Adjustment Guide: -

Controller

Positive Logic operation. 

Positive Logic operation. 

( Default setting )

( Default setting )

.

.

1.

Ensure command PWM signal is set to zero.

2.

Check 12V coil is selected for 12V system

3.

Check 24V coil is selected for 24V system.

4.

Connect driver unit onto valve coil to be driven ( check connector is secure ).

5.

Ensure that all other controller wire connections are correct and secure.

6.

Turn I Min potentiometer 20 turn Anti-Clockwise ( Minimum ).

7.

Turn I Max potentiometer 20 turns Clockwise ( Maximum ).

8.

‘Dither frequency’ potentiometer is pre-set to 200Hz to suit the ERA121C valve series.

9.

Apply supply power voltage to the controller. 

10.

Slowly increase command to approx 10% of maximum PWM.

11.

Use the I Min adjustment to give MAXIMUM motor speed required. 

12.

Slowly Increase command signal PWM to maximum ( 95% ) setting.

13.

Adjust  I Max until desired motor MINIMUM speed is achieved 

14.

Check that ‘Output ON’ led is functioning proportionally by varying the command signal. 

15.

Set command to maximum PWM %

16.

Isolate the controller from the power. Controller 700-00028-0 is now set and ready for operation.

17.

Attach the lid to the main controller unit carefully ensuring that seal is maintained.

18.

Replace securing screws and tighten ( Do not over tighten ).

19.

Mount re-assembled controller to bulkhead / panel.

20.

Unit is now ready for continuous application use.

700-00028-0, DFC-4 Fan Driver Unit.

Positive Logic operation 

means that the output current follows the input command signal.

i.e. 5% PWM  = Min current O/P  and  95% PWM = Max current O/P

This option is intended for use when the input PWM signal is conforming to positive logic as above.

In this configuration, if the power supply fails, the fan unit will default to the Maximum speed ( see note below ).

For this option to be activated, the user must 

leave

link ‘A’ fitted

, the location of which is shown on page 7 of 

this manual.

NOTE:-

At all times during the set-up procedure, it is assumed that a INVERSE ACTING pressure control valve is being 
used.

For other logic or valve types, please ensure the input output logic is correct before connection and operation.

Содержание 700-00028-0

Страница 1: ...1 Fan Controller Unit 700 00028 0 Application and Information Manual DFC 4 12 24V Direct Connect option Publ 700 00028 0 ver6 February 2006...

Страница 2: ...and or advice should be sought from your local distributor or from Parker internal sales departments This driver unit has been designed to interface and operate with Wide supply range 10VDC to 32VDC...

Страница 3: ...t under full load 8 Allow wires TO or FROM the unit to short circuit to each other or chassis cabinet e t c 8 Attempt to use this unit in areas of intense RF without adequate screening measures 8 Disc...

Страница 4: ...y slope angle e t c are already calculated for us This means that adjustment of the controller is simple with only three potentiometers Dither frequency which is needed to ensure correct repeatable an...

Страница 5: ...wer supply to the controller is removed Recommended Parker valve is the ERA121C30 3000psi operation other values are available please consult the IHD catalogue Adjustment Guide NON NON INVERSE INVERSE...

Страница 6: ...TE For operational safety if the input PWM signal is below approx 5 the output to the valve is OFF 0 20 40 60 80 100 110 Output Current mA 0 20 30 40 50 60 70 80 100 PWM input 10 90 Output Characteris...

Страница 7: ...ommand Input Value 10V 30V 5 to 95 PWM typical range 10 Command Input Frequency 20 to 125Hz 11 Available adjustments I Max I Min Dither Frequency adjust 12 Dither Frequency coil output Preset to 200Hz...

Страница 8: ...varying the command signal 15 Set command to maximum PWM 16 Isolate the controller from the power Controller 700 00028 0 is now set and ready for operation 17 Attach the lid to the main controller uni...

Страница 9: ...nd signal 16 Set command to minimum PWM 17 Isolate the controller from the power Controller 700 00028 0 is now set and ready for operation 18 Attach the lid to the main controller unit carefully ensur...

Страница 10: ...V max supply input PWM output PWM 0V output Emergency Fan MINIMUM SPEED relay configuration NC NO 1 2 Closing the relay will force the input to 24V supply voltage and the fan will be controlled to ful...

Страница 11: ...ightweight Aluminum alloy Housing Colour Eggshell Black Surface Finish Powder coated Unit size See above size detail drawings Unit Weight Approx 400 grams including Encapsulation material Cable Wire e...

Страница 12: ...12 Parker Hannifin Corporation Fan Drive Systems 14249 Industrial Parkway Marysville OH 43040 Customer Service Department Tel 937 644 4435 Fax 937 642 3639 www parker com hydraulics fandrive...

Отзывы: