14 

Reference & Installation Manual

5  

Keyswitch Programming

The DGP-NE96 control panel can support up to 32 keyswitch zones in addition to the 96 standard zones. A keyswitch allows a user to arm or disarm a 
system by pressing a key or by switching a keyswitch ON or OFF. A keyswitch can also be used to generate a Utility Key event which can then be used to 
activate or deactivate PGM outputs connected to the DGP-NE96 system. The keyswitches are connected to the hardwired input terminals of either the 
control panel, zone expansion modules or the keypad. For installation instructions, see section 2.9 on page 2. Keyswitches must be programmed as 
described in this section (see Figure 17). 

UL Note:

 Keyswitches are not to be used in UL Listed systems.

Figure 17: Keyswitch Programming

5.1 Keyswitch Numbering

S

ECTIONS

 [0501] 

TO

 [0532]

Keyswitch Numbering allows you to assign any hardwired input in the 
system to any of the 32 keyswitch zones in the control panel. It identifies 
where the keyswitch is connected and which keyswitch zone is assigned to 
the keyswitch (see Figure 18).

Figure 18: Example of Keyswitch Numbering

5.2 Keyswitch Definitions

Keyswitch Definitions determine how the control panel reacts when a 
keyswitch is activated.

5.2.1 Keyswitch Disabled

S

ECTIONS

 [0601] 

TO

 [0632]: F

IRST

 

DIGIT

 = 0

Disables keyswitch input.

5.2.2 Momentary Keyswitch

S

ECTIONS

 [0601] 

TO

 [0632]: F

IRST

 

DIGIT

 = 1

To arm a partition using the Momentary Keyswitch, turn on the keyswitch for 
approximately three seconds then turn it off. Repeating this sequence will 
disarm the system. The selected Keyswitch Option (see section 5.4) 
determines the type of arming. 

5.2.3 Maintained Keyswitch

S

ECTIONS

 [0601] 

TO

 [0632]: F

IRST

 

DIGIT

 = 2

To arm a partition using the Maintained Keyswitch, turn the switch from the 

ON

 to the 

OFF

 position. To disarm a partition set the keyswitch in the 

ON

 

position. The selected Keyswitch Option (see section 5.4 on page 15) 
determines the type of arming. If the keyswitch’s Arm Only option is 
enabled, the control panel will not perform any action when the switch is in 
the on position.

 

Press & hold the 

[0]

 key

Enter your 

[

INSTALLER

 

CODE

]

Enter 4-digit 

[

SECTION

]

Keyswitch Numbering

Sections 

[0501]

 to 

[0532]

 represent 

keyswitches 1 to 32 respectively

Keyswitch Parameters

Sections 

[0601]

 to 

[0632]

 represent 

keyswitches 1 to 32 respectively

Enter the module’s 8-digit 

[

SERIAL

 

NUMBER

]

 where the 

keyswitch is installed

Enter the 3-digit 

[

INPUT

 

NUMBER

]

 where the 

keyswitch is connected

Keyswitch Definition

First Digit

Keyswitch Partition 

Assignment

Second Digit

Keyswitch Options

Feature Select

Press 

[

ENTER

]

Keyswitch Definitions

[0] Disabled (default)
[1]

 Momentary Keyswitch

[2]

 Maintained Keyswitch

[3]

 Generates a Utility Key Event on Open

[4]

 Generates a Utility Key Event on Open & Close

Keyswitch Partition Assignment

[0] Not assigned to partition(s) (default)
[1]

 Assigned to partition 1

[2]

 Assigned to partition 2

[3]

 Assigned to partition 3

[4]

 Assigned to partition 4

[5]

 Assigned to partition 5

[6]

 Assigned to partition 6

[7]

 Assigned to partition 7

[8]

 Assigned to partition 8

Keyswitch Options

Default = All OFF
[1]

 to 

[3]

 = Future Use

[4]

 Stay/Instant Disarm

[5]

 Arm Only

[6]

 Stay Arming

*

[7]

 Force Arming

*

[8]

 Instant Arming

*

*

 Select one only; if all are OFF, defaults to regular 

arming.

Select one 

only

Select one 

only

Set 

options

Control Panel

SN#: 020000A2

Keyswitch B

Keyswitch C

                         Keyswitch
                            Zone #

Section

Serial#

Input#

   Keyswitch A:        1 =

[0501]

020000A2

001

   Keyswitch B:        2 =

[0502]

34000041

002

   Keyswitch C:        3 =

[0503]

34000041

006

Input

 2

Input

 6

Keyswitch A

Input

 1

Input Terminals

1    2    3    4    5    6    7    8

C

OMMUNICATION

 N

ETWORK

Zone Expansion Module

SN#: 34000041

Input Terminals

1     2     3     4     5     6     7     8

Combus

Содержание DIGIPLEX DGP-NE96

Страница 1: ...V1 5 96 Zone Expandable Security and Access Control Panel DGP NE96 Reference and Installation Manual DGP NE96 www paradox ca...

Страница 2: ......

Страница 3: ...e 16 Restrict Arming on Module Troubles 16 Timed Auto Arming 16 No Movement Auto Arming 17 Auto Arming Options 17 Switch To Stay Arming 17 Always Force Arm when Regular Arming 17 Follow Zone Switches...

Страница 4: ...evels 36 Access Schedules 36 Backup Schedules 37 Holiday Programming 37 Schedule Tolerance Window 37 Door Access Mode 37 Code Access 37 Card and Code Access 37 Skip Exit Delay When Arming With Access...

Страница 5: ...the CTR 21 approval are available as an option only 1 1 Features Digital combus Provides constant power supervision and two way communication between the control panel and all its modules Supports up...

Страница 6: ...a 12Vdc 4Ah rechargeable acid lead or gel cell backup battery YUASA model NP7 12 recommended as shown in Figure 3 on page 3 Connect the backup battery after applying AC power When installing verify pr...

Страница 7: ...resistor as close as possible to the bell A resistor is not required for sirens The bell output will shut down if the current exceeds 3A Bell Siren 1K9 resistor Bell Siren 1K9 resistor Transformer Re...

Страница 8: ...ion Module DGP2 ZX1 _______ X 14PU __________ PU 4 Zone Hardwire Module APR3 ZX4 _______ X 28PU __________ PU 8 Zone Hardwire Module APR3 ZX8 _______ X 28PU __________ PU Wireless Module OMN RCV3 ____...

Страница 9: ...rdwired input terminals for use with traditional hardwired non combus door contacts smoke detectors and or motion detectors The control panel also supports several hardwire zone expansion modules Devi...

Страница 10: ...nsion Plug in Device DGP2 ZX4 provides four additional hardwired input terminals 8 zones with ATZ enabled It connects directly to the control panel through its on board EXPANSION connector as shown in...

Страница 11: ...ote Not to be used with UL Listed systems 2 17 2 ESL CleanMe Installation The DGP NE96 control panel supports ESL smoke detectors that have the CleanMe feature Connect ESL smoke detectors like the sta...

Страница 12: ...ored in the RTC every hour If the times are different the DGP NE96 will reset its internal clock to the time saved in the RTC The RTC uses a 3V lithium battery CR2032 with a battery life of 11 years C...

Страница 13: ...he next section Press the right action key Exit to revert to the preceding step or press the left action key Clear to erase the current data 3 4 1 Feature Select Programming Most of the options are pr...

Страница 14: ...d to it Enter the module s 3 digit INPUT NUMBER where the hardwire device is connected NOTE For addressable PIRs door contacts and keypads no input is required Zone Definition First Digit Zone Partiti...

Страница 15: ...ters through the entry point to disarm the system 4 3 4 Instant Zones SECTIONS 0101 TO 0196 FIRST DIGIT 4 When an armed Instant zone opens the control panel immediately generates an alarm Instant zone...

Страница 16: ...ction 4 3 4 on page 11 When a Stay Delay zone is armed using the Stay or Instant arming methods and the zone is triggered the control panel will not generate an alarm until the programmed Stay Delay e...

Страница 17: ...e into effect until the Input Speed elapses The control panel will not display and or respond to an open zone until the Input Speed elapses to prevent glitches from causing an alarm or unnecessary rep...

Страница 18: ...tion using the Maintained Keyswitch turn the switch from the ON to the OFF position To disarm a partition set the keyswitch in the ON position The selected Keyswitch Option see section 5 4 on page 15...

Страница 19: ...ing the security system into eight completely independent systems Therefore each keyswitch must be assigned to one partition as shown in Figure 17 on page 14 For details on Partitioning see section 11...

Страница 20: ...le if options 1 2 and 5 are ON in section 3035 the control panel prevents arming if it detects an AC or battery failure on the control panel or on a module connected to the combus 6 9 Timed Auto Armin...

Отзывы: