![Parker 506 Series Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/parker/506-series/506-series_product-manual_755622018.webp)
4-2
Installing the 506/507/508
506/507/508 - HA389427
WARNING!
Ensure that all wiring is electrically isolated and cannot be
made "live" unintentionally by other personnel.
Wire Sizes
* Contains semiconductor fuses as recommended below.
Model Maximum
Output
Rating
Function
Cable
(Wire) Size
AC Supply
Fuse
Rating
SSD Drives Fuse
Isolator Kit Part
Numbers *
506 3A
DC
Armature,
AC Supply,
Ground
1.5mm
2
/
16AWG
10A LA054664
507 6A
AC
Supply,
Ground
DC Armature
2.5mm
2
/
14AWG
1.5mm
2
/
16AWG
10A LA054664
508 12A
AC
Supply
DC Armature,
Ground
6.0mm
2
/
10AWG
4.0mm2/
12AWG
20A LA050062
Terminal Tightening Torques
Terminal
Torque Setting
Power
0.8 Nm
7 lbf-in
Control
0.56 Nm 5 lbf-in
Ferraz Semiconductor Fuses
Fuse Rating Ferraz Type No.
SSD Drives Part No.
10A, 250V 250VFA10A6X32
CH230014
20A, 250V 250VFA20A6X32
CH230024
Содержание 506 Series
Страница 8: ...Contents Contents Page ...
Страница 10: ...1 2 Product Overview 506 507 508 HA389427 WWW SDS LTD UK 0117 9381800 ...
Страница 12: ...2 2 Overview of the 506 507 508 506 507 508 HA389427 ...
Страница 16: ...3 4 Terminal Description 506 507 508 HA389427 ...
Страница 29: ...4 14 Installing the 506 507 508 506 507 508 HA389427 ...
Страница 31: ...5 2 Routine Maintenance and Repair 506 507 508 HA389427 ...