SMARTZONE G6 UPS USER MANUAL
73
Figure 64: Outlet Group Control Page (Single-Phase EU UPS)
Inverter ON/OFF Page
This page has the same two banners across the top of the page as described in the
Status Menu page.
The main body of this page allows the user to turn ON and OFF the system output
inverter(s). If the system configuration is Single Mode (a system configured with only
one UPS)
, then the user my press the “Single ON” or “Single OFF” button to turn ON or
turn OFF the UPS output inverter. If the system configuration is Parallel Mode (a system
configured with 2 or more UPS unit connected in parallel), then the user should press
the
“Parallel ON” or “Parallel OFF” button to turn ON or OFF the group of parallel UPS
output inverters. The 5-10kVA Single Phase UPS units will only have a single ON and a
single OFF location, since single-phase UPS units cannot be used in a parallel
configuration mode. When the inverter(s) is turned OFF, system will then transition to
Bypass Mode, assuming bypass mode has not been previously disabled. If Bypass
Mode has been previously disabled, then the system output will shut down. Once the
Inverter OFF or ON location is pressed the action will take effect immediately.
Press the up and over arrow to return to the Common Menu page.