp
Chosen
at Setup
Valve Type
Readout
Description
16
1596 Step Bipolar Valve
313
3193 Step Bipolar Valve
00
00
2500 Step Bipolar Valve
636
6386 Step Bipolar Valve
400
400 Step Unipolar Valve
SPoS
Manual Valve Position
0 to 100% Open
Default is 0
Addr
MODBUS Network Address
1 to 255
Default is 1
BavD
MODBUS Baud Rate
Readout
Description
6
6
9600
1
19200
34
38400
nPAr
MODBUS Network Parity
Readout
Description
none
No Parity
EvEn
EvEn
Even Parity
Odd
Odd Parity
nP
Pressure Units
Readout
Description
Psi
Psi
Pounds Force Per
Square Inch
bAr
Bars
nt
Temperature Units
Readout
Description
FAHr
FAHr
Fahrenheit
CELS
Celsius
tt4p
Temperature Sensor Type
Readout
Description
typ3
3k
typ
typ
2k
tP10
10k
Pt4p
Chosen
at Setup
Pressure Sensor Type
Readout
Description
AbSL
Absolute Pressure Type
gAvg
gAvg
Gauge (Sealed) Pressure
Type
Prng
Chosen
at Setup
Pressure Sensor Range
Readout
Description
10
0-150 PSI
300
300
0-300 PSI
00
0-500 PSI
CALP
Pressure Sensor Calibration Offset
-5 to 5 PSI (-0.34 to 0.34 Bar)
Default is 0
CLT1
Suction Temperature Calibration Offset
-5 to 5°F (-2.7 to 2.7°C)
Default is 0
CLT
Liquid Outlet Temperature
Calibration Offset
-5 to 5°F (-2.7 to 2.7°C)
Default is 0
CLT3
Liquid Inlet Temperature
Calibration Offset
-5 to 5°F (-2.7 to 2.7°C)
Default is 0
CLT4
Auxiliary Temperature Calibration Offset
-5 to 5°F (-2.7 to 2.7°C)
Default is 0
CAdr
Controller Display Address
0 to 99
Default is 0, Do not change
Default values are highlighted.
Clockwise
Counterclockwise