Bulletin 61-60

4

24V AC/DC

(50/60 Hz)

1

2

3

Controller

or

PLC

mA

Alternative (-)

Supply

Electrical Instruction

HBLT probes are supplied with a 4-pole plug, DIN 43650, 
connector.  

Setting of Refrigerant

The HBLT probes are factory set for ammonia (NH

3

), and water 

(H

2

O).   Settings for all other refrigerants or in case the electronics 

has been replaced, follow the procedure below.

1.  To get in the refrigeration mode setting push the calibration 

push button and keep it pressed while 24 V/plug is connected 
and then release the push button.

2.  Release the calibration push button. Observe the present 

refrigerant setting and measure the 4-20 mA output signal.

1 - flash of Green LED - output signal is ~ 5 mA = R717 or R718 

(factory setting) 

2 - flashes of Green LED - output signal is ~ 6 mA = R22 

3 - flashes of Green LED - output signal is ~ 7 mA = R404A 

4 - flashes of Green LED - output signal is ~ 8 mA = R134a 

5 - flashes of Green LED - output signal is ~ 9 mA = R744

3.  Activate the calibration push button to select required 

refrigerant. 

Each activating will cause the HBLT to step to next refrigerant 
according to below sequence: 

~ 5 mA = R717 or R718 (factory setting) 

~ 6 mA = R22 

~ 7 mA = R404A 

~ 8 mA = R134a 

~ 9 mA = R744

4.  When the current corresponds to the required refrigerant, wait 

10 seconds until the green LED is constant ON (not flashing). 
This indicates that the required refrigerant has been selected.

5.  To leave the setting mode isolate the voltage supply to the level 

transmitter (disconnect plug from transmitter)

Go through step 1, 2 and 5 if you wish to control the setting.

Note: 
This sequence must be observed. If the supply voltage is 
connected before the calibration push button is activated, the 
signal damping will be changed

HBLT-A1/HBLT-A1-BSP Calibration Levels 

Milliamperes Vs. Level

Milliamperes

Percent Full

4

0.0

6

12.5

8

25.0

10

37.5

12

50.0

14

62.5

16

75.0

18

87.0

20

100.0

Signal Damping

Signal damping is factory set to 15 seconds. This setting can be 
altered by activating the calibration switch. The setting range is 1 to 
120 seconds. Settings can be made while the system is operating

Procedure:

1.  Connect the supply voltage.

2.  Push the calibration push button once for each second by 

which you want to increase the damping.

Example:

1. push  

  1 sec.   

120. pushes  

  120 sec.

2. pushes  

  2 sec. 

121. pushes  

  120 sec.

10 seconds after the last push, the value will be saved in the 
memory and the green LED will start flashing again. After 10 
seconds, a further push will start 1-second signal damping again. 
(If the damping setting is set too high, restart the procedure from 
step 1).

Calibration

The HBLT probes are factory calibrated for ammonia (NH

3

), and 

water (H

2

O).  Calibration is required for: 

■  If the default settings do not fit the maximum and minimum 

calibration points provided by the factory or if the points have to 
be adjusted.

Note: The chosen factory calibration setting for the maximum 

point in 20 mA and minimum point is 4 mA. See 
dimensional diagram for more details.

■  A refrigerant not all ready defined.

■  If the electrical head is replaced on an existing/installed probe.

Usually the minimum calibration point is chosen to be 4 mA and 
the maximum calibration point to be 20 mA, but it is also possible 
to calibrate the transmitter at other calibration points.

This can be useful when calibrating on a plant with no possibility 
of bringing the level to the limit points.

Default factory setting is:

0% (HBLT free of liquid) output signal: 4 mA

100% (HBLT fully covered by liquid) output signal: 20 mA

The maximum/minimum levels can be set to any value.

Wiring Diagram: 

DIN Connector

Содержание HBLT-A1

Страница 1: ...ccumulators or other similar pressure vessels Available in various lengths and factory calibrated for ammonia R717 Product Features Suitable for ammonia CO2 and halocarbon refrigerants Plug and Play no calibration required when installed on ammonia systems Service Friendly electronic head and probe can be separated without emptying the vessel Improved Calibration range signal output can be adapted...

Страница 2: ...d along the height of the pipe column to determine the level of the liquid when setting the HBLT A1 probe as well as to check its performance during operation of the system These are an essential part of any well designed pressure vessel system and the use of an electronic liquid level control does not eliminate this need The pipe connection at the top of the pipe column equalizing the vapor space...

Страница 3: ...5mm 1 Receiver Min 75mm 3 Min 100mm 4 Column Cap Sight Glass Pipe Column Weld Weld Liquid level Switch Notes Column caps are only available in 75mm and 100mm 3 and 4 diameters Mounting Instruction It is required to use Teflon tape paste on NPT connections or sealing ring on BSP connections Add Teflon tape paste to the threads Mount the liquid level transmitter on the vessel and tighten to a torque...

Страница 4: ...g will be changed HBLT A1 HBLT A1 BSP Calibration Levels Milliamperes Vs Level Milliamperes Percent Full 4 0 0 6 12 5 8 25 0 10 37 5 12 50 0 14 62 5 16 75 0 18 87 0 20 100 0 Signal Damping Signal damping is factory set to 15 seconds This setting can be altered by activating the calibration switch The setting range is 1 to 120 seconds Settings can be made while the system is operating Procedure 1 C...

Страница 5: ...he calibration push button and keep it activated in approximately 5 seconds until green LED stops flashing 3 Activate within the next 10 seconds the calibration push button two times with 1 second in between and keep it activated If calibration push button is not activated within 10 seconds it will automatically leave calibration mode and return to normal operation 4 Observe the output mA signal d...

Страница 6: ...n Probe Lengths Measuring Range mm inch mm inch 280 11 02 207 8 15 500 19 69 427 16 81 800 31 50 727 28 62 1000 39 37 927 36 50 1200 47 24 1127 44 37 1500 59 06 1427 56 18 1700 66 93 1627 64 05 2200 86 61 2127 83 74 3000 118 10 2927 115 24 HBLT A1 HBLT A1 BSP Parts List Item Part Description 1 Electronic Head 2 Connection DIN 3 LED Green 4 Calibration Push Button 5 LED Level Bar Graph 6 Cover Cali...

Страница 7: ...m can be solved by following these steps 1 Turn the HBLT probe upside down 1 Probe 2 3 or 4 Dia Column Tape Water 2 Tape all hole on the sleeve otherwise known as reference pipe to prevent any water from leaking out The 4 20 mA output signal is not inverted despite the upside down position 3 Fill the pipe with water according to your calibration needs With the sleeve full of water at the high leve...

Страница 8: ...ties Division Defective products or parts thereof returned to the factory with transportation charges prepaid and found to be defective by factory inspection will be replaced or repaired at Refrigerating Specialties option free of charge F O B factory Warranty does not cover products which have been altered or repaired in the field damaged in transit or have suffered accidents misuse or abuse Prod...