English
5/8
ICE310-360
4.4.1.1
Remote On / Off mode
0
Remote On/Off disabled
1
Remote On/Off enabled together with local On/Off
2
Remote On/Off only, local On/Off disabled
4.4.1.2
Alarm relay management
0
Relay normally deactivated, excited by an alarm.
1
Relay normally excited (also with control OFF), deactivated
by an alarm.
2
Relay normally excited (only with control ON), deactivated
by an alarm or with control OFF.
4.4.2 Temperature
control
PARAMETER
CODE
TYPE
DEFAULT
Temperature control set point
SEt
D
12.0
Temperature control diff erential
dIF
D
3.0
Set point lower limit
LI5
U
5.0
4.4.3
B1 sensor parameters
PARAMETER
CODE
TYPE DEFAULT
High temperature confi guration
cHAI
U
0
High temperature alarm
HAI
D
60.0
Low temperature alarm
LAI
D
-20.0
Sensor calibration
CAI
U
0.0
Low temperature alarm reset
diff erential
dbI
U
1.0
4.4.4
B2 sensor parameters
PARAMETER
CODE
TYPE DEFAULT
High temperature confi guration
cHA2
U
0
High temperature alarm
HA2
U
60.0
Low temperature alarm
LA2
U
3.0
Sensor calibration
CA2
U
0.0
B2 sensor presence
Ab2
U
1.0
4.4.5
P1 sensors parameters
PARAMETER
CODE
TYPE DEFAULT
Transducer calibration
CAP1
U
00
4.4.6
P2 sensors parameters
PARAMETER
CODE
TYPE DEFAULT
Transducer calibration
CAP2
U
00
4.4.7 Compressor
parameters
PARAMETER
CODE
TYPE
DEFAULT
Compressor rotation
rot
U
2
Compressor 1 enabling
AbC1
U
0
Compressor 3 enabling
AbC3
U
0
Compressor 2 enabling
AbC2
U
0
Compressor 4 enabling
AbC4
U
0
Compressor 1 operation hour
counter
HI
D
-
Compressor 3 operation hour
counter
H3
D
-
Compressor 2 operation hour
counter
H2
D
-
Compressor 4 operation hour
counter
H4
D
-
Compressor 1 hour counter
threshold
tHI
U
0
Compressor 3 hour counter
threshold
tH3
U
0
Compressor 2 hour counter
threshold
tH2
U
0
Compressor 4 hour counter
threshold
tH4
U
0
4.4.8 Pump
parameters
PARAMETER
CODE
TYPE
DEFAULT
Pump stop delay
dP5
U
5
Pump start delay
dPA
U
5
4.5 Parameter management
4.5.1
Temperature setting (see fi g.1)
1. 1. Turn the main swicth (QS) to “ON” and wait for the temperature
visualization.
2. Press buttons “
P3
” and “
P5
” together, to enter into “
dIrE
” (D)
parameters.
3. Press button “
P4
” to select “
SEt
” parameter, press the button
“
P5
” to confi rm.
4. Change the value, using the up and down arrow buttons “
P3
” and
“
P4
”, then press button “
P5
” to confi rm.
6. Press the button “
P3
” to return on “
dIrE
”
parameter.
7. Press the button “
P5
” to exit.
4.5.2 Diff erential setting (see fi g.1)
1. Turn the main swicth (QS) to “ON” and wait for the temperature
visualization.
2. Press buttons “
P3
” e “
P5
” together, to enter into “
dIrE
” (D)
parameters.
3. Press button two times “
P4
” to select “
diF
” parameter, press the
button “
P5
” to confi rm.
4. Change the value, using the up and down arrow buttons “
P3
” and
“
P4
”, then press button “
P5
” to confi rm.
6. Press the button two times “
P3
” to return on “
dIrE
”
parameter.
7. Press the button “
P5
” to exit.
4.5.3
Visualization sensors B1,B2...
“B1” is the “set” sensor of the macchine.
1. Start the chiller.
2. Press the button “
P4
” to visualize the temperature of the next sen-
sor.
3. Press the button “
P5
” to visualize the sensors “
b01
” ..“
b02
”....
It is recommended to leave on the display the B1 “set” sensor.