background image

ISO 9001 CERTIFIED

© 2013 Parker Hannifin Corporation

Safe Operation  (See Bulletin RSBCV)
People doing any work on a refrigeration system must be 
qualified and completely familiar with the system and the 
Refrigerating Specialties Division valves involved, or all other 
precautions will be meaningless. This includes reading and 
understanding pertinent Refrigerating Specialties Division 
Product Bulletins and Safety Bulletin RSB prior to installation 
or servicing work.

Where cold refrigerant liquid lines are used, it is necessary 
that certain precautions be taken to avoid damage which 
could result from liquid expansion. Temperature increase in a 
piping section full of solid liquid will cause high pressure due 
to the expanding liquid which can possibly rupture a gasket, 
pipe or valve. All hand valves isolating such sections should 
be marked, warning against accidental closing, and must not 
be closed until the liquid is removed. Check valves must never 
be installed upstream of solenoid valves, or regulators with 
electric shut-off, nor should hand valves upstream of solenoid 
valves or downstream of check valves be closed until the  
liquid has been removed. 

It is advisable to properly install relief devices in any section 
where liquid expansion could take place.  Avoid all piping 
or control arrangements which might produce thermal or 
pressure shock.

For the protection of people and products, all refrigerant 
must be removed from the section to be worked on before a 
valve, strainer, or other device is opened or removed.  Flanges 
with ODS connections are not suitable for ammonia service.

Warranty

All Refrigerating Specialties products are under warranty 

against defects in workmanship and materials for a period of 

one year from date of shipment from factory. This warranty 

is in force only when products are properly installed, field 

assembled, maintained, and operated in use and service as 

specifically stated in Refrigerating Specialties Catalogs or 

Bulletins for normal refrigeration applications, unless other-

wise    approved  in  writing  by  the  Refrigerating    Specialties                                                                      

Division.   Defective products, or parts thereof returned to the 

factory with transportation charges prepaid and found to be  

defective by factory inspection, will be replaced or repaired at 

Refrigerating Specialties option, free of charge, F.O.B. factory. 

Warranty does not cover products which have been altered, 

or repaired in the field, damaged in transit, or have suffered 

accidents, misuse, or abuse. Products disabled by dirt or other 

foreign substances will not be considered defective.

The express warranty set forth above constitutes the only 
warranty applicable to Refrigerating Specialties products, and 
is in lieu of all other  warranties, expressed or implied, written 
including any warranty of merchantability, or fitness for a 
particular purpose.

 

  

In no event is Refrigerating Specialties 

responsible for any consequential damages of any nature what-

soever.  No employee, agent, dealer or other person is authorized 

to give any warranties on behalf of Refrigerating Specialties, nor 

to assume, for Refrigerating Specialties, any other liability in  

connection with any of its products.

313172        ECN:  33071        02/05/2013

Symptom

Probable Cause

How to Detect/Repair Defect

No function

No supply voltage
Wrong supply voltage

Check power supply and connection cable

It takes a long time after power up before 
the 4-20 mA signal is updated

Min./Max. calibration has been carried out several 
times on-site

After power up, the green LED flashes rapidly as many times as 
it has been calibrated through its lifetime. After the green LED 
flash slowls down, the 4-20 mA is updated

4-20 mA output signal is to low

Oil has been accumulated in the column/standpipe
Oil falls to the bottom on ammonia systems

Drain oil out of column/standpipe. If a very large amount of oil 
is present it may be necessary to take out the sensor rod and 
clean it for oil

No 4-20 mA output

Not wired correctly

Green LED continues to flash rapidly.  If 24 AC/DC supply: 
check polarity

4-20 mA signal does not correspond to 
actual liquid level

Wrong refrigerant selected

Set correct refrigerant

No 4-20 mA output and green LED is off

Electronics defect

Replace HBLT electronics

4-20 mA signal does not correspond to 
actual liquid level

Operator has incorrectly calibrated probe

Fulfill a factory reset

Trouble Shooting

Содержание HBLT-A1

Страница 1: ...ccumulators or other similar pressure vessels Available in various lengths and factory calibrated for ammonia R717 Product Features Suitable for ammonia CO2 and halocarbon refrigerants Plug and Play no calibration required when installed on ammonia systems Service Friendly electronic head and probe can be separated without emptying the vessel Improved Calibration range signal output can be adapted...

Страница 2: ...d along the height of the pipe column to determine the level of the liquid when setting the HBLT A1 probe as well as to check its performance during operation of the system These are an essential part of any well designed pressure vessel system and the use of an electronic liquid level control does not eliminate this need The pipe connection at the top of the pipe column equalizing the vapor space...

Страница 3: ...5mm 1 Receiver Min 75mm 3 Min 100mm 4 Column Cap Sight Glass Pipe Column Weld Weld Liquid level Switch Notes Column caps are only available in 75mm and 100mm 3 and 4 diameters Mounting Instruction It is required to use Teflon tape paste on NPT connections or sealing ring on BSP connections Add Teflon tape paste to the threads Mount the liquid level transmitter on the vessel and tighten to a torque...

Страница 4: ...g will be changed HBLT A1 HBLT A1 BSP Calibration Levels Milliamperes Vs Level Milliamperes Percent Full 4 0 0 6 12 5 8 25 0 10 37 5 12 50 0 14 62 5 16 75 0 18 87 0 20 100 0 Signal Damping Signal damping is factory set to 15 seconds This setting can be altered by activating the calibration switch The setting range is 1 to 120 seconds Settings can be made while the system is operating Procedure 1 C...

Страница 5: ...he calibration push button and keep it activated in approximately 5 seconds until green LED stops flashing 3 Activate within the next 10 seconds the calibration push button two times with 1 second in between and keep it activated If calibration push button is not activated within 10 seconds it will automatically leave calibration mode and return to normal operation 4 Observe the output mA signal d...

Страница 6: ...n Probe Lengths Measuring Range mm inch mm inch 280 11 02 207 8 15 500 19 69 427 16 81 800 31 50 727 28 62 1000 39 37 927 36 50 1200 47 24 1127 44 37 1500 59 06 1427 56 18 1700 66 93 1627 64 05 2200 86 61 2127 83 74 3000 118 10 2927 115 24 HBLT A1 HBLT A1 BSP Parts List Item Part Description 1 Electronic Head 2 Connection DIN 3 LED Green 4 Calibration Push Button 5 LED Level Bar Graph 6 Cover Cali...

Страница 7: ...m can be solved by following these steps 1 Turn the HBLT probe upside down 1 Probe 2 3 or 4 Dia Column Tape Water 2 Tape all hole on the sleeve otherwise known as reference pipe to prevent any water from leaking out The 4 20 mA output signal is not inverted despite the upside down position 3 Fill the pipe with water according to your calibration needs With the sleeve full of water at the high leve...

Страница 8: ...ties Division Defective products or parts thereof returned to the factory with transportation charges prepaid and found to be defective by factory inspection will be replaced or repaired at Refrigerating Specialties option free of charge F O B factory Warranty does not cover products which have been altered or repaired in the field damaged in transit or have suffered accidents misuse or abuse Prod...

Отзывы: