SMARTZONE G6 UPS USER MANUAL
42
Figure 29: Status Information Page 1 (3-Phase UPS)
Status Information Page 2
The main body of the second page contains status of the lock plate over the
maintenance bypass breaker in the Maintenance Bypass Switch unit, the status of the
generator dry contact points and the ambient temperature detected by the UPS. The
Maintenance Bypass Switch unit
’s MBS switch is sensed through the MAINT senor port
on the back of the 3-Phase UPS unit. The Dry MBS Switch contact indicates if the
locking plate is covering or not covering the bypass breaker in the Maintenance Bypass
Switch unit. If the plate is removed this contact point will change to
“Close”, meaning the
UPS could be switched out of the system. When there is no Maintenance Bypass
Switch unit in the system, the status of this
switch will be “Open”.
The Generator Access point is sensed through an IN dry contact port on the back of the
3-Phase UPS. The Generator Access field is available only on the 3-phase UPS units
that have built in dry contact points. When a generator is connected to the 3-phase UPS
the generator feedback must be connected to an IN dry contact point on the back of the
UPS and this contact point must be configured to Generator (see Advanced Settings).
The Ambient Temperature at the input side of the UPS (where the air enters the UPS
from the cold aisle) is measure with a temperature sensor and displayed on this page.
This is the only Status Page and the only information shown on the Status Page for the
single-phase 5-10kVA UPS units.
Press the up arrow to go to the previous Status Information page. Press the up and over
arrow to return to the Status Menu page.