ting the controller changes the thermocouple se-
lection to Type-S.
1
From
[IDLE]
, press
OPTIONS
repeatedly until
[TC]
appears.
2
Press
ENTER
. Use the
1
or
3
key to select
[ K]
,
[ N]
,
[ R]
or
[ S]
.
3 After selecting one of the above, press
ENTER
. Press
STOP
to return to
[IDLE]
.
F/C / Selecting Between °F and °C
Temperature Display
The controller operates in your choice of Fahrenheit or
Celsius temperature. In °C display, a lighted dot appears in
the lower right. In °F, it disappears. To switch from °F to °C
or vice versa:
1
From
[IDLE]
, press
OPTIONS
repeatedly until
[F/C]
appears.
2
Press
ENTER
. Use the
1
or
3
key to select
[ F]
or
[ C.]
.
3
After selecting one of the above, press
ENTER
.
Press
STOP
to return to
[IDLE]
.
°F/°C Temperature Conversion Formulas
Below are formulas for converting temperture between
°F and °C. Converting a firing rate requires a different for-
mula than converting a firing temperature:
Firing to a Temperature
(i.e. “Fire to 1600°F.” 1600°F = 871°C)
(°C x 1.8) +32 = °F
(°F - 32) ÷ 1.8 = °C
Firing Rate or Temperature Change
(i.e. “Fire at 200°F per hour” or “Fire 200°F hotter.” 200°F =
111°C)
°C x 1.8 = °F
°F ÷ 1.8 = °C
TCOS / Thermocouple Offset
Calibrate the Thermocouple(s)
The thermocouple is the rod protruding into the firing
chamber. It measures temperature. K-Type thermocouples
can “drift” as they age, causing a gradual shift in tempera-
ture readings. Thermocouple Offset calibrates the control-
ler to compensate for drift.
Note:
The thermocouple must protrude into the
firing chamber the correct distance: about ¾” for
¼” wide thermocouples, ½” - 5/8” for 1/8” wide
thermocouples.
Setting Thermocouple Offset
You can enter a temperature change up to 45°F/25°C
higher or lower than the zero factory setting.
1
From
[IDLE]
, press
OPTIONS
repeatedly until
[TCOS]
appears.
2
Press
ENTER
.
[
O]
, or a Thermocouple Offset,
will appear.
3
Using the
1
and
3
keys, enter the new offset. Press
ENTER
.
[TCOS]
will appear. To return to
[IDLE]
,
press
STOP
.
Thermocouple Offset Settings
°F Setting °C Setting
Result
0
0
No adjustment
H 1-45
H 1-25
Kiln will fire hotter
C 1-45
C 1-25
Kiln will fire cooler
Thermocouple Offset Examples
Setting
Result
H 1
Kiln will fire 1° hotter
H 17
Kiln will fire 17° hotter
C 12
Kiln will fire 12° cooler
Multiple-Zone Thermocouple Offset
1
From
[IDLE]
, press
OPTIONS
repeatedly until
[TCOS]
appears.
2
Press
ENTER
.
[TC1]
(top thermocouple) will ap-
pear.
3
While
[TC1]
displays, press
OPTIONS
. The other
thermocouple(s), then
[TCOS]
, will appear with
each press of the
OPTIONS
key.
3 zone kilns:
[TC1] [TC2] [TC3] [TCOS]
2 zone kilns:
[TC 1] [TC3] [TCOS]
4
When the correct thermocouple appears, press
ENTER
.
5
Using the
1
and
2
keys, enter the new offset. (See
charts above.) Press
ENTER
. The thermocouple
you adjusted (i.e.
[TC1]
) will appear. Select an-
other thermocouple, if necessary, or return to
[IDLE]
by pressing
STOP
.
AOP1, AOP2 / Auxiliary Outputs
Select Vent Fan or Alarm for the Auxiliary Outputs
The
[AOP1]
and
[AOP2]
(Auxiliary Outputs) are for re-
ceptacles (called sockets in England) mounted on the kiln
switch box. The outlets can power a kiln vent or an external
alarm, such as a bell. (An AOP outlet is optional and might
not be included on your kiln.)
The choices in the
[AOP1]
and
[AOP2]
options:
I
[VFAN]
Kiln Vent or Gas Outlet:
This option adds a
display prompt for fan (
[ FN]
) to each segment during
Ramp-Hold programming (page 15).
I
[CPT]
When the kiln fires to completion, and
[CPTL]
appears in the display, the controller will turn on power
to the AOP outlet. Plug a bell or other alarm into the
AOP outlet to notify you that the firing is done.
I
[ALRM]
Alarm:
This choice sends power to the AOP
receptacle whenever the alarm sounds. (See Tempera-
22
Cone-Fire / Ramp-Hold
Do not leave your kiln unattended during operation.