8

 

Reference & Installation Manual

smoke detector sends a CleanMe

TM

 signal, the control panel will 

generate a Zone Fault trouble and if programmed will transmit the 
Fire Loop report code to the monitoring station. The trouble will be 
cleared if there is no CleanMe

TM

 signal for 255 seconds. If an 

alarm occurs, the trouble will be cleared until it is detected again.

Figure 10: PGM1 2-wire Smoke Detector Input

2.15.3 Smoke Detector Installation (4-Wire)

Connect the 4-wire smoke detectors and a relay as shown in 
Figure 11. Recommended: The System Sensor model 2112/24D 
smoke detectors. To comply with UL955, the 4-wire smoke 
detectors must be installed using 18 gauge wire. In the event 
power is interrupted, the relay will cause the control panel to 
transmit the Fire Loop Trouble report if programmed in section 
[707]. To reset (unlatch) the smoke detector after an alarm, verify 
that the negative (-) of the smoke detector is connected to a PGM 
as shown in Figure 11. Then program the PGM with the “Smoke 
Reset” activation event (see section 10.1 on page 30) to interrupt 
power to the smoke detector for four seconds when the [

CLEAR

] 

and [

ENTER

(LCD keypads) or [

*

] and [#] (Grafica keypads) keys 

are pressed and held for two seconds.

Figure 11: Fire Zones 

It is recommended that all 2-wire and 4-wire smoke 
detectors be connected in a daisy chain configuration.

PGM1 becomes 
input #255

When using ESL smoke detectors with the 
CleanME™ feature, do not connect more than 
20 detectors in parallel.

Single Fire Zone Connections Only

If the ATZ feature is enabled, do not use the extra 

input (i.e. in the above example, input 009 cannot be 

used as a zone).

Содержание Digiplex DGP-848

Страница 1: ...Digiplex Control Panel DGP 848 V4 1 Reference and Installation Manual Includes DGP2 641BL RB Installation Instructions DGP 848...

Страница 2: ......

Страница 3: ...ch Features 20 Exit Delay 20 Keypad Lock out Feature 20 Maximum Bypass Entries 21 Display Bypass If Armed 21 Bell Squawk 21 Ring back 21 Switch To Stay Arming 21 Always Force Arm When Regular Arming 2...

Страница 4: ...Access Levels 42 Schedules 42 Holiday Programming 42 Logging Access Control Events 42 Global Access Door Features 43 WinLoad Software 44 Answering Machine Override 44 Ring Counter 44 Panel Identifier...

Страница 5: ...ne combus for up to 95 modules All modules have Plug and Play capability Connect modules up to 3000ft 914m from the panel Full supervision and sabotage proof technology without additional wiring Up to...

Страница 6: ...nds If the battery is disconnected if its capacity is too low or if the battery voltage drops to 10 5 volts or less when there is no AC the Battery Trouble message will appear in the Trouble Display A...

Страница 7: ...To metallic enclosure To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals COMBUS AUX POWER Refer to transformer req...

Страница 8: ...ontact Modules DGP2 ZC1 _______ X 30mA __________ mA 1 Zone Expansion Modules DGP2 ZX1 _______ X 30mA __________ mA 4 Zone Expansion Modules APR3 ZX4 _______ X 30mA __________ mA 8 Zone Expansion Modu...

Страница 9: ...0ft Magellan Module MG RCV3 A 35mA LCD Keypad DGP2 641BL D 110mA 15m 50ft 7 5m 25ft 7 5m 25ft 15m 50ft Motion Detector Module DGP2 70 E 30mA LED Keypad DGP2 648 F 110 mA LED Keypad DGP2 648 G 110 mA A...

Страница 10: ...would exceed the system s capacity For information on how to assign a detection device to a zone in the control panel please refer to Zone Programming on page 11 Before connecting a module to the cont...

Страница 11: ...shown in Figure 3 on page 3 2 14 Keyswitch Connections Connect the keyswitches to the keypad control panel or Zone Expansion Module s hardwired input terminals as shown in Figure 9 Once a keyswitch i...

Страница 12: ...elay will cause the control panel to transmit the Fire Loop Trouble report if programmed in section 707 To reset unlatch the smoke detector after an alarm verify that the negative of the smoke detecto...

Страница 13: ...the right action key Exit on Grafica keypads as many times as needed to return to the desired screen Please note that a module s serial number can be located on the module s PC board or it may already...

Страница 14: ...that the write protect jumper is on 3 Enter section 965 to copy the contents of the panel except sections 001 to 048 device serial numbers and 049 to 056 keyswitch serial numbers to the key 966 to co...

Страница 15: ...esent zones 1 to 48 respectively Zone Parameters Sections 101 to 148 represent zones 1 to 48 respectively Enter the 8 digit SERIAL NUMBER of the addressable detection device or module that has a hardw...

Страница 16: ...ry Delay 1 Timer 230 Entry Delay 2 Timer 231 Entry Delay 3 Timer 232 Entry Delay 4 Timer 233 Please note these are the same timers used for Stay Delay zones see section 4 2 9 on page 13 Entry Delay zo...

Страница 17: ...lay 4 Timer in section 233 Please note that the Entry Delay Timers are the same timers used for Entry Delay zones 4 3 Zone Partition Assignment SECTIONS 101 TO 148 SECOND DIGIT 1 TO 4 The control pane...

Страница 18: ...digit delay value 010 to 255 seconds into section 200 Fire Zones cannot be set as Intellizones 4 4 7 Delay Alarm Transmission SECTIONS 101 TO 148 OPTION 8 When an alarm condition occurs on a zone wit...

Страница 19: ...Panel 15 Table 5 Hebrew Keypad Letter Assignment Table 6 Russian Keypad Letter Assignment Table 7 Special Characters Catalogue Table 8 Hebrew Special Characters Catalogue Table 9 Russian Special Chara...

Страница 20: ...t 004 speed 205 Panel Terminal 5 Input 005 speed 206 Panel Terminal 6 Input 006 speed 207 Panel Terminal 7 Input 007 speed 208 Panel Terminal 8 Input 008 speed 209 Panel Doubler 1 Input 009 speed 210...

Отзывы: