32
04
Booster outlet sensor fault
detected. Possible sensor failure.
By-pass to continue.
The booster pump outlet pressure transducer sensor is
not reporting values as expected. The transducer could
be unplugged, a wiring fault may exist, or the sensor
itself may have failed. The fault must be fixed and
cleared before running the system again. If an
emergency exists the system can still be run by
activating the sensor by-pass function. Please contact
your dealer for help.
05
HP pump inlet sensor fault
detected. Possible sensor failure.
By-pass to continue.
The high-pressure pump inlet pressure sensor is not
reporting values as expected. The transducer could be
unplugged, a wiring fault may exist, or the sensor itself
may have failed. The fault must be fixed and cleared
before running the system again. If an emergency exists
the system can still be run for a limited time by
activating the sensor by-pass function. Please contact
your dealer for help.
06
HP pump outlet sensor fault
detected. Possible sensor failure.
By-pass to continue.
The high-pressure pump inlet pressure sensor is not
reporting values as expected. The transducer could be
unplugged, a wiring fault may exist, or the sensor itself
may have failed. The fault must be fixed and cleared
before running the system again. If an emergency exists
the system can still be run for a limited time by
activating the sensor by-pass function. Please contact
your dealer for help.
09
Salinity sensor fault detected.
Possible sensor failure. Only
manual mode permitted.
The salinity sensor temperature function is no longer
readable by the control system, this is usually an
indication of water penetration into the sensor itself
causing failure. The system will default to manual mode
only if salinity readings are still available. The user can
divert potable water into the ships storage tank, but if
salinity readings are not available, the user must bypass
this sensor to gain access to potable water diversion
functions. Please contact your dealer for help.
10
Product flow sensor fault detected.
Possible sensor failure. By-pass to
continue.
The product water flow meter is no longer sending
reading to the controller. The sensor could be
unplugged, a wiring fault may exist, or the sensor itself
may have failed. Automatic operation is not available.
The sensor must be fixed or replaced before Automatic
mode is available. If an emergency exists, the system
can still be run in automatic mode by activating the
sensor by-pass function. Please contact your dealer for
help.