12
Reference & Installation Manual
4.1 Zone Numbering
S
ECTIONS
[001]
TO
[048]
The Zone Numbering feature allows you to assign any detection
device in the system to any of the 48 zones. This feature tells the
control panel where the device is connected and which of the 48
zones is assigned to that device (Figure 14 on page 12).
•
To assign an addressable detection device connected to the
combus, program the detector's serial number into the section
corresponding to the desired zone (i.e. program zone 34 in
section [034]).
•
To assign a detection device connected to a module or control
panel's hardwired input terminal, program the module's or
control panel's serial number and the input number where the
device is connected into the section corresponding to the
desired zone. Refer to the appropriate module's Installation
Guide for details of its input numbers. Note: An input number is
not required for motion detectors, keypad zones, and the
Access Control Module (DGP2-ACM1P).
If PGM1 is defined as a smoke detector input (see
section 10.4 on page 31), the control panel will
recognize it as input # 255.
Figure 14: Zone Numbering
4.1.1 Clearing a Zone’s Numbering
For LCD keypads:
1)
Enter a section number between [001] and [048].
2)
Press [0] and then [
ENTER
] to save and exit.
For Grafica keypads:
1)
Enter a section number between [001] and [048].
2)
Press [0] to clear the serial number.
3)
Using Grafica’s scroll keys, highlight the input number and
then press [0] to clear the data.
4)
Press Grafica’s center action key (Save) to save and exit.
4.2 Zone Definitions
Select one of the 15 available zone definitions described below
(also refer to Figure 13 on page 11).
4.2.1 Zone Disabled
S
ECTIONS
[101]
TO
[148]: F
IRST
DIGIT
= 0
Disables the corresponding zone. All zones are disabled by
default.
4.2.2 Entry Delays 1 to 4
S
ECTIONS
[101]
TO
[148]: F
IRST
DIGIT
= 1
TO
4
When an armed zone defined as an Entry Delay opens, the control
panel will not generate an alarm until the programmed Entry Delay
Timer has elapsed. A zone can be defined with one of four Entry
Delays. Each Entry Delay is associated with an Entry Delay Timer.
To program the Entry Delay Timer, key in the desired 3-digit delay
value (000 to 255 seconds) into the corresponding section:
•
Entry Delay 1 Timer: [230]
•
Entry Delay 2 Timer: [231]
•
Entry Delay 3 Timer: [232]
•
Entry Delay 4 Timer: [233]
Please note these are the same timers used for Stay Delay zones
(see section 4.2.9 on page 13). Entry Delay zones are commonly
used at the entry/exit points of the protected area (i.e. front/back
door or garage). Using different Entry Delays is useful when, for
example, one entry point requires a longer delay than the other
entry point or in a partitioned system where each partition may
require a different Entry Delay.
4.2.3 Follow Zones
S
ECTIONS
[101]
TO
[148]: F
IRST
DIGIT
= 5
If an armed Follow zone opens, the control panel will immediately
generate an alarm. If an armed Entry Delay zone (see section
4.2.2) opens before the Follow zone, the control panel will wait until
the end of the Entry Delay before generating an alarm. If more than
one Entry Delay zone opens before the Follow zone, the control
panel will wait until the end of the first Entry Delay before
generating an alarm.
4.2.4 Instant Zones
S
ECTIONS
[101]
TO
[148]: F
IRST
DIGIT
= 6
When an armed Instant zone opens, the control panel immediately
generates an alarm. Instant zones are commonly used for
windows, patio doors, skylights and other perimeter type zones.
4.2.5 24Hr Buzzer Zones
S
ECTIONS
[101]
TO
[148]: F
IRST
DIGIT
= 7
Whenever a 24Hr Buzzer zone opens, whether the zone is armed
or disarmed, the control panel will activate the keypad buzzer to
indicate that the zone was breached. The control panel will report
the alarm, but will not enable the bell/siren output. Enter any valid
access code on the keypad to stop the buzzer.
The keypads must be assigned to the same partition as
the 24Hr Buzzer zone. Otherwise, the buzzer will not
activate.
4.2.6 24Hr Burglary Zones
S
ECTIONS
[101]
TO
[148]: F
IRST
DIGIT
= 8
Whenever a 24Hr Burglary zone opens, whether the system is armed
or disarmed, the control panel will immediately generate an alarm.
4.2.7 Delayed 24Hr Fire Zone
S
ECTIONS
[101]
TO
[148]: F
IRST
DIGIT
= 9
The Delayed 24Hr Fire Zone definition described in Figure 15 on
page 13 is commonly used in residential homes where a smoke
detector often generates false alarms (i.e. cigarette smoke, burning
bread, etc.). When a zone is programmed as a Fire zone, the zone
becomes normally open and requires an EOL resistor. The zone
will not function as normally closed.
The keypads must be assigned to the same partition as
the Delayed 24Hr Fire zone for the buzzer to activate.
Содержание Digiplex DGP-848
Страница 2: ......