SMARTZONE G6 UPS USER MANUAL
87
returns when the UPS changes status
because of an event or when the UPS
Display Interface is pressed.
Date and
Time
2022-01-01
and
07:00:00
Date and time
Enter the current date and time.
Settings/
Advanced/
System
Setup
Working Mode
Normal
Normal, ECO,
CF
Set up the UPS working Mode
System
Conf iguration
Single
Single
Parallel
Single is a single UPS in the system.
Parallel is 2 to 4 UPSs in a system
(available only on the 3-Phase UPS).
Input: Output
Phase
3:3
3:3
3:1
3-Phase IN and 3-Phase OUT or 3-Phase
IN and single-Phase OUT (available only on
the 3-Phase UPS).
Battery
Temperature
Sensor
Disable
Enable
Disable
An external senor cable must be connected
f rom the first EBP to the UPS.
Settings/
Advanced/
Parallel
Setup
Parallel ID
1
1-4
Each UPS in a parallel system must have a
unique ID.
Parallel Basic
Units
2
2-4
This is the number of UPS units in the
system.
Parallel
Redundancy
Units
0
1-3
The parallel system is setup f or a
redundancy parallel conf iguration, this is
the ID number of UPS unit that is the
redundant unit in the system (0 means no
redundancy).
Settings/
Advanced/
Output
Setup
Output
Frequency
Auto
Auto,
50Hz, 60Hz
Set the output frequency for the UPS.
Output
Voltage
Depends on
SKU
Depends on
SKU
Set the output voltage f or the UPS. This
setting can only be changed when the UPS
output is off.
Inverter
Voltage
Adjustment
0%
-5% to +5%
Used f or f ine tuning the output on UPS units
in the parallel system (available only on the
3-Phase UPS).
Bypass Up
Limit
264V
230V-276V
Set the bypass up limit
Bypass
Down Limit
176V
176V-220V
Set the bypass down limit
UPS Mode
Normal
Normal
、
ECO
、
CF
、
Parallel
、
Generator
Set the ups mode
Bypass
Function
Enable
Enable
、
Disable
Set the bypass function
Battery
Battery Group
1
1 to 5
Or 1 to 8
Set the number of EBP units connected to
the UPS (single-phase UPS is 1-5 and 3-