background image

9

For assistance, call toll-free at 800-343-4048

After all the components have been properly installed (see Figure 5), the following procedure should
be followed to ensure optimal operation of the entire nitrogen supply system.

1

1

1

1

1

Set the inlet pressure to the Balston Nitrogen Generator using the customer-provided pressure

regulator, and initiate the air flow through the system.

2

2

2

2

2

Set the flow control valve to its fully open position.  The nitrogen flow meter reading should be at

the top of the scale.

3

3

3

3

3

Close the shut-off valve to the process and open the vent valve downstream from the receiving

tank to prevent substandard nitrogen from entering the process.

4

4

4

4

4

Fully open the outlet pressure regulator on the nitrogen generator, and adjust the back pressure

controller until the outlet pressure gauge on the nitrogen generator reads 10 psig (0.7 bar) less
than the desired nitrogen storage pressure.  Maximize the storage pressure to minimize the size
of the receiving tank needed.

5

5

5

5

5

Set the flow control valve on the front panel of the nitrogen generator to the proper reading, as

specified by the Nitrogen Purity Label.  Read from the middle of the ball.

6

6

6

6

6

Purge the entire system for 5 minutes, venting the initial nitrogen stream through the vent valve

to atmosphere.

7

7

7

7

7

Close the vent valve, open the process shut-off valve, and initiate the flow of nitrogen to the

process.

The use of a receiving tank upstream from the process, as detailed in this literature, significantly
reduces the effects of fluctuating nitrogen demand on the purity of the emergent nitrogen process
stream from the Balston Nitrogen Generator.  Parker recommends a 5 minute purge of the system
(see Step 3 above) each time the unit is started.

If the temperature of the inlet air to the Balston Nitrogen Generator differs from the temperature of
the module (i.e. ambient temperature), the system must be allowed to reach temperature equilibrium
before a constant purity of nitrogen is delivered from the system.  If the temperature difference is
10°F-20°F (5°C-11°C), this equilibrium period may be as long as 60 minutes.  The inlet air tempera-
ture and, more importantly, inlet air dewpoint, must not be higher than the temperature of the system
or condensation of water within the system may occur, resulting in inefficient performance of the
system and/or damage to the membrane.

Performance of the Balston Nitrogen Generator is highly dependent on the temperature of the inlet
air.  The data on purity and flow rate presented in this bulletin is based on an inlet air temperature of
68°F (20°C).  If the temperature of the inlet air at the point of use for this system varies from 68°F
(20°C) by more than 5°F (3°C), the factory must be consulted for flow and purity information.

The optimum performance of the Balston Nitrogen Generator is dependent on system parameters
remaining stable and accurate; therefore, the system should be checked at least once per week.
This routine system check should include correcting any changes in the flowmeter reading, confirm-
ing pressure gauge reading stability and operating pressure setting, checking the downstream
flowmeter (if applicable) to ensure flows are consistent with the required nitrogen purity level, and
calibrating the oxygen analyzer.

System upsets relative to pressure or flow rate will result in variations in purity of the outlet gas.
System upsets relative to temperature, dewpoint, or hydrocarbon content of the inlet compressed air
may result in variations of the system performance.  These types of upsets should be eliminated
from the compressed air delivery system to assure consistent performance of the Balston Nitrogen
Generator.

Proper shutdown of the Balston Nitrogen Generator can be accomplished by simply closing the inlet
air gate valve and turning off the oxygen analyzer.  If the inlet valve is left open, the system will
continue to consume inlet compressed air.  Closing the outlet flow control valve will not prevent air
consumption because the membrane module permeate ports are open to atmosphere.

Operation/Calibration

Receiver Tank
Applications

Operation: Adjustment Procedure

Temperature Equilibrium

Evaluation

System Upsets

Shutting Down

Содержание Balston HFX-3

Страница 1: ...separate air into a concentrated nitrogen output stream and an oxygen enriched permeate stream To monitor the purity of the nitrogen stream Parker has incorporated an oxygen analyzer into the design o...

Страница 2: ...ure 1 Air separation takes place in the membrane module This module consists of bundles of hollow fiber membranes The compressed air enters the center bore of these fibers and travels the length of th...

Страница 3: ...junction with safety interlocks and or alarm systems to assure proper nitrogen purity levels at all times systems to assure proper nitrogen purity levels at all times systems to assure proper nitrogen...

Страница 4: ...nt surrounding the nitrogen generator should also be adequately ventilated The environment surrounding the nitrogen generator should also be adequately ventilated The generator creates a 30 to 40 oxyg...

Страница 5: ...sure to maintain the proper polarity black red The HFX0 3 Nitrogen Generator is preset at the factory for operation at 120 VAC The voltage setting for the generator is shown through a small window on...

Страница 6: ...outside circuitry alarm relay contacts to outside circuitry alarm relay contacts to outside circuitry alarm relay contacts to outside circuitry The relay contacts are rated for 250 VAC 5 amps resistiv...

Страница 7: ...gen using a span gas known quantity of oxygen per gas supplier or compressed air 20 9 oxygen In the single point method only one point in the calibration range is set using either span gas or compress...

Страница 8: ...oxygen analyzer on a routine basis If the nitrogen purity level falls below the desired level readjust the flow control valve until the proper nitrogen purity level is reached Note If more than minor...

Страница 9: ...vered from the system If the temperature difference is 10 F 20 F 5 C 11 C this equilibrium period may be as long as 60 minutes The inlet air tempera ture and more importantly inlet air dewpoint must n...

Страница 10: ...vice schedule and replacement part numbers are outlined at the end of this section The calibra tion procedure for the oxygen analyzer is outlined on page 6 The analyzer should be calibrated on a regul...

Страница 11: ...en servicing This equipment has fuses in both neutral and phase lines Use care when servicing Occasionally one or both of the fuses P N 13221 in the generator may burn out The fuses are located in the...

Страница 12: ...ve 95 F 35 C the longevity of the membrane will be reduced and the warranty will be void 6 6 6 6 6 The drain lines from the first two stages of filtration should be piped away to an appropriate collec...

Страница 13: ...58 F 50 C Particles 0 01 m None None Suspended Liquids None None Commercially Sterile Yes Yes Max Operating Pressure 145 psig 10 barg 145 psig 10 barg Maximum Pressure Drop 10 psi 0 7 bar 10 psi 0 7 b...

Страница 14: ...d range during calibration Replace sensor P N 72695 Operating Conditions To arrange for system service contact the Technical Services Department at 1 800 343 4048 8AM to 5PM Eastern Time For location...

Страница 15: ...cription Description Description Description Caution refer to accompanying documents for explanation Refer the caution warning note indicated for explantion Caution risk of electric shock 3 3 3 3 3 Ex...

Страница 16: ...rhill MA 01835 0723 Tel 978 858 0505 Fax 978 556 7501 Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation F...

Отзывы: