SMARTZONE UPS USER MANUAL
41
Screen #
DC VRLA Settings
Content display
connected loads will tolorate. Decreasing this voltage may limit the UPS from
switching to bypass (when the input voltage is high).
S-07
Bypass Voltage Lower Limit
setting
(80 - 110)
(176 – 220)
The default Bypass Voltage Lower Limit setting is 80Vac for North American UPS
units and 176Vac for European UPS units. These values my be changed in 1Vac
increments/decrements. This value should be set to the minimum voltage that the
connected loads will tolorate. Increasing this voltage may limit the UPS from
switching to bypass (when the input voltage is low).
S-08A
Buzzer setting
(ON, OFF)
The default Buzzer setting is ON.
S-08B
Buzzer setting
(ON, OFF)
To mute all audiable alarms, set this to OFF.The Buzzer will be muted, even with
new Alerts. A speaker with a line through it will be illuminiated in the upper right
corner of all pages.