Torque Settings 

The following table shows recommended torque settings for all mechanical and electrical connections 
according to screw or nut size in inch pounds (in-lbs). 
 

Table 6: Recommended Torque Settings 

 

Screw or Nut Size 

Toque (in-lbs) 

4-40 6 
6-32 12 
8-32 22 

10-32 37 
12-24 50 

¼-20 65 

 

Required Tools  

The 

DP

O

E™

 Power System is designed to be installed with commonly available tools: 

 

  #1 & #2 flat blade and Phillips head screwdrivers  

  Torque wrench  

  7/16” socket, ¼” drive  

  Wire and cable strippers (

PANDUIT

 part number CT-100) 

  Wire and cable crimpers (such as 

PANDUIT

 part CT-1550, CT-1551, CT-1570, CT-1700 

Contour Crimp

TM

 Controlled Cycle Crimp Tools) (used for optional bulk DC connection) 

   

Site and Equipment Preparation 

Prior to unpacking the 

DP

O

E™

 Power System, note any physical package damage that could indicate 

potential damage to the contents. After removing the 

DP

O

E™

 Power System from the boxes and packing 

material, inspect for shipping and/or other damage. Any problems should be reported to 

PANDUIT

 

technical support. 
 

Table 7: 

PANDUIT

 Corp. Contact Information 

 

PANDUIT

 Technical Support 

Fax: 

1-708-444-6993 

E-mail: [email protected] 

PANDUIT

 Product Installation Instructions 

www.panduit.com/resources/install_maintain.asp

 

Worldwide Subsidiaries and Sales Offices 

www.panduit.com

 

 
Have all tools, wire, cables, hardware, etc., within easy reach. To the extent possible, ensure a clean 
(free of debris, dust, foreign material, etc.) work environment. Care should be taken in the installation 
process to prevent wire clippings from getting into the equipment.  
 

NOTE: 

If possible, the rectifiers should remained sealed in their shipping boxes until the 
chassis wiring is complete. Rectifiers should not be inserted until all 

DP

O

E™

 

components are properly connected.  

 

Содержание DPOE PN380C

Страница 1: ...ding or otherwise without written permission from PANDUIT No patent liability is assumed with respect to the use of the information contained herein Although every precaution has been taken in the pre...

Страница 2: ...ndesired operation WARNING Changes or modifications to this unit not expressly approved by the party responsible for the compliance could void the user s authority to operate this equipment WARRANTY U...

Страница 3: ...direct indirect special incidental or consequential damages whether based on contract tort or other legal theory Unless otherwise specified by PANDUIT Corp opening this product by unauthorized personn...

Страница 4: ...cuit and Current Limit 11 TROUBLESHOOTING 12 Figures Figure 1 Top View of Power Chassis with Power Rectifiers Installed 1 Figure 2 Individual AC Feed Wiring Architecture 4 Figure 3 DC Wire Diagram 5 F...

Страница 5: ...0C v Table 4 Recommended AC Circuit Breaker and Wire Sizes 4 Table 5 Minimum Recommended DC AWG for 90 C Cabling for Unprotected Outputs 6 Table 6 Recommended Torque Settings 7 Table 7 PANDUIT Corp Co...

Страница 6: ...an However 120 watts may not be enough power to support all the Powered Devices PD connected to the panel or powered midspan In these cases or in cases of multiple DPOE Power over Ethernet Systems a l...

Страница 7: ...its are shown in Table 5 Minimum Recommended DC AWG for 90 C Cabling for Unprotected Outputs respectively In practice loop voltage drop considerations will usually dictate larger than minimum safe wir...

Страница 8: ...m and typical British Thermal Units per hour BTU hr of heat dissipated from each rectifier The maximum is calculated at 90 VAC and typical is calculated at 230 VAC Table 3 Heat Dissipation Part Number...

Страница 9: ...utput Wiring Sizing There are two main considerations for sizing DC wire ampacity and voltage drop Ampacity refers to the safe current carrying level as specified by U S based organizations such as Un...

Страница 10: ...tion may be used as a battery input or as an unfused bulk output The connections require a terminal lug 1 4 single hole lug with a max tongue width of 0 63 or less such as PANDUIT part LCA4 14 L Size...

Страница 11: ...e not attached to the power harness Contact PANDUIT Technical Support for more information about connecting the redundant B Feed power PANDUIT part DPOEPWRDUAL should be used for redundant powering op...

Страница 12: ...System note any physical package damage that could indicate potential damage to the contents After removing the DPOE Power System from the boxes and packing material inspect for shipping and or other...

Страница 13: ...the DPOE Power System chassis with mounting screws in the front an optional rack mount shelf may be installed underneath the chassis on the backside of the rack to alleviate potential sagging of the...

Страница 14: ...Figure 8 Chassis Rear View AC Connections 4 40 Screws Figure 9 Securing Cord Bracket to Chassis DC Output DC connections are accomplished via the rear terminal blocks and bulk output connection as sh...

Страница 15: ...re available from PANDUIT Corp The bulk output terminals feature a break off plastic piece to prevent inadvertent contact with the terminals If using the bulk DC output feature carefully break off eac...

Страница 16: ...the backplane While pressing the latch button down use the latch handle to gently ease the rectifier into the rear connector When the rectifier is properly seated releasing the latch button will hold...

Страница 17: ...rs are properly mated Table 8 Troubleshooting Alarm Problem Possible Solution DC OK LED is extinguished This rectifier has stopped outputting power Rectifier failed Replace this unit AC OK and all LED...

Отзывы: