![Parker LINKnet AC30P Скачать руководство пользователя страница 159](http://html1.mh-extra.com/html/parker/linknet-ac30p/linknet-ac30p_users-product-manual_3855138159.webp)
10-6
Trips & Fault Finding
AC30 series Variable Speed Inverter
ID
Trip Name
Possible Reason for Trip
Criteria for Warning
40
A8
Application trip 8
Application warning 8.
41
SPEED ERROR
FAULT
Difference between actual motor speed and the speed setpoint is greater than a
threshold for a period of time.
Difference between actual motor
speed and the speed setpoint has
been greater than the trip
threshold for more than half the
trip delay time.
42
PEER TO PEER
OVERRUN
Configuration error on Master and/or Slave(s) side
PTP or Peer to Peer are OFF on one drive
Destination IP or Destination Port incompatible between Master and Slave(s)
Peer to Peer is not useable
Multiple delayed Peer To
Peer messages have
occurred. This may cause
incorrect phase alignment if
phase control is being used.
43
PHASE CONFIG
Something is wrong in the phase configuration : one or more of the encoders set up
for speed control, master and/or slave are wrongly declared. See Phase Ctrl Config :
Error Number for a detailed description of the error
(Only applicable if phase control is enabled)
Not applicable
.
44
ETHERNET IP
BREAK
Lost Base EtherNet IP communications:
A break in the Base EtherNet IP communications has been detected. Refer to
“Appendix A EtherNet IP Adapter”.
Not applicable.
45
RESOLVER
ERROR
An error has been detected on the resolver signals
Error type is available by looking at
1820 Resolver Trip Type
Not applicable
46
PMAC ALIGN
ERROR
If
1796 Alignment on Power On
has been set to TRUE, the drive should run a
successful Pos Alignment sequence, at power up before being run safely.
or
Something wrong occurred during the last Pos Alignment sequence.
Error type is available by looking at
1807 Alignment error
Not applicable
Содержание LINKnet AC30P
Страница 47: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Страница 49: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Страница 51: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Страница 53: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Страница 55: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Страница 57: ...4 37 Installation AC30 series Variable Speed Inverter AFE Control Wiring Excludes 7004 04 00 Wiring...
Страница 152: ...9 27 Setup Wizard AC30 series Variable Speed Inverter MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 153: ...Setup Wizard 9 28 AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Страница 161: ...10 8 Trips Fault Finding AC30 series Variable Speed Inverter...