DGP-848 Control Panel

 

11

4  

Zone Programming

All detection devices connected to the control panel, keypads and zone expansion modules must be assigned to a zone and that zone must 
be defined as described in this section: 

Zone Numbering [001] to [048]:

Serial number of the device/module

Input number of the device/module

Zone Parameters [101] to [148]:

Zone Definition

Zone Partition Assignment

Zone Options

The Zone Numbering feature is used to individually assign each detection device to any desired zone in the Digiplex system (see section 
4.1 on page 12). 
The Zone Parameters define the type of zone, the zone's partition assignment and how the control panel will react when 
an alarm condition occurs on that zone (see section 4.2 on page 12 to section 4.4 on page 13). For more information on the installation of 
devices and modules, please refer to Figure 3 on page 3 or to their respective Installation Guides.

Figure 13: Zone Programming

Press & hold the 

[0] key

Key in the

 [

INSTALLER

 

CODE

]

Key in 3-digit

[

SECTION

]

Zone Numbering

Sections [001] to [048] represent 

zones 1 to 48 respectively

Zone Parameters

Sections [101] to [148] represent 

zones 1 to 48 respectively

Enter the 8-digit [

SERIAL

 

NUMBER

] of the addressable 

detection device or module that 

has a hardwire device 

connected to it.

Enter the module’s 3-digit [

INPUT

 

NUMBER

] where the hardwire 

device is connected.

NOTE: An input number is not 
required for motion detectors, 
keypad zones, and the Access 
Control module(DGP2-ACM1P)

Zone Definition

First Digit

Zone Partition 

Assignment
Second Digit

Zone Options
Feature Select

Press [

ENTER

]

Select 

one only

Select one only

Select one 

or more

Zone Definitions

0 - Disabled (Default)
1 - Entry Delay 1

8 - 24Hr Burglary

2 - Entry Delay 2

9 - Delayed 24Hr Fire

3 - Entry Delay 3

A - Standard 24Hr Fire

4 - Entry Delay 4

B - Stay Delay 1

5 - Follow

C - Stay Delay 2

6 - Instant

D - Stay Delay 3

7 - 24Hr Buzzer

E - Stay Delay 4

Zone Partition Assignment

1 - Zone Assigned to Partition 1 (Default)
2 - Zone Assigned to Partition 2
3 - Zone Assigned to Partition 3
4 - Zone Assigned to Partition 4

Zone Options

[1] Auto Zone Shutdown
[2] Bypass Zone (Default)
[3] Stay Zone
[4] Force Zone
[5]  [6]

Zone Alarm Type

off

off

Audible Alarm (steady)

off

on

Audible Alarm (pulsed)

on

off

Silent Alarm

on

on

Generates only a report

[7] Intellizone
[8] Delay before transmission

Содержание Digiplex DGP-848

Страница 1: ...Digiplex Control Panel DGP 848 V4 1 Reference and Installation Manual Includes DGP2 641BL RB Installation Instructions DGP 848...

Страница 2: ......

Страница 3: ...ch Features 20 Exit Delay 20 Keypad Lock out Feature 20 Maximum Bypass Entries 21 Display Bypass If Armed 21 Bell Squawk 21 Ring back 21 Switch To Stay Arming 21 Always Force Arm When Regular Arming 2...

Страница 4: ...Access Levels 42 Schedules 42 Holiday Programming 42 Logging Access Control Events 42 Global Access Door Features 43 WinLoad Software 44 Answering Machine Override 44 Ring Counter 44 Panel Identifier...

Страница 5: ...ne combus for up to 95 modules All modules have Plug and Play capability Connect modules up to 3000ft 914m from the panel Full supervision and sabotage proof technology without additional wiring Up to...

Страница 6: ...nds If the battery is disconnected if its capacity is too low or if the battery voltage drops to 10 5 volts or less when there is no AC the Battery Trouble message will appear in the Trouble Display A...

Страница 7: ...To metallic enclosure To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals COMBUS AUX POWER Refer to transformer req...

Страница 8: ...ontact Modules DGP2 ZC1 _______ X 30mA __________ mA 1 Zone Expansion Modules DGP2 ZX1 _______ X 30mA __________ mA 4 Zone Expansion Modules APR3 ZX4 _______ X 30mA __________ mA 8 Zone Expansion Modu...

Страница 9: ...0ft Magellan Module MG RCV3 A 35mA LCD Keypad DGP2 641BL D 110mA 15m 50ft 7 5m 25ft 7 5m 25ft 15m 50ft Motion Detector Module DGP2 70 E 30mA LED Keypad DGP2 648 F 110 mA LED Keypad DGP2 648 G 110 mA A...

Страница 10: ...would exceed the system s capacity For information on how to assign a detection device to a zone in the control panel please refer to Zone Programming on page 11 Before connecting a module to the cont...

Страница 11: ...shown in Figure 3 on page 3 2 14 Keyswitch Connections Connect the keyswitches to the keypad control panel or Zone Expansion Module s hardwired input terminals as shown in Figure 9 Once a keyswitch i...

Страница 12: ...elay will cause the control panel to transmit the Fire Loop Trouble report if programmed in section 707 To reset unlatch the smoke detector after an alarm verify that the negative of the smoke detecto...

Страница 13: ...the right action key Exit on Grafica keypads as many times as needed to return to the desired screen Please note that a module s serial number can be located on the module s PC board or it may already...

Страница 14: ...that the write protect jumper is on 3 Enter section 965 to copy the contents of the panel except sections 001 to 048 device serial numbers and 049 to 056 keyswitch serial numbers to the key 966 to co...

Страница 15: ...esent zones 1 to 48 respectively Zone Parameters Sections 101 to 148 represent zones 1 to 48 respectively Enter the 8 digit SERIAL NUMBER of the addressable detection device or module that has a hardw...

Страница 16: ...ry Delay 1 Timer 230 Entry Delay 2 Timer 231 Entry Delay 3 Timer 232 Entry Delay 4 Timer 233 Please note these are the same timers used for Stay Delay zones see section 4 2 9 on page 13 Entry Delay zo...

Страница 17: ...lay 4 Timer in section 233 Please note that the Entry Delay Timers are the same timers used for Entry Delay zones 4 3 Zone Partition Assignment SECTIONS 101 TO 148 SECOND DIGIT 1 TO 4 The control pane...

Страница 18: ...digit delay value 010 to 255 seconds into section 200 Fire Zones cannot be set as Intellizones 4 4 7 Delay Alarm Transmission SECTIONS 101 TO 148 OPTION 8 When an alarm condition occurs on a zone wit...

Страница 19: ...Panel 15 Table 5 Hebrew Keypad Letter Assignment Table 6 Russian Keypad Letter Assignment Table 7 Special Characters Catalogue Table 8 Hebrew Special Characters Catalogue Table 9 Russian Special Chara...

Страница 20: ...t 004 speed 205 Panel Terminal 5 Input 005 speed 206 Panel Terminal 6 Input 006 speed 207 Panel Terminal 7 Input 007 speed 208 Panel Terminal 8 Input 008 speed 209 Panel Doubler 1 Input 009 speed 210...

Отзывы: