background image

8

Parker Hannifin Corporation

 Bulletin TI-HFX-3D

Elevated Pressure
Applications

(>10 psig/0.7 barg)

The user must determine the nitrogen purity, flow rate, and pressure required by the application
prior to adjusting the system for desired outlet nitrogen purity and flow rate.  The inlet air pressure
must be constant in order for the system to supply nitrogen of consistent purity to the application.
The inlet pressure to the Balston Nitrogen Generator should be maximized (within process and
generator parameters) to optimize the operation of the membrane module.  The required inlet air
flow rate and all flow and purity specifications for different operating conditions are shown in the
specifications listing on pages 12-13.
Flow adjustments are made according to the values on the Nitrogen Purity label attached to the
front of the generator (and shown below).

If the Balston Nitrogen Generator is being used to deliver nitrogen at or near atmospheric pressure
(e.g. purging or blanketing applications), use the following procedure for start-up and adjustment of
the system.

1

1

1

1

1

Open the (customer installed) inlet air gate valve.

2

2

2

2

2

Adjust the (customer installed) inlet air pressure regulator until the Operating Pressure Gauge

(see Figure 1) shows the pressure reading required to achieve the purity and flow to match the
application (see Purity/Flow label above).

3

3

3

3

3

Adjust the Outlet Pressure Regulator (see Figure 1) until the Outlet Pressure Gauge reads less

than 10 psig (0.7 barg).

4

4

4

4

4

Consult the Nitrogen Purity Label on the control panel of the generator to determine the proper

flowmeter setting for the required process nitrogen purity and inlet air pressure.  Adjust the flow
control valve on the control panel (see Figure 1) to yield the proper flowmeter reading.

5

5

5

5

5

Allow the system to reach equilibrium at the desired flowrate, pressure, and purity parameters.

This should take approximately 15 minutes.

6

6

6

6

6

Check the purity readings on the oxygen analyzer on a routine basis.  If the nitrogen purity level

falls below the desired level, readjust the flow control valve until the proper nitrogen purity level is
reached.  (Note:  If more than minor adjustments of the flow control valve are required to reach
the desired purity level, please see the Troubleshooting section of this manual for further guid-
ance.)

If the Balston Nitrogen Generator is being used to deliver nitrogen at an elevated pressure
(>10 psig/0.7 barg), use the following procedure for start-up and adjustment of the system.  (Note:
In elevated pressure applications, the customer should install a flow controller downstream from the
Nitrogen Generator.)

1

1

1

1

1

Open the (customer installed) inlet air gate valve.

2

2

2

2

2

Adjust the (customer installed) inlet air pressure regulator until the Operating Pressure gauge

(see Figure 1) shows the pressure reading required to achieve the purity and flow to match the
application (see Purity/Flow label, page 13).

3

3

3

3

3

Turn the Flow Control Valve to its fully open position

4

4

4

4

4

Set the Outlet Pressure Regulator (see Figure 1) to the desired outlet nitrogen pressure.

5

5

5

5

5

Consult the Nitrogen Purity Label on the control panel of the HFX0-3 to determine the proper

dimensionless flowmeter setting for the required process nitrogen purity and operating air
pressure.  Adjust the (customer installed) flow controller until the dimensionless flowmeter shows
the correct reading (based on the Nitrogen Purity Label).

6

6

6

6

6

Allow the system to reach equilibrium at the desired flowrate, pressure, and purity parameters.

This should take approximately 15 minutes.

7

7

7

7

7

Check the purity readings on the oxygen analyzer on a routine basis.  If the nitrogen purity level

falls below the desired level, readjust the downstream flow controller until the proper nitrogen
purity level is reached.  (Note:  If more than minor adjustments of the downstream flow controller
are required to reach the desired purity level, please see the Troubleshooting section of this
manual for further guidance.)

Operation: Adjustment Procedure

System Adjustment for
Desired Outlet Purity

Atmospheric Pressure
Applications

(<10 psig/0.7 barg)

Содержание Balston HFX-3

Страница 1: ...separate air into a concentrated nitrogen output stream and an oxygen enriched permeate stream To monitor the purity of the nitrogen stream Parker has incorporated an oxygen analyzer into the design o...

Страница 2: ...ure 1 Air separation takes place in the membrane module This module consists of bundles of hollow fiber membranes The compressed air enters the center bore of these fibers and travels the length of th...

Страница 3: ...junction with safety interlocks and or alarm systems to assure proper nitrogen purity levels at all times systems to assure proper nitrogen purity levels at all times systems to assure proper nitrogen...

Страница 4: ...nt surrounding the nitrogen generator should also be adequately ventilated The environment surrounding the nitrogen generator should also be adequately ventilated The generator creates a 30 to 40 oxyg...

Страница 5: ...sure to maintain the proper polarity black red The HFX0 3 Nitrogen Generator is preset at the factory for operation at 120 VAC The voltage setting for the generator is shown through a small window on...

Страница 6: ...outside circuitry alarm relay contacts to outside circuitry alarm relay contacts to outside circuitry alarm relay contacts to outside circuitry The relay contacts are rated for 250 VAC 5 amps resistiv...

Страница 7: ...gen using a span gas known quantity of oxygen per gas supplier or compressed air 20 9 oxygen In the single point method only one point in the calibration range is set using either span gas or compress...

Страница 8: ...oxygen analyzer on a routine basis If the nitrogen purity level falls below the desired level readjust the flow control valve until the proper nitrogen purity level is reached Note If more than minor...

Страница 9: ...vered from the system If the temperature difference is 10 F 20 F 5 C 11 C this equilibrium period may be as long as 60 minutes The inlet air tempera ture and more importantly inlet air dewpoint must n...

Страница 10: ...vice schedule and replacement part numbers are outlined at the end of this section The calibra tion procedure for the oxygen analyzer is outlined on page 6 The analyzer should be calibrated on a regul...

Страница 11: ...en servicing This equipment has fuses in both neutral and phase lines Use care when servicing Occasionally one or both of the fuses P N 13221 in the generator may burn out The fuses are located in the...

Страница 12: ...ve 95 F 35 C the longevity of the membrane will be reduced and the warranty will be void 6 6 6 6 6 The drain lines from the first two stages of filtration should be piped away to an appropriate collec...

Страница 13: ...58 F 50 C Particles 0 01 m None None Suspended Liquids None None Commercially Sterile Yes Yes Max Operating Pressure 145 psig 10 barg 145 psig 10 barg Maximum Pressure Drop 10 psi 0 7 bar 10 psi 0 7 b...

Страница 14: ...d range during calibration Replace sensor P N 72695 Operating Conditions To arrange for system service contact the Technical Services Department at 1 800 343 4048 8AM to 5PM Eastern Time For location...

Страница 15: ...cription Description Description Description Caution refer to accompanying documents for explanation Refer the caution warning note indicated for explantion Caution risk of electric shock 3 3 3 3 3 Ex...

Страница 16: ...rhill MA 01835 0723 Tel 978 858 0505 Fax 978 556 7501 Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation Parker Filtration Separation F...

Отзывы: