SMARTZONE G5 USER MANUAL
84
6. When the upload is finished, the system will reboot automatically.
Serial (Command Line Interface) Method
To access a PDU, directly connect to serial connection.
1. Copy the Panduit.fw file in /(root) directory using ftp.
2. Connect to the PDU via Serial using hypertrm. Press Enter.
3. Login by using a role with administration privileges.
4. Enter the command: sys upd all
5. The CLI will show the message: Success
6. It will show the message: System will enter upgrade mode after reboot, System
Reboot now, Are you sure? (Y/N)
7. Enter: Y
8. When the upgrade is finished, the system will reboot automatically.