background image

21

20

LOAD SHEDDING FUNCTION

The output receptacles are electrically wired into two segments to support the
"Load Shedding Function" (Labeled Load 1 & Load 2).  The user can control
the two segments individually or both at the same time.  The Load Shedding
Function is controllable by the Power Monitoring Software or the SNMP card.

NOTE:

  The output segment labeled 'Always On' does not support the "Load

Shedding Function".

EMERGENCY POWER OFF (EPo) FUNCTION

Connect one end of the RJ11 cable to the REPO port and the other end of the
RJ11 cable to the EPO switch.  In the AC or the Battery mode short pin4 to
pin5 for approximately 0.5-seconds to shutdown the UPS.  The UPS must be
turned on to restart the UPS.  The LCD screen will display EPo for this func-
tion.

The LCD screen will include dedicated icons for the following information:

AC Mode / AVR Mode (Boost and Buck: The AC mode icon will flash)
On-Battery
Weak/Bad Battery
UPS Fault
SWF (Site Wiring Fault)
Overload
EPo (Emergency Power Off)

The LCD backlight that will turn on when the UPS is turned on.  After approxi-
mately 20-seconds the backlight will turn off to conserve energy.  When an
event (alarm) occurs, such as going to the battery mode, the backlight will turn
on for approximately 20-seconds to alert the user that an event has occurred
and then the backlight will turn off.  While the Scroll button is in use the
backlight will remain on.  Approximately 20-seconds after the Scroll button has
stopped being used the backlight will turn off.

POWER MONITORING SOFTWARE

This UPS series supports Minuteman's SentryHD power monitoring software.
Please go to our web site at www.minutemanups.com/support, then look under
Downloads, and then Software Download Center.  Please download (Free of
Charge) the latest version of the Minuteman SentryHD software.  The USB
communications protocol is HID.  The HID USB driver comes standard in the
Windows OS.  Simply connect the USB cable to the USB communications port
on the rear panel of the UPS.  Connect the other end of the USB cable to the
device that will be monitoring/controlling the UPS and then follow the prompts
on the screen.  

NOTE:

  When using the UPS's USB port with Windows XP, 7,

8 or 10 the Power Options in the Control Panel may need to be configured.

WEAK/BAD BATTERY

The UPS automatically tests the battery’s condition.  If the battery is weak, bad
or disconnected, the  Weak/Bad Battery icon will illuminate and the Battery
Capacity Bar Graph will turn off, the LCD screen will display error code E06
and the audible alarm will sound three beeps every five minutes until the bat-
tery is either reconnected or replaced.  This alarm will be repeated until the
batteries pass a self-test.  It is recommended that the UPS be allowed to
charge overnight before performing a battery test to confirm a Weak/Bad
Battery condition.

OVERLOAD

When the amount of load attached to the UPS exceeds its power rating, the
Overload icon will illuminate, the LCD scrren will display error code E02 and
the audible alarm will sound continuously (AC and Battery modes).  This alarm
will remain on until the excess load is removed or the UPS’s self protection
circuit shuts the UPS down.

To clear the overload alarm when the UPS has shutdown requires that the UPS
perform a battery test.  First remove part of the load, then turn the UPS on, the
Overload icon and the audible alarm will be on.  Second either use the Test
Button or unplug the input power cord to perform the battery test.

ALARMS

ON BATTERY

When the UPS is operating on the batteries, the AC mode icon will extinguish,
the On-Battery icon will illuminate, the LCD will display the estimated runtime
remaining and the audible alarm will sound one beep every 10 seconds.  Once
the UPS returns to the AC mode, the audible alarm will stop, the On-Battery
icon will extinguish and the AC mode icon will illuminate.

LOW BATTERY WARNING

When the batteries reach the predetermined level, the audible alarm will sound
two beeps every five seconds, the Battery Bar Graph will display the remain-
ing battery capacity and the LCD will display error code E07.  This informa-
tion is to inform the user that there is approximately two minutes of runtime
remaining before the UPS shuts down.  This condition will continue until either
AC returns or the UPS’s self protection circuit shuts the UPS down to protect
the battery from over discharging.

UPS FAULT

When the UPS detects an internal fault, the Fault icon will illuminated and an
error code will be displayed on the LCD screen,  the audible alarm will sound
continuously and the output will be turned off.  The fault condition, in some
instances, may be cleared by turning the UPS off and then on.  If the fault
condition does not clear the UPS must be sent in for service.  See the Trouble-
shooting section.

Содержание Minuteman PRO-RT 2U Series

Страница 1: ...User s Manual PRO RT 2U Series UPS Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000526 R3 ...

Страница 2: ...n 2 2 Controls and Indicators 8 3 Installation 11 4 Operation 18 5 Obtaining Service 22 6 Troubleshooting 23 7 Replacing the Battery 24 8 Specifications 28 9 Limited Product Warranty 30 A1 Declaration of Conformity 31 ...

Страница 3: ...rrectement installer le système pour atteindre son rendement maximum en toute sécurité CAUTION Connect the UPS to a two pole three wire grounded utility power AC wall outlet The receptacle must be connected to the appropriate branch protection circuit breaker or fuse Connection to any other type of recep tacle may result in a shock hazard and violate local electrical codes Do not use extension cor...

Страница 4: ...self test Once the UPS has passed its self test the UPS will be ready for normal operation When the UPS is in the AC mode Press and then release the On Off Test button during the audible alarm s first beep to turn the UPS off To perform a ten second self test With the UPS in the AC mode press and hold the On Off Test button until the audible alarm sounds four beeps and then release During the test...

Страница 5: ... prior written permission of Para Systems Given that Para Systems will continuously improve and de velop the product changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes Para Systems will make all possible efforts to secure the accuracy and the integrity of this Manual Para Systems disclaims any kinds or forms of war ...

Страница 6: ...played and the UPS will sound a constant alarm to indicate that there is an Overload condition Battery Capacity Bar Graph Displays the amount of Battery Ca pacity available in the AC and Battery mode as 20 40 60 80 100 UPS Parameters Input Voltage and Frequency Output Voltage and Frequency Connected load KVA and KW Estimated Runtime minutes AC mode and Battery mode The Multi Function On Off Test b...

Страница 7: ...ptacles are electrically wired into two segments to support the Load Shedding Function Labeled Load 1 Load 2 7 TheAlways On Battery Backup output receptacles LabeledAlways On does not support the Load Shedding Function NOTE The locking recptacle is only on the PRO2000RT2U model 8 The option slot is for option cards 9 The rackmount brackets are for mounting the UPS to the rack 10 The RJ11 45 modula...

Страница 8: ...unstable due to the weight distribution 2 The Rackmount Configuration is complete See Connecting your Equipm ent CONNECTING THE BATTERIES QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNINGS and CAUTIONS before attempting to con nect the batteries Use two or more people when installing the UPS the UPS is extremely heavy 1 Remove the UPS from the shipping box and place on a flat surface...

Страница 9: ...R CONFIGURATION The tower configuration allows the user to install the UPS in the up right position The tower brackets are provided with the UPS Use two or more people when installing the UPS the UPS is extremely heavy 1 Once the location of the UPS has been determined place the UPS on a flat sur face remove the rackmount brackets from the UPS and then place the tower br ackets in the desired loca...

Страница 10: ...electrical device into the output receptacles of the UPS COAX PROTECTION CONNECTION OPTIONAL Connect a cable modem CATV converter DSS receiver or DVR to the coax connectors on the rear panel of the UPS This connection will require another coax cable The cable coming from the coax service is connected to the port marked IN The equipment to be protected is connected to the port marked OUT NOTE Conne...

Страница 11: ... will blink During normal AC operation the UPS will quietly and confidently protect your system from power anomalies The UPS will charge the batteries with the UPS in the on or off position when the UPS is plugged into the wall outlet and there is an acceptable AC voltage present 90 150VAC When a blackout brownout or an overvoltage condi tion occurs the UPS will transfer to the battery mode the On...

Страница 12: ...y tests the battery s condition If the battery is weak bad or disconnected the Weak Bad Battery icon will illuminate and the Battery Capacity Bar Graph will turn off the LCD screen will display error code E06 and the audible alarm will sound three beeps every five minutes until the bat tery is either reconnected or replaced This alarm will be repeated until the batteries pass a self test It is rec...

Страница 13: ...or the UPS Check the specifications Chapter 5 Obtaining Service IF THE UPS REQUIRES SERVICE 1 Use the Troubleshooting section to eliminate obvious causes 2 Verify there are no tripped circuit breakers and that the batteries are good A tripped circuit breaker and defective batteries are the most common iss ues 3 Call your dealer for assistance If you cannot reach your dealer or if they cannot resol...

Страница 14: ...battery system can present a risk of electrical shock These batteries produce sufficient current to burn wire or tools very rapidly produc ing molten metal Observe these precautions when replacing the batteries 1 Remove watches rings or other metal objects 2 Use hand tools with insulated handles 3 Wear protective eye gear goggles rubber gloves and boots 4 Do not lay tools or other metal parts on t...

Страница 15: ...IG 2 FIG 3 7 Disconnect the battery connectors FIG 2 8 Remove the four retaining screws for the battery retaining bracket FIG 2 9 Remove the battery retaining bracket and set aside 10 Grasp the battery pull tab and gently pull the battery module out of the UPS and set aside FIG 3 NOTE DO NOT use the battery wires to pull the battery module out Use Caution the battery module is heavy 11 Slide the n...

Страница 16: ...Life 3 to 5 years Environmental factors do affect battery life High temperatures poor utility power and frequent short duration discharges have a negative impact on battery life 8 hours to 90 capacity from a full load discharge Battery Type Sealed Non Spillable Maintenance Free Value Regulated LeadAcid Runtime Half Load minutes Runtime Full Load minutes SURGE PROTECTION AND FILTERING Audible Noise...

Страница 17: ... FIT NESS FORAPARTICULAR PURPOSE Some states do not permit limitation of implied warranties therefore the aforesaid limitation s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IFADVISED OF THE POSSI BILITY OF SUCH DAMAGE Specifically Para Syst...

Страница 18: ...33 32 Notes Notes ...

Отзывы: