Installation
2-7
3360-A2-GB20-30
March 1999
Installing the Redundant –
48 Vdc Power
Supply
To install the E1 NTU using a redundant – 48 Vdc
power supply, refer to Figure 2-11 and use the following
procedure.
To install the redundant – 48 Vdc power supply:
"
Procedure
1. Connect the black wire to the – 48 Vdc return
source B.
2. Connect the red wire to the – 48 Vdc return
source A.
3. Connect the green wire to a suitable ground.
4. Connect the orange wire to the – 48 Vdc input
source B.
5. Connect the blue wire to the – 48 Vdc input
source A.
6. Cut the white wire off at the outer insulation.
7. Plug the power connector into the E1 NTU.
1
2
3
4
5
6
BLACK
RED
GREEN
WHITE
ORANGE
BLUE
– 48 VDC RETURN B
– 48 VDC RETURN A
GROUND
– 48 VDC INPUT B
– 48 VDC INPUT A
99-14745-01
X
NTU POWER
PLUG
TO CUSTOMER-SUPPLIED BATTERY
CABLE NUMBER 3100-F1-520
Figure 2-11. –
48 Vdc Redundant Source Power Supply Pinouts
Содержание ACCULIN 3364
Страница 1: ...ACCULINK 3360 3364 AND 3365 E1 NTU OPERATOR S GUIDE Document No 3360 A2 GB20 30 March 1999 ...
Страница 8: ...ACCULINK 3360 3364 and 3365 E1 NTU iv March 1999 3360 A2 GB20 30 ...
Страница 16: ...ACCULINK 3360 3364 and 3365 E1 NTU 1 6 March 1999 3360 A2 GB20 30 ...
Страница 26: ...ACCULINK 3360 3364 and 3365 E1 NTU 2 10 March 1999 3360 A2 GB20 30 ...
Страница 64: ...ACCULINK 3360 3364 and 3365 E1 NTU 3 38 March 1999 3360 A2 GB20 30 ...
Страница 92: ...ACCULINK 3360 3364 and 3365 E1 NTU A 2 March 1999 3360 A2 GB20 30 ...
Страница 156: ...ACCULINK 3360 3364 and 3365 E1 NTU E 20 March 1999 3360 A2 GB20 30 ...
Страница 162: ...ACCULINK 3360 3364 and 3365 E1 NTU H 2 March 1999 3360 A2 GB20 30 ...
Страница 172: ...ACCULINK 3360 3364 and 3365 E1 NTU Glossary 10 March 1999 3360 A2 GB20 30 This page intentionally left blank ...