Operations Manual, HPA3, Mini Compact Outdoor SSPA
208143 REV -
15
2.2.3 RF Output Sample Port (J3) [Type N (F)]
The RF Output Sample port, J3, is located on the bottom of the amplifier as shown in
Figure
2-1
. This connector provides a -40 dBc coupled sample of the amplifier’s output signal. It is a
type N female connector.
2.2.4 Monitor & Control Port (J4) [MS3112E18-32S]
The M&C (Monitor and Control) connector is the primary input for controlling the amplifier and
monitoring fault conditions. It is a 32-pin circular connector, MS3112E18-32S. It requires a
mating connector, MS3116F18-32P, which is supplied with the unit. The pin-out for this
connector is described in
Table 2-2
on the following page.
The Mini Compact Outdoor Amplifier has no on/off switch or circuit breaker in the AC Input
path. As soon as AC power is applied to J7, the unit’s power supplies and microcontroller are
enabled and the cooling fans should begin to spin.
However, the internal amplifier module
is disabled until the Mute Line Input (J4, Pin B) is pulled to Ground (J4, Pin V).
If it is
desired to have the RF enabled every time the AC input is applied, a permanent connection
can be made between J4, Pin B and J4, Pin V.
2.2.4.1 Alarms on J4
A variety of alarm signals are present at the M&C connector, J4. Both Form-C relays and
open collector outputs are available.
2.2.4.1.1 Summary Alarm (J4) Form C Contacts
The Summary Alarm is accessible in both Form C relay and open collector format. The
Form C relay is “energized” under normal operating conditions and “de-energized”
when a Fault condition exists.
2.2.4.1.2 Auxiliary Alarm (J4) Form C Contacts
The Auxiliary Alarm relay is an end user alarm that can be used to signal an alarm
condition that is dependent on the state of the Auxiliary Input (J4-Pin P).
The Auxiliary Input is a contact closure to ground. When this input is pulled to ground
the Auxiliary Alarm relay is energized (Normal State). When the Auxiliary Input is open
circuited the Auxiliary Alarm relay is de-energized (Alarm State).
2.2.4.1.3 Open Collector Alarm Outputs (J4)
The open collector alarm outputs will require external pull-up resistors (unless
connected to the Auxiliary Input). They are capable of sinking up to 20mA current at 30
VDC. The open collector outputs are pulled to ground under normal operating condi-
tions and switch to high impedance state during an alarm condition.
•
Auxiliary Alarm: follows state of Auxiliary Input as described above
Содержание RA 5785
Страница 8: ...8 208143 REV Operations Manual HPA3 Mini Compact Outdoor SSPA THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...12 208143 REV Operations Manual HPA3 Mini Compact Outdoor SSPA THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 46: ...46 208143 REV Operations Manual HPA3 Mini Compact Outdoor SSPA THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 56: ...56 208143 REV Operations Manual HPA3 Mini Compact Outdoor SSPA THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 82: ...82 208143 REV Operations Manual HPA3 Mini Compact Outdoor SSPA...