Bulletin 100-50-5.2 –

 Page 11

 PARAMETERS

ESC

Escape and Save Settings

LoSP

Liquid Outlet Temperature Setpoint

Change to desired Liquid Out Temperature 

10 to 100°F  (-12.3 to 37.7°C)

Default is 75°F  (23.8°C)

rghL

Return Gas High Limit

40 to 120°F  (4.4 to 48.8°C)

Default is 120°F  (48.8°C)

SboF

Subcooler Off Temperature Differential

0 to 30°F  (0 to 16.7°C)

Default is 10°F  (5.5°C)

SHSP

Superheat Setpoint

Change to desired Superheat Setpoint

5 to 45°F  (2.8 to 25°C)

Default is 10°F  (5.5°C)

rEFr

Chosen
at Setup

Refrigerant Type

Change to desired Refrigerant Type

Readout

Description

r

R-22

134A

R-134A

40A

R-402A

404A

404A

R-404A

40A

R-407A

40C

R-407C

410A

R-410A

41A

R-417A

4A

R-422A

4d

R-422D

r0

R-507A

r44

R-744

4F

R-245FA

r-E

R-E5

43A

R-438A

401b

R-401B

40A

R-408A

0A

R-508A

0B

R-508B

40F

R-407F

434A

R-434A

444B

R-444B

44A

R-448A

40A

R-450A

44A

R-449A

4A

R-452A

13A

R-513A

HiCP

Maximum Valve Capacity

0 to 100%  

Default is 100

-LP-

Liquid Proportional Coefficient

0 to 25.5  

Default is 1.0

 

Increase value to increase valve response 

to liquid out temperature

-L-

Liquid Integral Coefficient

0 to 255  

Default is 60

Increase value to decrease valve response 

to liquid out temperature over time

-Ld-

Liquid Derivative Coefficient

0 to 255  

Default is 0

Increase value to increase valve response 

to change in liquid out temperature

-SP-

Superheat Proportional Coefficient

0 to 25.5  

Default is 1.0

Increase value to increase valve response 

to superheat

-S-

Superheat Integral Coefficient

0 to 255  

Default is 120

Increase value to decrease valve response 

to superheat over time

-Sd-

Superheat Derivative Coefficient

0 to 255  

Default is 0

Increase value to increase valve response 

to change in superheat

Counterclockwise

Clockwise

APPENDIX E - Setpoint Parameters

Default values are highlighted.

Содержание Sporlan Subcool Control

Страница 1: ...Bulletin 100 50 5 2 Page 1 Subcool Control Installation and Operation Instructions July 2020 Bulletin 100 50 5 2 Controller v G 1...

Страница 2: ...e The user through its own analysis and testing is solely responsible for making the final selection of the system and components and assuring that all performance endurance maintenance safety and war...

Страница 3: ...ressure temperature control for most common refrigerants It displays actual leaving liquid temperature superheat suction pressure valve position controller status and alarms It also allows manual cont...

Страница 4: ...ivity and you will lose all changes entered 1 Enter the Parameter Menu Press and hold the SELECT knob for 5 seconds Rotate the knob to enter the pass word 111 and press the SELECT knob again 2 To chan...

Страница 5: ...ges Ensure superheat does not drop below that described above To exit manual operation mode press encod er knob scroll to ESC and press the knob again After exiting manual mode observe the system for...

Страница 6: ...ammed with de fault Proportional Integral Derivative PID settings that will provide efficient control It may be necessary however to fine tune the PID settings in applications where systems experi enc...

Страница 7: ...nsor will read 60 on the controller Temperature sensor output can be checked by measuring the DC voltage across the sensor wire using the tables in Appen dix L page 19 and Appendix M page 20 Since the...

Страница 8: ...ontrol power Pump down signal ensure Subcool Control expansion valve is not closed Proper system refrigerant charge Liquid line filter clogging or excessive pressure drop Proper Subcooler OffTemperatu...

Страница 9: ...adout Description R 22 R 134a R 402A R 404A R 407A R 407C 410A R 410A 417A R 417A R 422A R 422D R 507A R 744 R 245FA R E5 R 438A R 401B 408A R 408A 508A R 508A 508B R 508B 407F R 407F 434A R 434A 444B...

Страница 10: ...ional S 4 Status of the Auxiliary Temperature Input Stat Controller Status ALS Controller Alarms APPENDIX C Controller Status DISPLAY DESCRIPTION CooL Subcool On Valve modulating pdn Pumpdown Valve cl...

Страница 11: ...448A R 448A 450A R 450A 449A R 449A 452A R 452A 513A R 513A Maximum Valve Capacity 0 to 100 Default is 100 Liquid Proportional Coefficient 0 to 25 5 Default is 1 0 Increase value to increase valve res...

Страница 12: ...Units Readout Description Pounds Force Per Square Inch Bars Temperature Units Readout Description Fahrenheit Celsius t4p Temperature SensorType Readout Description typ3 3k typ2 typ2 2k tP10 10k 4 Cho...

Страница 13: ...Coefficient LSHi Low Superheat Integral Gain Coefficient The integral gain coefficient to use for the superheat PID loop if the superheat is below 3 degrees F CyCt CycleTime The PID update time StEP...

Страница 14: ...ENDIX G Alarms and Failsafes APPENDIX H Technical Specifications ELECTRICAL Supply Voltage 20 26VAC 50 60Hz or 22 26 6VDC Class II input 40VA is recommended for each controller Digital Inputs 0 5VDC M...

Страница 15: ...ls Counter Flow Brazed Plate Heat Exchanger Dry Contacts T4 Evap Outlet Temp T1 Liquid Outlet Temp T2 White Signal Green Ground Black 5VDC Black 24V AC DC RS485 White Green Red B Ground A Suction Temp...

Страница 16: ...ensors 10 14 inches from the heat exchanger on a free draining hori zontal line 2 Remove all insulation and adhesives at the marked loca tion Using Scotch BriteTM clean the copper line to remove oxide...

Страница 17: ...422D 10 R 507A 11 R 744 12 R 245FA 13 R E5 14 R 438A 15 R 401B 16 R 408A 17 R 508A 18 R 508B 19 R 407F 20 R 434A 21 R 444B 22 R 448A 23 R 450A 24 R 449A 25 R 452A 26 R 513A 5 Valve Maximum 0 to 100 6...

Страница 18: ...sor Range and Type 15 to 500 PSI 1 01 to 34 47 Bar Maximum Range 4 Saturation Temperature 60 to 150 F 51 1 to 65 6 C 5 Suction Temperature 60 to 125 F 51 1 to 65 6 C 6 Valve Position of Max Stroke 0 t...

Страница 19: ...5 0 41 1 837 1 915 5 6 42 1 812 1 889 6 1 43 1 788 1 863 6 7 44 1 763 1 837 7 2 45 1 739 1 812 7 8 46 1 715 1 787 8 3 47 1 691 1 763 8 9 48 1 668 1 738 9 4 49 1 644 1 714 10 0 50 1 621 1 690 10 6 51 1...

Страница 20: ...698 5 0 41 2 556 2 663 5 6 42 2 522 2 628 6 1 43 2 489 2 593 6 7 44 2 455 2 558 7 2 45 2 422 2 524 7 8 46 2 389 2 489 8 3 47 2 356 2 455 8 9 48 2 323 2 421 9 4 49 2 290 2 386 10 0 50 2 258 2 353 10 6...

Страница 21: ...438 3 540 15 0 59 3 412 3 511 15 6 60 3 383 3 486 16 1 61 3 357 3 456 C F RANGE VDC 16 7 62 3 327 3 427 17 2 63 3 301 3 401 17 8 64 3 271 3 372 18 3 65 3 244 3 346 18 9 66 3 214 3 316 19 4 67 3 183 3...

Страница 22: ...een 98 6k Surface Sensor white 952662 230545 230546 230072 230076 230078 230073 952565 Used with or without well 20 ft Surface only 20 ft Air Only 20 ft Surface only 20 ft Surface only 20 ft Surface o...

Страница 23: ...ion Author Approved 000 122011 Added Revision History 001 062012 Updated Appendices E I K N Updated Table 2 JH ER 002 112012 Revised as Bulletin JH ER APPENDIX P System Flow Chart Start NO PROCESS Con...

Страница 24: ...Parker Hannifin Corporation Sporlan Division 206 Lange Drive Washington MO 63090 USA phone 636 239 1111 fax 636 239 9130 www sporlan com Bulletin 100 50 5 2 72020 2020 Parker Hannifin Corporation...

Отзывы: