 Power System User Manual 

 

Part Number: PN380C 

 
 

CAUTION: 

ALWAYS FOLLOW NEC GUIDELINES AND YOUR LOCAL COMPANY 
PRACTICES WHEN SELECTING DC WIRING AND PROTECTION. 

 

Table 5: Minimum Recommended DC AWG for 90°C Cabling for Unprotected Outputs 

 shows 

recommended wire sizes based on ampacity. The maximum current rating for the chassis is 100 A

 

Re

ct

ifi

e

rs

Single hole bulk

battery connections

(¼" studs)

14 GMT Fuse

Connections

14

1

2

 

 

Figure 3: DC Wire Diagram 

 

Each chassis is equipped with 14 GMT style fuse connections and an unfused bulk DC connection 
located on the rear of the chassis

.

 The GMT fused connections are made on “lugless” terminal blocks 

with compression screws. The terminal blocks will accept wire sizes up to 12AWG.  
 
The bulk DC connection may be used as a battery input or as an unfused bulk output. The connections 
require a terminal lug (1/4” single hole lug with a max tongue width of 0.63” or less), such as 

PANDUIT

 

part # LCA4-14-L. Size wires based on the total rectifier capacity and choose conductor size according to 

Table 5: Minimum Recommended DC AWG for 90°C Cabling for Unprotected Outputs 

 

Connecting to a 

DPoE

™ Power Patch Panel or Compact 8 Midspan 

 

Each 

DP

O

E™

 Power over Ethernet System is shipped with a keyed power connector harness and two 

butt splices (

PANDUIT

 part # BSV14X) for use in connecting the panel to the power source. The butt 

splices included with the 

DP

O

E™

 Power Patch Panel will support 14 - 16 AWG solid or stranded wire. 

 

WARNING: 

Connect each separate 

DP

O

E™

 Power Patch Panel or Compact 8 Midspan to the 

rear of the 

DP

O

E™

 Power System using one of the 14 GMT-fused outputs per 

panel. 

 
Do not wire multiple untis to a single output on the 

DP

O

E™

 

Power System. 

 

 

 

 

 

5

 

 

Содержание DPOE PN380C

Страница 1: ...ding or otherwise without written permission from PANDUIT No patent liability is assumed with respect to the use of the information contained herein Although every precaution has been taken in the pre...

Страница 2: ...ndesired operation WARNING Changes or modifications to this unit not expressly approved by the party responsible for the compliance could void the user s authority to operate this equipment WARRANTY U...

Страница 3: ...direct indirect special incidental or consequential damages whether based on contract tort or other legal theory Unless otherwise specified by PANDUIT Corp opening this product by unauthorized personn...

Страница 4: ...cuit and Current Limit 11 TROUBLESHOOTING 12 Figures Figure 1 Top View of Power Chassis with Power Rectifiers Installed 1 Figure 2 Individual AC Feed Wiring Architecture 4 Figure 3 DC Wire Diagram 5 F...

Страница 5: ...0C v Table 4 Recommended AC Circuit Breaker and Wire Sizes 4 Table 5 Minimum Recommended DC AWG for 90 C Cabling for Unprotected Outputs 6 Table 6 Recommended Torque Settings 7 Table 7 PANDUIT Corp Co...

Страница 6: ...an However 120 watts may not be enough power to support all the Powered Devices PD connected to the panel or powered midspan In these cases or in cases of multiple DPOE Power over Ethernet Systems a l...

Страница 7: ...its are shown in Table 5 Minimum Recommended DC AWG for 90 C Cabling for Unprotected Outputs respectively In practice loop voltage drop considerations will usually dictate larger than minimum safe wir...

Страница 8: ...m and typical British Thermal Units per hour BTU hr of heat dissipated from each rectifier The maximum is calculated at 90 VAC and typical is calculated at 230 VAC Table 3 Heat Dissipation Part Number...

Страница 9: ...utput Wiring Sizing There are two main considerations for sizing DC wire ampacity and voltage drop Ampacity refers to the safe current carrying level as specified by U S based organizations such as Un...

Страница 10: ...tion may be used as a battery input or as an unfused bulk output The connections require a terminal lug 1 4 single hole lug with a max tongue width of 0 63 or less such as PANDUIT part LCA4 14 L Size...

Страница 11: ...e not attached to the power harness Contact PANDUIT Technical Support for more information about connecting the redundant B Feed power PANDUIT part DPOEPWRDUAL should be used for redundant powering op...

Страница 12: ...System note any physical package damage that could indicate potential damage to the contents After removing the DPOE Power System from the boxes and packing material inspect for shipping and or other...

Страница 13: ...the DPOE Power System chassis with mounting screws in the front an optional rack mount shelf may be installed underneath the chassis on the backside of the rack to alleviate potential sagging of the...

Страница 14: ...Figure 8 Chassis Rear View AC Connections 4 40 Screws Figure 9 Securing Cord Bracket to Chassis DC Output DC connections are accomplished via the rear terminal blocks and bulk output connection as sh...

Страница 15: ...re available from PANDUIT Corp The bulk output terminals feature a break off plastic piece to prevent inadvertent contact with the terminals If using the bulk DC output feature carefully break off eac...

Страница 16: ...the backplane While pressing the latch button down use the latch handle to gently ease the rectifier into the rear connector When the rectifier is properly seated releasing the latch button will hold...

Страница 17: ...rs are properly mated Table 8 Troubleshooting Alarm Problem Possible Solution DC OK LED is extinguished This rectifier has stopped outputting power Rectifier failed Replace this unit AC OK and all LED...

Отзывы: