21/07/2010
23
MRAR 01/96 C
Fixed Parameter
Value
Tolerance Remarks
Tripping Time
200mS
< 10mS
This time starts with the protection
tripping command and is interrupted by
the CB Off Alarm. When this time has
elapsed, a CB defect is present.
Energy Wait Time
200mS
<10mS
During this time the CB's Standby state
is checked before reclosing. This check
can be blocked by applying auxiliary
voltage to terminal 22.
Sync. Wait Time
200mS
< 10mS
During this time the synchronous
condition is checked before reclosing.
This check can be blocked by applying
auxiliary voltage to terminal 23.
Protection Wait
Time
200mS
< 10mS
This time starts with the protection
tripping command after reclosing and is
interrupted by the CB Off Alarm.
C.B. Wait Time
100mS
< 10mS
This time starts with the CB Off Alarm
after an unsuccessful reclosing and is
interrupted by the Off Command. When
this time has elapsed a manual Off is
present.
Relay Test Time
1 s
< 10mS
With a time gap of one second between
each relay, this feature checks the
tripping of each of the output relays.
Default Password
^^^^
Can be re-programmed using code
jumper J1, see paragraph 4.3.
8.4 System data
Design standard
= IEC 255-4
Operating temperature range
= -20°C to 70°C
Storage temperature range
= -40°C to 85°C
Relative humidity
= 93% @ 40°C for 56 days
Test Voltages to EN50081-1, EN50082-2
Isolation Test
= 2.5kV / 50Hz / 1 min.
Impulse Test
= 5kV, 1.2 / 50mS, 0.5J
High frequency interference Test
= 2.5kV / 1MHz
Burst transient Test
= 4kV / 2.5KHz, 15mS
ESD Test
= 8kV