MRAR 01/96 C 

5.1.5 AR Blocked 
 

The AR Unit changes immediately to the AR Blocked state when an external or internal blocking signal 
exists.  No  auto  reclosing  is  possible  in  this  state and  only  an  external  reset  signal  can  cancel  this.  An 
exception  to  this  is  the  blocked  state  that  is  reached  when  the  unit  reaches  the  preset  Maintenance 
Lockout  number.  This  blocked  state  can  be  cancelled  when  the  counter  (No)  has  been  reset.  (see  also 
para 5.2). 
 

5.2 Description of Status Transition 
 
AR Status Matrix 
Closed 
From

 

Inactive

 

Reclaim 
Time

 

Ready

 

Starting

 

Cycle

 

Blocked

 

Inactive 

 

CB 
Manual 
ON 

 

 

 

External 
Blocking 
Signal 

Reclaim 
Time 

CB OFF 

 

Reclaim 
Time 
Exprired 

 

 

External 
Blocking 
Signal 

Ready 

CB OFF 

 

 

Protection 
Running 
and/or 
Tripped, 
CB Energy 
OK 

 

External 
Blocking 
Signal 

Starting 

 

Starting 
Conditions 
Not 
Fulfilled 

Start 
Signal 
Interrupted 

 

Start 
Conditions 
Fulfilled 
(Fault 
Time, CB 
OFF etc.) 

External 
Blocking 
Signal 

Cycle 

 

 

AR 
Successful 

 

 

External or 
Internal 
Blocking 
Signal 

Blocked 

External 
Blocking 
Signal 

 

 

 

 

 

 

 

 

= No Transition Possible

 

 
From the above table it is possible to determine which status transitions are possible with the MRAR. 
When the unit for instance is in the Cycle State, only two transitions are possible: 

  Transition to the Ready state when reclosing has been successful. 

 

  Transition to the Blocked state by an external or internal blocking signal. 

The grey shaded sections indicate that no transition is possible. 

Содержание MRAR

Страница 1: ...n 50 60 Hz V PH Vx MRAR MODEL SERIAL NO No SHOT tD2 tf tD1 tD4 tD3 tC1 tR MRI IDS PB O LO RUN OK I CB No M No L P B Engineering P B Engineering Belle Vue Works 12 14 Crompton Way Boundary Street Crawl...

Страница 2: ...Success 14 5 3 6 Successful Reclosing 15 5 3 7 Repeated Reclosing 15 5 3 8 External Blocking and Reseting 15 5 3 9 Supervision of the Circuit Breaker Ready Information 15 5 4 Operation and Release of...

Страница 3: ...21 07 2010 3 MRAR 01 96 C 8 4 System data 23 8 5 Power supply 24 9 Housing 25 9 1 Connection Details 26 10 Order Form 27...

Страница 4: ...vercurrent Relay Independent time I D M T earth directional facilities MRI V Voltage Dependent Overcurrent Relay MREF Restricted Earth Fault Relay MRAR Auto Reclosing Relay MRMF Mains Failure Relay MR...

Страница 5: ...eg the MRI I MRCS The protective functions of the MRAR are summarised as follows Independent adjustable time ranges Four digit counter for display of the completed auto reclosing High Set blocking out...

Страница 6: ...tested by the application of a high voltage power frequency input flash tested as this will cause damage to the unit Explanation of the Circuit Diagram 4 1 1 Information Inputs Using the information...

Страница 7: ...voltage to terminal 24 This blocking can only be removed by applying the auxiliary volatge to terminal 25 Blocking has priority during the simultaneous activation of inputs 24 and 25 Reserve 26 This...

Страница 8: ...2 Adjusting LED s SHOT Green Number of reclosing attempts No Red Number of AR s carried out tf Green Fault Time tD1 Green Dead Time for the first reclosing tD2 Red Dead Time for the second reclosing...

Страница 9: ...I Red CB Red LO Red No CB Off signal after protection OFF CB CB Red Dead Time closing conditions not met S E O I Red Switch was manually switched off during Reclaim Time Manu Password combination of...

Страница 10: ...hange at an increased rate The ENTER push button is used to transfer the indicated value to the internal parameter memory An unintended or unauthorised change of the selected parameter can be avoided...

Страница 11: ...relays Code jumper J2 OFF The alarm relays respond directly upon the initiation of the corresponding measuring circuit Thus an alarm signal e g for negative sequence current will be given before the r...

Страница 12: ...ot been interrupted by other faults Activation of the unit due to protection faults is also not possible in the Reclaim Time State thus no auto reclosing can take place 5 1 3 AR Ready The relay is in...

Страница 13: ...ing Signal Reclaim Time CB OFF Reclaim Time Exprired External Blocking Signal Ready CB OFF Protection Running and or Tripped CB Energy OK External Blocking Signal Starting Starting Conditions Not Fulf...

Страница 14: ...the unit changes from the Ready to the Starting state The RUN LED illuminates and the fault timer tf adjustable from 0 01 to 2 05 s begins to time out A tripping timer set at 0 2 s is started when the...

Страница 15: ...by the applying of a reset signal to terminal 25 5 3 9 Supervision of the Circuit Breaker Ready Information Because the supervision of the circuit breaker energy store responds often after the first f...

Страница 16: ...rnal blocking input was activated The AR cycle was terminated without success The circuit breaker energy is not sufficient during a switch on attempt after first attempt see also paragraph 5 3 9 The s...

Страница 17: ...21 07 2010 17 MRAR 01 96 C 5 6 Circuit Example Connection Diagram of the MRAR and MRI Together...

Страница 18: ...ime 1 tD1 Dead Time 2 tR Reclaim Time As a short circuit occurs the circuit breaker is switched off by the protecting device and the dead time counter in the MRAR starts to time out After this dead ti...

Страница 19: ...ed 5 7 3 Manual Switching On of the Circuit Breaker to Faulty Lines Protection Energised Short Circuit Protection Tripped Circuit Breaker Switch on Command 1 Manual On 2 Protection Tripped 1 2 The MRA...

Страница 20: ...ommand during the reclaim time leads to the switching off of the breaker Number of Reclosings Until Maintenance Alarm No M After a certain number of reclosings the circuit breaker must be serviced Thi...

Страница 21: ...he SELECT push button you can check all the unit set values Modification is via the UP and DOWN push buttons followed by ENTER 7 4 Checking the CB Status Input Circuit 28 15 Apply auxiliary voltage to...

Страница 22: ...2 Output Relays Number 5 Contacts 2 Voltage free changeover contacts for switch on relays 1 Voltage free change over contact for other relays 8 3 Setting Ranges and Steps Setting Parameter Setting Ran...

Страница 23: ...tection tripping command after reclosing and is interrupted by the CB Off Alarm C B Wait Time 100mS 10mS This time starts with the CB Off Alarm after an unsuccessful reclosing and is interrupted by th...

Страница 24: ...IEC 41B CO 38 Class 1 Vibration IEC 41B CO 35 Class 1 Degree of Protection Front IP52 Rear IP00 Weight Approx 2kg 8 5 Power supply Two auxiliary power supply versions are available Vaux 24V in a rang...

Страница 25: ...in close proximity and hazardous environments When the relay is inserted a leaf spring along the top edge of the module makes contact with a solidly bonded nickel plated steel strip on the interior of...

Страница 26: ...Each connection facilitates 2 pre insulated push on blades 4 8mm wide 0 8mm thick complying with BS5057 Combinations Each terminal will accept either 2 ring type connectors or 2 push on blade type co...

Страница 27: ...T C T CT Ratio LV side for example 3000 5A Rating Transformer maximum rating for example 2MVA H T C T CT Ratio HV side for example 150 5A 150 5 H T Flc Full load current HV side or rated voltage for...

Отзывы: