Safe Torque Off
AC30 series Variable Speed Inverter
OUTPUT SPECIFICATION
OFF state:
Maximum applied voltage:
±30V (X10/06 relative to X10/05)
Leakage current:
Less than 0.1mA.
ON state:
Maximum output current:
150mA
Overcurrent protection:
Included
Resistance between output terminals:
Less than 6Ω.
WARNING
WIRED CONNECTIONS TO TERMINALS X10/01, X10/03, X10/05 AND X10/06 MUST BE LESS THAN 25 METRES IN LENGTH
AND REMAIN WITHIN THE CUBICLE OR DRIVE ENCLOSURE. PARKER IS NOT LIABLE FOR ANY CONSEQUENCES IF
EITHER CONDITION IS NOT MET.