background image

LT5944 Iss 1 (25/10/11) 

12

 

PARAGON FOCUS RS PLUS 

Installation Instructions 

 

SECTION EIGHT 

Siting the Appliance 

 
 (When  installing  in  a  timber  framed  dwelling  reference  must  be  made  to  the  specific  installation 
requirements stated in 

Section 10 Installing the Appliance in Timber Framed Dwelling

). 

 

THERE ARE TWO TYPES OF INSTALLATION

 (into conventional masonry walls): -   

 

The appliance body can be recessed back into the brickwork cavity so that the appliance is flush 
fitting with the wall or fireplace back panel, see Installation Instructions,  

OR 

 

With a dummy chimneybreast constructed forward into the room to take up the 180mm depth of 
the firebox. This depth can be reduced if a deep rebated surround is also used the rebate depth 
can be deducted from the dummy breast depth 

Any  surround  used  must  meet  the  specification  stated  later  in  this  section.  Prior  to  installing  the 
appliance all combustible materials must be removed from the rear faces as described in Section 10.  

 

GENERAL REQUIREMENTS 

 

 

The  flue  and  air  duct  length 
must  be  between  100mm  to 
1metre.  The  fire  is  supplied 
with a standard pipe length of 
535mm  (to  be  cut  in  half  to 
make  a  flue  and  air  duct 
length  of  267mm)  The  flue 
and 

air 

duct 

must 

not 

accommodate 

any 

bends.  

Other  lengths  of  flue  and  air 
duct are available 

 

The flue outlet must terminate 
on a suitable outside wall.  

 

The  minimum  flue  terminal 
clearances,  which  must  be 
maintained, are as shown below.   
   

A  

Directly below an openable window or other opening. E.g. air brick   

300mm

 

 

Below gutters, soil pipes or drain pipes   

 

 

 

 

300mm

 

Below eaves  

 

 

 

 

 

 

 

 

300mm

 

Below balconies or car port roofs   

 

 

 

 

 

600mm

 

From vertical drain pipes and soil pipes   

 

 

 

 

75mm

 

From internal and external corners 

 

 

 

 

 

300mm

 

Above ground, roof or balcony level 

 

 

 

 

 

370mm

 

From a surface facing the terminal 

 

 

 

 

 

600mm

 

From a terminal facing the terminal 

 

 

 

 

 

1200mm

 

From an opening in a car port into a dwelling e.g. door, window, etc  

1200mm

 

Vertically from a terminal on the same wall 

 

 

 

 

1500mm 

Horizontally from a terminal on the same wall   

 

 

 

300mm   

Note: These dimensions are taken from the centre of the circular flue outlet. 
 
 
 
 

 

Содержание focus rs plus remote

Страница 1: ... SEALED INSET LIVE FUEL EFFECT GAS FIRE OWNER S MANUAL Please read these instructions carefully before you start using the appliance Keep this booklet handy for future reference This appliance is for use in GREAT BRITAIN or IRELAND only TELFORD SHROPSHIRE ENGLAND ...

Страница 2: ...eneral Requirements 12 SECTION NINE Preparing the Appliance for Installation 13 SECTION TEN Install the appliance 14 Installing the Appliance into a Cavity Wall 14 Installing the Appliance into a Deep Rebated Surround or Dummy Breast 15 Installing the Appliance into a Timber Framed Dwelling 17 Connecting the Gas Supply 18 Checking Gas Soundness 18 SECTION ELEVEN Assemble the Appliance 18 SECTION T...

Страница 3: ...waste These materials are not classified as hazardous waste and should be disposed of at a site licensed for the disposal of industrial waste The PARAGON FOCUS RS PLUS is an inset room sealed decorative fuel effect gas appliance The PARAGON FOCUS RS PLUS is available in LPG G31 37 mbar Only The marking G31 for Propane Gas Only on the packaging and the data badge specify the gas for which the appli...

Страница 4: ...mediately above first Run the fire on high over a few days The first time you light your new appliance a smell may occur due to its new condition This is quite normal and will soon disappear after a few hours use at maximum setting open a window until the smell disappears The appliance MUST NOT be used if the glass panel is not correctly fitted or if this panel is cracked or broken Any debris shou...

Страница 5: ...d SECTION THREE Operation Do not use this appliance without the glass panel fitted or if this panel is cracked or broken WARNING If the burner or pilot is extinguished for any reason do not attempt to re light the pilot for at least three minutes LIGHTING THE FIRE The pilot can be left on or the pilot can be extinguished and relit each time the fire is used The appliance Control Knob is positioned...

Страница 6: ...leading Supermarkets Remove the glass panel as follows Remove ash pan cover and fret Remove decorative trim held in place with four magnets Slacken but do not remove the 4 nuts securing the bottom glass clamp Remove the 3 screws located down each side Note when they are replaced ensure the glass is central and these brackets pushed up to the side of the glass before tightening the finger nuts Whil...

Страница 7: ... ADDED to the appliance If any Fuel Bed Parts are broken then they must be replaced before the appliance is used Note There is only a COAL fuel bed arrangement for the L P G Please check the label on the appliance carton to ensure you have the correct fuel bed The fuel bed parts are delicate and should be handled with great care The loose part should be removed for cleaning They can be brushed ver...

Страница 8: ...ng Fuel Bed Laying Continued COAL BED LAYOUT The Coal set as shown consists of Rear Matrix Front Matrix 10 x Individual Coals The Front Matrix is located as shown in front of the burner The Rear Matrix is located so that it fits behind the burner ensure it is not placed over the burner ...

Страница 9: ...als as shown That completes the coal bed assembly Go to section eleven to complete the appliance assembly Ensure the glass panel and other associated parts are fitted before lighting the appliance SECTION FIVE Replacement Parts The only user removable parts are Cast fret Top Outlet Grill Glass panel fixing clamps and fret apron Decorative Trim Refractory fuel bed components ...

Страница 10: ...hind decorative fret Note When flue length exceeds 200mm you may experience outing from cold In this case it may be necessary to remove the restrictor plate Please ensure that the flue pipe has been adequately sealed before undertaking removal of this plate MODEL Propane Gas G31 Version Category of appliance CII NOX Class 3 Efficiency Class 1 Gas Category I3P Gas Type G31 Propane Gas Gas Pressure ...

Страница 11: ...ND BRITISH STANDARDS B S 5871 PART 2 B S 5440 PART 1 B S 6891 B S 1945 Note This appliance must be installed to current versions of the above standards and include any relevant amendments THE BUILDING REGULATIONS ISSUED BY THE DEPARTMENT OF THE ENVIRONMENT THE BUILDING STANDARDS SCOTLAND CONSOLIDATED REGULATIONS ISSUED BY THE SCOTTISH DEVELOPMENT OFFICE PRIOR TO THE INSTALLATION ENSURE THAT THE LO...

Страница 12: ...s as described in Section 10 GENERAL REQUIREMENTS The flue and air duct length must be between 100mm to 1metre The fire is supplied with a standard pipe length of 535mm to be cut in half to make a flue and air duct length of 267mm The flue and air duct must not accommodate any bends Other lengths of flue and air duct are available The flue outlet must terminate on a suitable outside wall The minim...

Страница 13: ...combustible surround should not be less than 800 mm provided fire is central to the surround and sides do not project more than 150 mm When vertical side forward projection is increased by 12 5 mm add 50 mm to inside width of surround Check with the supplier or manufacturer that the surround meets 1500 C minimum rating attention should especially be given to man made materials such as resin When i...

Страница 14: ... a horizontal line at a height of 555mm above the hearth line joining the two outside lines together Mark the position for a lintel above the top horizontal line Mark two short horizontal lines so they cross the centre line one at 105mm and the second at 480mm above hearth level line These are the centre points for the air duct and flue holes Using a long masonry drill make two pilot holes complet...

Страница 15: ... so that it seals to both the flue pipe and the air duct use flue seal or fire cement to ensure air tight seal Drill through the four holes in the outer wall terminal plate and fix back to the wall using plugs and screws Position the outer terminal cover and fix to wall terminal plate with the four screws provided If the flue outlet is fitted below 2m from the floor or a balcony then the flue guar...

Страница 16: ...al taking account of the relative gas regulations appertaining to a gas pipe in a cavity Permanently fix the deep rebated surround in position and pack the void behind the fascia panel of the deep rebated surround with Rockwool Pack 150mm thickness of Rockwool over the appliance top and side if it is fitted into a dummy chimneybreast and fill any space between the appliance and the outside wall Po...

Страница 17: ...e 200mm diameter must be fitted to these clearance holes To ensure that any condensation formed on the duct pipes does not drip on to the inner wall a length of galvanised wire must wrapped around each flue pipe and secured in position by twisting the ends together Ensure that the twisted ends are located at the bottom of the pipes and the wire is centrally located within the cavity The vapour bar...

Страница 18: ...nclosed in a gas tight sleeve It must be sealed at the point at which the sleeved installation pipe enters the fire The Gas Safety Installation and Use Regulations Certificate of exemption number 1 of 1996 Where the pipe enters the fire the outer sleeve must be sealed to the grommet and the pipe must be sealed to its outer sleeve using suitable mastic CHECKING GAS SOUNDNESS Complete gas connection...

Страница 19: ...et up to the appliance conforming to the requirements referred to in section one of this manual SECTION THIRTEEN Instruct and Advise the Customer Demonstrate the lighting and extinguishing procedure to the consumer user and the removal and refitting of the decorative trim for cleaning Explain that for the first few hours of the fire operating there will be an initial odour This is due to the curin...

Страница 20: ...ews on the left hand side 4 Disconnect the injector pipe from the left hand side of the gas control 5 Disconnect the pilot pipe from the underside of the pilot burner 9 Pull off the connection to the spark electrode 10 Undo the supply connection to the pressure test elbow 11 Remove the 2 connections to the micro switch 12 Remove the two screws holding the gas valve bracket to the casing 13 Pull th...

Страница 21: ...dness and re commission Replacement of the Pilot Injector 1 Undo the pilot tube nut at the pilot bracket 2 Pull the pipe gently back taking care not to damage 3 Remove the pilot injector from inside the pilot bracket 4 Clean or replace in reverse order turn on the gas supply check for soundness and re commission Replacement of the Spark Electrode 1 Remove the cable from the electrode connection 2 ...

Страница 22: ...ce must be installed by a GAS SAFE registered person 2 The appliance must be used in accordance with the users instructions 3 The appliance must be serviced annually by a GAS SAFE registered person 4 The service log must be correctly filled out and the record of annual services must be up to date and supported by receipts in each case 5 This warranty is not transferable and relates to the original...

Страница 23: ...the helpdesk Model PARAGON FOCUS RS PLUS Serial No This information can be found on the label attached to the packaging and on the data badge which is located on the appliance remove decorative front for access Retailer Name ___________________________________________ Address ________________________________ ___________________________________________ ___________________________________________ Da...

Страница 24: ...f First annual service Engineer Name Gas Safe Registration No Date of Second annual service Engineer Name Gas Safe Registration No Date of Third annual service Engineer Name Gas Safe Registration No Date of Fourth annual service Engineer Name Gas Safe Registration No We may introduce modifications to products from time to time and consequently the details given in this booklet are subject to alter...

Страница 25: ...LT5944 Iss 1 25 10 11 25 ...

Страница 26: ...TAILS Name ________________________________ Address ________________________________ Post Code TELEPHONE No PRODUCT DETAILS Model PARAGON FOCUS RS PLUS Serial No Date of Purchase This information can be found on the label attached to the packaging and on the data badge which is located on the appliance remove decorative front for access WHERE DID YOU PURCHASE THIS PRODUCT Name ____________________...

Страница 27: ...LT5944 Iss 1 25 10 11 27 ...

Страница 28: ...Burner Tray Box Assembly Air Test Completed Microswitch Check Warning Label Fire Guard Nut Spinner Installation Seal 2090 Restrictor Elbow 2189 Magnets 4 x 3048 Glass Panel Canopy 4540 Flue Assembly Terminal Guard Wall Gasket Flue Pipe Fret Plate Doughnut Seal 2 Fixing Kit Owners Book Serial Number Inspector ...

Отзывы: