background image

21/07/2010 

14 

MRAR 01/96 C 

5.3 Functional Sequence 
 

To understand this chapter completely it is advised that paragraphs 4.1 and 4.2 should be read first. 
 

5.3.1 Switching on the MRAR Relay 
 

If  the  circuit  breaker  to  be  supervised  is  in  the  off  position  while  switching  on  the  MRAR,  the  unit 
changes to the Inactive state when applying the auxiliary voltage. The OK LED on the front panel is not 
lit and the unit is not ready for auto reclosing. If, however, the circuit breaker is in the on position when 
applying the auxiliary voltage, the unit changes to the Reclaim Time state and remains blocked for this 
period (from 1 to 300 seconds adjustable). This is indicated by the tr LED. After the Reclaim Time has 
elapsed the unit changes to the Ready state and  auto reclosing may now be carried out. The OK  LED 
indicates this state. 
 

5.3.2 Switching on the Circuit Breaker Manually 
 

If the circuit breaker is switched manually to an un-faulted line, first the unit will remain blocked for the 
Reclaim Time (adjustable 1 - 300 seconds) and then changes to the Ready state. If the circuit breaker is 
switched  manually  to  a  faulted  line  then  the  breaker  is  switched  off  by  the  associated  protection  unit. 
The MRAR then remains in the Inactive state and reclosing is not possible. 
 

5.3.3 Switching off the Circuit Breaker Manually 
 

When switching off the circuit breaker manually, the unit changes at once from the Ready state to the 
Inactive state. The OK LED extinguishes and reclosing is not possible. 
 

5.3.4 Starting Auto-Reclosing 
 

When signals are applied to the Protection Energising or the Protection Tripping inputs, 21 and 27, the 
unit  changes  from  the  Ready  to  the  Starting  state.  The  RUN  LED  illuminates  and  the  fault  timer  (tf 
adjustable  from  0.01  to  2.05  s)  begins  to  time  out.  A  tripping  timer  (set  at  0.2  s)  is  started  when  the 
mains  protection  tripping  command  takes  place  before  the  fault  timer  has  timed  out.  The  "Start 
requirements  not  fulfilled"  is  evaluated  and  the  MRAR  is  locked  out  for  the  duration  of  the  Reclaim 
Time if there is a difference between the Mains Protection Energised/Tripped and the set Fault Time. If 
the Circuit Breaker OFF signal occurs before the tripping timer has timed out, it is evaluated as a "Start 
Condition Fulfilled" and the unit changes to the Cycle state. If, however, the OFF signal does not occur 
before the tripping timer has timed out, it will be evaluated as "Start Condition Not Fulfilled" and the 
unit is locked out for the duration of the set Reclaim Time. 
 

5.3.5 Reclosing Without Success 
 

After the start condition has been fulfilled the unit changes to the Cycle state and the Dead Time, tD, is 
started. The MRAR can be programmed to reclose between one and four times and for each reclosing a 
Dead Time has to be set, (tD1 = 0.1 - 20 s, tD2 - tD4 = 0.2 - 99.9 s). When the Dead Time has expired 
and  all  other  reclosing  conditions  have  been  fulfilled,  the  switch  on  command  is  given  to  the  Circuit 
Breaker.  The  switch  on  command  will  remain  as  long  as  the  On  signal  to  the  Circuit  Breaker    or  the 
setting of the On Impulse Timer (adjustable between 0.05 - 9.99 s). With the beginning of the switch on 
command the Reclaim Timer is started. When a new OFF signal, not a fault signal, to the circuit breaker 
appears  during  the  Reclaim  Time,  a  reclosing  has  taken  place  without  success.  The  unit  then  changes 
from the Cycle state to the Blocked state and the RUN LED extinguishes with the LO and O

I LED's 

being illuminated. 

Содержание MRAR

Страница 1: ...n 50 60 Hz V PH Vx MRAR MODEL SERIAL NO No SHOT tD2 tf tD1 tD4 tD3 tC1 tR MRI IDS PB O LO RUN OK I CB No M No L P B Engineering P B Engineering Belle Vue Works 12 14 Crompton Way Boundary Street Crawl...

Страница 2: ...Success 14 5 3 6 Successful Reclosing 15 5 3 7 Repeated Reclosing 15 5 3 8 External Blocking and Reseting 15 5 3 9 Supervision of the Circuit Breaker Ready Information 15 5 4 Operation and Release of...

Страница 3: ...21 07 2010 3 MRAR 01 96 C 8 4 System data 23 8 5 Power supply 24 9 Housing 25 9 1 Connection Details 26 10 Order Form 27...

Страница 4: ...vercurrent Relay Independent time I D M T earth directional facilities MRI V Voltage Dependent Overcurrent Relay MREF Restricted Earth Fault Relay MRAR Auto Reclosing Relay MRMF Mains Failure Relay MR...

Страница 5: ...eg the MRI I MRCS The protective functions of the MRAR are summarised as follows Independent adjustable time ranges Four digit counter for display of the completed auto reclosing High Set blocking out...

Страница 6: ...tested by the application of a high voltage power frequency input flash tested as this will cause damage to the unit Explanation of the Circuit Diagram 4 1 1 Information Inputs Using the information...

Страница 7: ...voltage to terminal 24 This blocking can only be removed by applying the auxiliary volatge to terminal 25 Blocking has priority during the simultaneous activation of inputs 24 and 25 Reserve 26 This...

Страница 8: ...2 Adjusting LED s SHOT Green Number of reclosing attempts No Red Number of AR s carried out tf Green Fault Time tD1 Green Dead Time for the first reclosing tD2 Red Dead Time for the second reclosing...

Страница 9: ...I Red CB Red LO Red No CB Off signal after protection OFF CB CB Red Dead Time closing conditions not met S E O I Red Switch was manually switched off during Reclaim Time Manu Password combination of...

Страница 10: ...hange at an increased rate The ENTER push button is used to transfer the indicated value to the internal parameter memory An unintended or unauthorised change of the selected parameter can be avoided...

Страница 11: ...relays Code jumper J2 OFF The alarm relays respond directly upon the initiation of the corresponding measuring circuit Thus an alarm signal e g for negative sequence current will be given before the r...

Страница 12: ...ot been interrupted by other faults Activation of the unit due to protection faults is also not possible in the Reclaim Time State thus no auto reclosing can take place 5 1 3 AR Ready The relay is in...

Страница 13: ...ing Signal Reclaim Time CB OFF Reclaim Time Exprired External Blocking Signal Ready CB OFF Protection Running and or Tripped CB Energy OK External Blocking Signal Starting Starting Conditions Not Fulf...

Страница 14: ...the unit changes from the Ready to the Starting state The RUN LED illuminates and the fault timer tf adjustable from 0 01 to 2 05 s begins to time out A tripping timer set at 0 2 s is started when the...

Страница 15: ...by the applying of a reset signal to terminal 25 5 3 9 Supervision of the Circuit Breaker Ready Information Because the supervision of the circuit breaker energy store responds often after the first f...

Страница 16: ...rnal blocking input was activated The AR cycle was terminated without success The circuit breaker energy is not sufficient during a switch on attempt after first attempt see also paragraph 5 3 9 The s...

Страница 17: ...21 07 2010 17 MRAR 01 96 C 5 6 Circuit Example Connection Diagram of the MRAR and MRI Together...

Страница 18: ...ime 1 tD1 Dead Time 2 tR Reclaim Time As a short circuit occurs the circuit breaker is switched off by the protecting device and the dead time counter in the MRAR starts to time out After this dead ti...

Страница 19: ...ed 5 7 3 Manual Switching On of the Circuit Breaker to Faulty Lines Protection Energised Short Circuit Protection Tripped Circuit Breaker Switch on Command 1 Manual On 2 Protection Tripped 1 2 The MRA...

Страница 20: ...ommand during the reclaim time leads to the switching off of the breaker Number of Reclosings Until Maintenance Alarm No M After a certain number of reclosings the circuit breaker must be serviced Thi...

Страница 21: ...he SELECT push button you can check all the unit set values Modification is via the UP and DOWN push buttons followed by ENTER 7 4 Checking the CB Status Input Circuit 28 15 Apply auxiliary voltage to...

Страница 22: ...2 Output Relays Number 5 Contacts 2 Voltage free changeover contacts for switch on relays 1 Voltage free change over contact for other relays 8 3 Setting Ranges and Steps Setting Parameter Setting Ran...

Страница 23: ...tection tripping command after reclosing and is interrupted by the CB Off Alarm C B Wait Time 100mS 10mS This time starts with the CB Off Alarm after an unsuccessful reclosing and is interrupted by th...

Страница 24: ...IEC 41B CO 38 Class 1 Vibration IEC 41B CO 35 Class 1 Degree of Protection Front IP52 Rear IP00 Weight Approx 2kg 8 5 Power supply Two auxiliary power supply versions are available Vaux 24V in a rang...

Страница 25: ...in close proximity and hazardous environments When the relay is inserted a leaf spring along the top edge of the module makes contact with a solidly bonded nickel plated steel strip on the interior of...

Страница 26: ...Each connection facilitates 2 pre insulated push on blades 4 8mm wide 0 8mm thick complying with BS5057 Combinations Each terminal will accept either 2 ring type connectors or 2 push on blade type co...

Страница 27: ...T C T CT Ratio LV side for example 3000 5A Rating Transformer maximum rating for example 2MVA H T C T CT Ratio HV side for example 150 5A 150 5 H T Flc Full load current HV side or rated voltage for...

Отзывы: