background image

157 

<Model: WH-UD12CE5-A  WH-UD14CE5-A  WH-UD16CE5-A 
(WH-UD12CE5-A-1  WH-UD14CE5-A-1  WH-UD16CE5-A-1)> 

 

REF. 

NO. 

DESCRIPTION & NAME 

QTY. 

WH-UD12CE5-A 

(WH-UD12CE5-A-1) 

WH-UD14CE5-A 

(WH-UD14CE5-A-1) 

WH-UD16CE5-A 

(WH-UD16CE5-A-1) 

REMARK

BASE PAN ASS’Y 

CWD52K1275 

 

 

 

2 COMPRESSOR 

5JD420XAA22 

 

 O 

BUSHING - COMPRESSOR MOUNT 

CWH50055 

 

 

 

4 NUT-COMPRESSOR 

MOUNT 

CWH561049 

 

 

 

4a 

GASKET FOR TERMINAL COVER 

CWB811017 

 

 

 

5 CRANKCASE 

HEATER 

CWA341053 

 

 

 

6 CONDENSER 

COMPLETE 

CWB32C2983 

 

 

 

HIGH PRESSURE SENSOR 

CWA50C2570 

 

 O 

8 DISCHARGE 

MUFFLER 

CWB121014 

 

 

 

9 PRESSURE 

SWITCH 

CWA101013 

 

 

 

10 3-WAYS 

VALVE 

(GAS) 

CWB011251 

 

 

 

11 4-WAYS 

VALVE 

CWB001046 

 

 

 

12 3-WAYS 

VALVE 

(LIQUID) 

CWB011292 

 

 

 

13 STRAINER 

CWB111032 

 

 

 

19 ACCUMULATOR 

CWB131026A 

 

 

 

20 

SOUND PROOF MATERIAL 

CWG302265 

 

 

 

21 

SOUND PROOF MATERIAL 

CWG302266 

 

 

 

22 

SOUND PROOF BOARD 

CWH15K1019 

 

 

 

23 

V-COIL COMPLETE - 4-WAYS VALVE 

CWA43C2169J 

 

 O 

24 

V-COIL COMPLETE - EXP.VALVE 

CWA43C2385 

 

 O 

25 SENSOR-COMP. 

TEMP./COIL 

CWA50C2730 

 

 O 

26 SENSOR-COMP. 

DISCHARGE 

CWA50C2576 

 

 

 

27 SENSOR-COMPLETE 

TOP 

CWA50C2629 

 

 O 

27a SENSOR-COMP. 

DEF 

CWA50C2577 

 

 O 

28 CABINET 

REAR 

PLATE-COMPLETE 

CWE02C1059 

 

 

 

29 

CONTROL BOARD CASING 

CWH10K1049 

 

 

 

31 

TERMINAL BOARD ASS’Y 

CWA28K1213 

 

 O 

36 ELECTRONIC 

CONTROLLER 

CWA746169 

 

 O 

38 ELECTRONIC 

CONTROLLER-NF 

CWA745446 

 

 O 

44 ELECTRONIC 

CONTROLLER 

(MAIN) 

CWA73C4835R CWA73C4836R CWA73C4837R O 

46 REACTOR 

G0C592J00005 

 

 O 

48 TERMINAL 

COVER 

CWH171039A 

 

 

 

49 NUT-TERMINAL 

COVER 

CWH7080300J 

 

 

 

50 

FAN MOTOR BRACKET 

CWD54K1024 

 

 

 

50a 

SCREW-FAN MOTOR BRACKET 

CWH551040J 

 

 

 

53 FAN 

MOTOR 

EHDS80AAC 

 

 O 

54 FAN 

MOTOR 

EHDS80BAC 

 

 O 

54a 

SCREW-FAN MOTOR MOUNT 

CWH551323 

 

 

 

55 PROPELLER 

FAN 

ASSY 

CWH00K1006 

 

 

 

56 NUT 

CWH561092 

 

 

 

57 

CABINET FRONT PLATE 

CWE061098A 

 

 

 

58 DISCHARGE 

GRILLE 

CWE201073 

 

 

 

59 

CABINET SIDE PLATE ASSY 

CWE04K1023A 

 

 

 

60 WIRE 

NET 

CWD041103A 

 

 

 

61 

CABINET TOP PLATE CO. 

CWE03C1096 

 

 

 

62 ACCESSORY-COMPLETE 

CWH82C1535 

 

 

 

64 

PIPE COVER (FRONT) 

CWD601074A 

 

 

 

65 

PIPE COVER (BACK) 

CWD601075A 

 

 

 

66 

CABINET FRONT PLATE CO. 

CWE06C1091 

 

 

 

67 HANDLE 

CWE161008 

 

 

 

68 

TUBE ASSY (CAP. TUBE) 

CWT07K1541 

 

 

 

Содержание (WH-UD12CE5-A-1

Страница 1: ...EMPERATURE In order to avoid frostbite be assured of no refrigerant leakage during the installation or repairing of refrigeration circuit WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to service a pr...

Страница 2: ...13 Operation and Control 63 13 1 Basic Function 63 13 2 Water Pump 74 13 3 Pump Down Operation 75 13 4 Flow Switch 75 13 5 Force Heater Mode Operation 75 13 6 Indoor Unit Safety 76 13 7 Auto Restart Control 76 13 8 Indication Panel 76 13 9 Indoor Back Up Heater Control 77 13 10Tank Booster Heater Control 77 13 11Base Pan Heater Control Optional 78 13 12Three Way Valve Control 78 13 13Sterillizatio...

Страница 3: ...st 147 20 1 WH SDF07C3E5 WH SDF09C3E5 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF07C3E5 1 WH SDF09C3E5 1 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 147 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 149 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 154 ...

Страница 4: ... instruction An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 10 This equipment must be properly earthed Earth line must not be connected to gas pipe water pipe earth of lightning rod and telephone Otherwise it may cause electric shock in case equipment breakdown or insulatio...

Страница 5: ...rk The weight of indoor outdoor unit might cause injury if carried by one person 4 Do not touch outdoor unit air inlet and aluminium fin It may cause injury 5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the...

Страница 6: ... 7 23 0 Pipe Length Range m ft 3 9 8 30 98 4 I D O D Height Difference m ft 20 65 6 Additional Gas Amount g m oz ft 30 0 3 Refrigeration Charge Less m ft 10 32 8 Type Hermetic Motor Rotary Motor Type Brushless 4 poles Compressor Rated Output kW 1 70 Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Fan Speed rpm 580 Fin material Aluminium Pre Coat Fin ...

Страница 7: ...nlet mm inch 28 1 3 32 Water Pipe Diameter Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Motor Type Capacitor Run Induction Motor 2 5 μF No of Speed 3 Pump Input Power W 100 Type Brazed Plate No of Plates 48 Size W x H x L mm 93 82 325 Hot Water Coil Water Flow Rate l min m 3 h 20 1 1 2 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch ...

Страница 8: ... D O D Height Difference m ft 20 65 6 Additional Gas Amount g m oz ft 30 0 3 Refrigeration Charge Less m ft 10 32 8 Type Hermetic Motor Rotary Motor Type Brushless 4 poles Compressor Rated Output kW 1 70 Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Fan Speed rpm 640 Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 30 17 Heat...

Страница 9: ...ameter Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Motor Type Capacitor Run Induction Motor 2 5 μF No of Speed 3 Pump Input Power W 100 Type Brazed Plate No of Plates 48 Size W x H x L mm 93 82 325 Hot Water Coil Water Flow Rate l min m 3 h 25 8 1 6 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Devi...

Страница 10: ...ifference m ft 30 98 4 Additional Gas Amount g m oz ft 50 0 5 Refrigeration Charge Less m ft 30 98 4 Type Hermetic Motor Rotary Motor Type Brushless 4 poles Compressor Rated Output kW 3 00 Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Fan Speed rpm 510 Top Fan 550 Bottom Fan Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51...

Страница 11: ...Diameter Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Motor Type Capacitor Run Induction Motor 5 μF No of Speed 3 Pump Input Power W 190 Type Brazed Plate No of Plates 80 Size H x W x L mm 130 93 325 Hot Water Coil Water Flow Rate l min m 3 h 34 4 2 1 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Dev...

Страница 12: ...Difference m ft 30 98 4 Additional Gas Amount g m oz ft 50 0 5 Refrigeration Charge Less m ft 30 98 4 Type Hermetic Motor Rotary Motor Type Brushless 4 poles Compressor Rated Output kW 3 00 Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Fan Speed rpm 540 Top Fan 580 Bottom Fan Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 5...

Страница 13: ...Diameter Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Motor Type Capacitor Run Induction Motor 5 μF No of Speed 3 Pump Input Power W 190 Type Brazed Plate No of Plates 80 Size H x W x L mm 130 93 325 Hot Water Coil Water Flow Rate l min m 3 h 40 1 2 4 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Dev...

Страница 14: ...Difference m ft 30 98 4 Additional Gas Amount g m oz ft 50 0 5 Refrigeration Charge Less m ft 30 98 4 Type Hermetic Motor Rotary Motor Type Brushless 4 poles Compressor Rated Output kW 3 00 Type Propeller Fan Material PP Motor Type Induction 8 poles Input Power W Output Power W 60 Fan Fan Speed rpm 580 Top Fan 620 Bottom Fan Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 5...

Страница 15: ...Diameter Outlet mm inch 28 1 3 32 Water Drain Hose Inner Diameter mm inch 15 00 19 32 Motor Type Capacitor Run Induction Motor 5 μF No of Speed 3 Pump Input Power W 190 Type Brazed Plate No of Plates 80 Size H x W x L mm 130 93 325 Hot Water Coil Water Flow Rate l min m 3 h 45 9 2 8 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Dev...

Страница 16: ...m auto restart after power failure for safety restart operation Gas leakage protection Prevent compressor reverse cycle Inner protector to protect compressor Serviceability Improvement Breakdown Self Diagnosis function System Status Check Buttons for servicing purpose System Pumpdown Button for servicing purpose Front maintenance design for outdoor unit Operation Condition Indoor Outdoor Water out...

Страница 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...

Страница 18: ...18 ...

Страница 19: ...19 ...

Страница 20: ...20 4 1 2 Weekly Timer Setting ...

Страница 21: ...21 4 1 3 Setting Up The Special Functions ...

Страница 22: ...22 4 1 4 Main Components ...

Страница 23: ...23 4 2 Outdoor Unit ...

Страница 24: ...24 5 Dimensions 5 1 Indoor Unit ...

Страница 25: ...25 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...

Страница 26: ...26 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...

Страница 27: ...ngth m Max Piping Length m Additional Refrigerant g m UD07CE5 5 8 1 4 5 7 5 20 3 30 30 UD09CE5 5 8 1 4 5 7 5 20 3 30 30 UD12CE5 5 8 3 8 5 7 5 30 3 40 50 UD14CE5 5 8 3 8 5 7 5 30 3 40 50 UD16CE5 5 8 3 8 5 7 5 30 3 40 50 If piping length is over common length additional refrigerant should be added as shown in the table ...

Страница 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...

Страница 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...

Страница 30: ...30 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDF07C3E5 WH SDF09C3E5 WH SDF07C3E5 1 WH SDF09C3E5 1 ...

Страница 31: ...31 8 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 ...

Страница 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...

Страница 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...

Страница 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDF07C3E5 WH SDF09C3E5 WH SDF07C3E5 1 WH SDF09C3E5 1 ...

Страница 35: ...35 9 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 ...

Страница 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...

Страница 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...

Страница 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...

Страница 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...

Страница 40: ...40 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 10 2 1 1 Main Printed Circuit Board ...

Страница 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...

Страница 42: ...42 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 10 2 2 1 Main Printed Circuit Board ...

Страница 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...

Страница 44: ...UNIT If an awning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed Avoid installations in areas where the ambient temperature may drop below 20 C Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a short circuit of the discharged air If outdoor unit i...

Страница 45: ...solar pump station the distance between both apparatuses shall be 2 8 meters and the length of the said cable must be shorter than 10 meter Failure to do so may lead to abnormal operation to the system 2 Engage the slots on the indoor unit to the hooks of installation plate Ensure the hooks are properly seated on the installation plate by moving it left and right 3 Fix the screws to the holes on t...

Страница 46: ...age 11 3 3 3 Indoor Unit Refrigerant Pipe Installation 1 Please make flare after inserting flare nut located at joint portion of tube assembly onto the copper pipe In case of using long piping 2 Do not use pipe wrench to open refrigerant piping Flare nut may be broken and cause leakage Use proper spanner or ring wrench 3 Connect the piping o Align the center of piping and sufficiently tighten the ...

Страница 47: ...ring and electronic type Valve cable shall be 3 x min 0 5 mm2 of type designation 60245 IEC 57 or heavier or similarly double insulation sheathed cable note Should be CE marking compliance component It should be directed to heating mode when it is OFF Maximum load for the valve is 9 8VA 5 Room Thermostat cable must be 4 or 3 x min 0 5 mm2 double insulation layer of PVC sheathed or rubber sheathed ...

Страница 48: ...48 Terminal screw Tightening torque N cm kgf cm M4 157 196 16 20 M5 196 245 20 25 11 3 4 1 Wire Stripping and Connecting Requirement ...

Страница 49: ...greater than or equal to 828 38kW The equipment s power supply 1 shall be connected to a suitable supply network having service current capacity 100A per phase Please liaise with supply authority to ensure that the service current capacity at the interface point is sufficient for the installation of the equipment The equipment s power supply 2 complies with IEC EN 61000 3 12 The equipment s power ...

Страница 50: ...rting the flare nut locate at valve onto the copper pipe Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table Local pipes can project in any of four directions Make holes in the pipe panels for the pipes to pass through Be sure to install the pipe panels to prevent rain from getting inside the outdoor unit Removing the service panel 1 ...

Страница 51: ...of the 3 way valve at a torque of 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve and 3 way valve Position both of the valves to OPEN using a hexagonal wrench 4 mm 8 Mount valve caps onto the 2 way valve and the 3 way valve o Be sure to check for gas leakage CAUTION If gauge needle does not move from 0cmHg 0MPa to 76cmHg 0 1MPa in step above take the following measur...

Страница 52: ...m Please wrap the insulated piping end to prevent water from going inside the piping 2 If drain hose or connecting piping is in the room where dew may form please increase the insulation by using POLY E FOAM with thickness 6 mm or above 11 4 6 Disposal of Outdoor Unit Drain Water When a Drain elbow is used please ensure to follow below o the unit should be placed on a stand which is taller than 50...

Страница 53: ... is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed Avoid installations in areas where the ambient temperature may drop below 20 C Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a short circuit of the discharged air If outdoor unit installed near sea...

Страница 54: ...8 meters and the length of the said cable must be shorter than 10 meter Fail to do so may lead to abnormal operation to the system 2 Engage the slots on the indoor unit to the hooks of installation plate Ensure the hooks are properly seated on the installation plate by moving it left and right 3 Fix the screws to the holes on the hooks of installation plate as illustrated below 12 3 3 2 Water Pipi...

Страница 55: ... are after inserting fl are nut located at joint portion of tube assembly onto the copper pipe In case of using long piping 2 Do not use pipe wrench to open refrigerant piping Flare nut may be broken and cause leakage Use proper spanner or ring wrench 3 Connect the piping o Align the center of piping and sufficiently tighten the flare nut with fingers o Further tighten the flare nut with torque wr...

Страница 56: ...alve shall be spring and electronic type Valve cable shall be 3 x min 0 5 mm2 of type designation 60245 IEC 57 or heavier or similarly double insulation sheathed cable note Should be CE marking compliance component It should be directed to heating mode when it is OFF Maximum load for the valve is 9 8VA 5 Room Thermostat cable must be 4 or 3 x min 0 5 mm2 double insulation layer of PVC sheathed or ...

Страница 57: ...57 Terminal screw Tightening torque N cm kgf cm M4 157 196 16 20 M5 196 245 20 25 12 3 4 1 Wire Stripping and Connecting Requirement ...

Страница 58: ...UD16CE5 0 244Ω Please liaise with supply authority to ensure that the power supply 1 is connected only to a supply of that impedance or less The equipment s power supply 2 complies with IEC EN 61000 3 12 The equipment s power supply 2 shall be connected to a suitable supply network with the following maximum permissible system impedance Zmax at the interface for models WH SDF12C6E5 UD12CE5 WH SDF1...

Страница 59: ...N Do not over tighten over tightening cause gas leakage Connecting the Piping to Outdoor Unit Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make flare after inserting the flare nut locate at valve onto the copper pipe Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table Local pipes can project in any...

Страница 60: ...evacuate the air approximately ten minutes 4 Close the Low side valve of the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not move after approximately five minutes Note BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the serv...

Страница 61: ...eted tie the wires and cord together with the binding strap so that they do not touch other parts such as the compressor and bare copper pipes 6 Install back the control board cover 12 4 4 1 Wire Stripping and Connecting Requirement Same as indoor requirement For details please refer the diagram on AIR TO WATER HEATPUMP INDOOR UNIT section 12 3 4 CONNECT THE CABLE TO THE INDOOR UNIT 12 4 5 PIPE IN...

Страница 62: ...50 mm o cover the 8 holes ø20mm with Rubber cap refer to illustration below o use a tray field supply when necessary to dispose the outdoor unit drain water If the unit is used in an area where temperature falls below 0 C for 2 or 3 consecutive days it is recommended not to use the Drain elbow and Rubber cap for the drain water freezes and the fan will not rotate ...

Страница 63: ...et Temperature Internal Water Setting Temperature 2 C for continuously 3 minutes Compressor is ON after waiting for 3 minutes if the Water Outlet Temperature Water Inlet Temperature temperature at thermostat OFF is triggered 3 C 13 1 3 Tank Mode Operation Control contents 3 ways valve direction 3 ways valve switch and fix to tank side Heat pump Thermostat characteristic Water set temperature Tank ...

Страница 64: ...after DELAY TIMER 2 When tank temperature lower than HEATER ON TEMP 3 20 minutes from previous heater off Booster heater turn OFF condition 1 When tank temperature higher than tank set temperature for continuous 15 secs Solar 3 way valve Solar pump operates follow solar operation specification 2 way valve closes Others Indoor backup heater cannot be ON during tank mode only ...

Страница 65: ...65 ...

Страница 66: ...oom Thermo OFF AND Solar 3 ways valve OFF 2 Heat pump operation control o During External Room Thermo ON time When room thermo ON heat pump must operate to room side Heat pump operate follow normal operation at room side o During External Room Thermo OFF time Switch 3 ways valve to tank side IF Under Solar Priority Set condition o Tank temperature Tank THERMO ON TEMP AND Solar Valve OFF Under Sola...

Страница 67: ...2 o Heat pump THERMO OFF TEMP 1 Heat pump THERMO OFF TEMP 53 C 4 C 2 Water outlet temperature Heat pump THERMO OFF TEMP for continuous 3 minutes heat pump OFF o Next THERMO ON TEMP 1 THERMO ON TEMP Water inlet when heat pump THERMO OFF 3 C 2 If water outlet temperature THERMO ON TEMP AND External Room Thermo OFF heat pump ON Case 3 o Heat pump THERMO OFF TEMP 1 Water inlet temperature 55 C for con...

Страница 68: ...operation specification Under solar priority is set condition when solar 3WV turn ON booster heater will turn OFF and 3 ways valve switch to room side Under solar priority is not set condition solar 3WV will OFF when heat pump operate to tank side o 2 way valve opens ...

Страница 69: ...emperature or 50 C whichever lower Heat pump Water Outlet set temperature is set to Maximum 55 C during tank interval Initial Tank THERMO ON TEMP heat pump tank target temperature 1 C Case 1 THERMO OFF TEMP 1 THERMO OFF TEMP Heat pump tank target temperature 1 C 2 Tank temperature THERMO OFF TEMP for continuous 10 seconds after heat pump off due to water thermo switch 3 ways valve to room side End...

Страница 70: ...eat up interval Booster heater ON OFF according to booster heater operation control o During tank heat up interval Once switch from heating heat up interval to tank heat up interval turn off the booster heater and start counting the BOOSTER HEATER DELAY TIMER Booster heater turn ON after BOOSTER HEATER DELAY TIMER fulfill and tank temperature lower than tank set temperature BOOSTER HEATER DELAY TI...

Страница 71: ...71 ...

Страница 72: ...72 ...

Страница 73: ...ump provide heating capacity to room side by hot water through heating panel floor or fan coil 1 3 ways valve control o 3 ways valve switch and fix to heating side 2 Heat pump operate follow normal heating operation 3 Backup heater operate follow normal operation 4 Solar 3 way valve operates follow solar operation specification 5 2 way valve opens 13 1 6 Water Temperature Thermo Shift Setting Swit...

Страница 74: ...ill be OFF permanently and OFF ON control panel LED will blink H62 error occurs When error happen the power has to be reset to clear the error If there is no error indication The water pump shall be continuously running The water pump will remain ON when compressor OFF due to thermostat OFF setting is reached Pump ON OFF control a During operation OFF or water pump stop at Tank Mode b During ERROR...

Страница 75: ...ce mode 2 In service mode select Sr 01 and press SET S W to start Pump Down operation 3 There will be no Low Pressure error Freeze prevention judgement during pumpdown operation 4 3 ways valve will shift to room side 5 Press the ON OFF button to stop the unit 13 4 Flow Switch 13 4 1 Flow Switch Control 1 The water flow switch serve as an overload protector that shuts down the unit when the water l...

Страница 76: ...he water inlet temperature exceeds 80 C for continuously 10 seconds the water pump will be OFF immediately 3 After water pump OFF for more than 10 minutes it will be ON back and the indoor unit safety control checking is restarted 13 7 Auto Restart Control 1 When the power supply is cut off during the operation of Air to Water Heatpump the compressor will re operate after power supply resumes 13 8...

Страница 77: ...ater switch is Off OR d Heat pump thermo off or OFF condition 2 Force Heater Mode o Heater On Condition a After water pump operate 9 mins b When water outlet temperature water set temperature 8 C c 20 minutes since previous Backup heater Off o Heater Stop condition a Force mode off OR b When water outlet temperature water set temperature 2 C for continuous 15 secs Do not operate heater at the foll...

Страница 78: ...heater will continue ON for 10 minutes after deice operation ends Base pan heater OFF condition o When outdoor ambient temperature 3 C OR o When operation is not heating OR o Base pan heater ON timer count completed 13 12 Three Way Valve Control Purpose 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side Control contents 1 3 ways valve switc...

Страница 79: ...eration by reduces outdoor unit noise Starting condition 1 When quiet button is presses 2 When quiet request ON time by weekly timer Refer to control panel When any of above mentioned condition is achieved this control is activated New target FM speed Present target FM speed 80 rpm Minimum target FM speed 200 rpm Cancellation condition 1 Cancel by press quiet button 2 Stop by OFF ON button 3 When ...

Страница 80: ... the Solar pump 3 Way Valve is requested ON Refer to figure below 13 16 2 Solar Operation Control When solar priority is SET 1 Operation condition a 3 way valve operates if all of the following conditions are fulfilled Power On regardless operation ON or OFF There is operation request from solar pump station Tank hot water temp is below solar on upper limit temp 72 C 2 Stop condition a 3 way valve...

Страница 81: ...rating when No power supply to unit OR There is NO operation request from solar pump station OR Tank hot water temp is above solar off upper limit temp 80 C Heat pump thermo ON and operate to tank side during operation ON and tank mode selected ...

Страница 82: ...82 ...

Страница 83: ...uit OFF Short Circuit ON Set Temp Actual Temp Short Circuit ON Open Circuit OFF Wire Connection and thermo characteristic of Siemen RAA20 Setting L Y1 H Heat Thermo L Y2 C Cool Thermo Set Temp Actual Temp Open Circuit OFF Short Circuit ON Set Temp Actual Temp Short Circuit ON Open Circuit OFF Control Content External room thermostat control activate only when remote thermostat connection select YE...

Страница 84: ... minutes when the IPM temperature decreases to 90 C If this condition repeats continuously 3 times within 30 minutes system will stop operation and OFF ON control panel LED will blink F22 error occurs B DC Peak Current Control 1 When the current to IPM exceeds set value of 40 1 5 0 A UD07CE and UD09CE 44 7 5 0 A UD12CE UD14CE and UD16CE compressor will stop Compressor will restart after three minu...

Страница 85: ...top operation o OFF ON control panel LED will blink H64 error occurs 14 1 9 Outside Temperature Current Control 14 1 10 Crank case heater control Purpose For compressor protection during low outdoor ambient operation during heating low temperature operation Control content a Trigger heater START condition o when the outdoor air temperature is 4 C or below and discharge temperature is 12 C or below...

Страница 86: ...e operation start where outdoor fan motor stop 14 2 3 Heat exchanger hot water coil protection control Backup heater ON condition o water inlet temperature 23 C AND o outdoor ambient temperature 10 C Backup heater OFF condition o water inlet temperature 25 C OR o outdoor ambient temperature 13 C ...

Страница 87: ...olding both of the handles 15 3 Test Run 1 Fill up the boiler tank with water For details refer to boiler tanks installation instruction and operation instruction 2 Set ON to the indoor unit and RCCB ELCB Then for control panel s operation please refers to air to water heatpump s operation instruction 3 For normal operation pressure gauge reading should be in between 0 05 MPa and 0 3 MPa If necess...

Страница 88: ...e noise of running water Below graph shown the external static pressure kPa versus water flow rate L min Flow rate characteristic of indoor unit is as per above mentioned 15 6 Expansion Vessel Pre Pressure Checking Expansion Vessel with 10L air capacity and initial pressure of 1 bar is installed in this indoor unit Total amount of water in system should be below 200L Note This amount of water is n...

Страница 89: ...hen contact your local authorized dealer 3 Air purge valve Air purge valve must be installed at all high points in a closed water circuit system An automatic air purge valve is provided inside the indoor unit To automatically purge the air from the system turn the plug on the air outlet anticlockwise by one complete turn from fully closed position Excessive air is automatically purged if the plug ...

Страница 90: ...r of step a b 7 External water filter field supply Clean the external water filter in regularly basic o External water filter is located inside the tube connector which is before water inlet connector of indoor unit indicated with WATER IN Refer to figure below o Use spanner to detach the tube connector nut o Take out the filter carefully so that not deforms it shape o Use tap water only to wash t...

Страница 91: ...no electrical problems before inspecting the refrigeration cycle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table on the right ...

Страница 92: ...nits Low Pressure High Pressure Electric current during operation Water leakage or insufficient water flow rate in the system Excessive amount of refrigerant Inefficient compression Insufficient refrigerant gas leakage Outdoor heat exchange deficiency Clogged expansion valve or Strainer Carry out the measurements of pressure electric current and temperature fifteen minutes after an operation is st...

Страница 93: ...IC memory To check the error code 1 When an abnormality occurs system will stop operation and OFF ON control panel LED will blink 2 Error code of the abnormality will display on the control panel Timer display LCD 3 To determine the abnormality description the Error Code Table needs to be referred To display past last error code 1 Turn ON power supply 2 Press and hold the CHECK button for more tha...

Страница 94: ...akage Clogged expansion valve or strainer Excess refrigerant Outdoor PCB H99 Indoor heat exchanger freeze prevention Indoor heat exchanger Refrigerant shortage F12 Pressure switch activate 4 times occurrence within 20 minutes Pressure switch F14 Outdoor compressor abnormal revolution 4 times occurrence within 20 minutes Outdoor compressor F15 Outdoor fan motor lock abnormality 2 times occurrence w...

Страница 95: ...6 Outdoor Current Transformer open circuit Insufficient refrigerant Outdoor PCB Compressor low F48 Outdoor EVA outlet temperature sensor abnormality Continue for 5 sec Outdoor EVA outlet temperature sensor defective or disconnected F49 Outdoor bypass outlet temperature sensor abnormality Continue for 5 sec Outdoor bypass outlet temperature sensor defective or disconnected F95 Cooling high pressure...

Страница 96: ...ration of cooling and heating the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality Malfunction Caused 1 Wrong model interconnected 2 Wrong indoor unit or outdoor unit PCB main used 3 Faulty indoor unit or outdoor unit PCB main Abnormality Judgment Continue for 90 seconds ...

Страница 97: ...During startup and operation of cooling and heating the temperatures detected by the compressor tank temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 98: ... During startup and operation of cooling and heating the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 99: ...ove 26 C is detected by the outdoor pipe temperature sensor Malfunction Caused 1 Dust accumulation on the outdoor unit heat exchanger 2 Air short circuit at outdoor unit 3 2 way valve partially closed 4 Faulty outdoor unit fan motor 5 Refrigerant shortage refrigerant leakage 6 Clogged expansion valve or strainer 7 Faulty outdoor pipe temperature sensor 8 Faulty outdoor unit main PCB main ...

Страница 100: ...etected by the indoor water flow switch is used to determine water flow error Malfunction Caused 1 Faulty water pump 2 Water leak in system 3 Faulty connector connection 4 Faulty water flow switch 5 Faulty indoor unit PCB main Abnormality Judgment Continue for 10 seconds but no judgment for 9 minutes after compressor startup restart ...

Страница 101: ...Decision Conditions During operation of heating when the outdoor low pressure sensor output signal is 0Vdc or 5Vdc Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue 4 times in 20 minutes ...

Страница 102: ...on Conditions During operation of cooling and heating when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue 4 times in 20 minutes ...

Страница 103: ...ndoor backup heater when no power supplies to indoor backup heater or OLP open circuit Malfunction Caused 1 Faulty power supply connector connection 2 Faulty connector connection 3 Faulty indoor backup heater overload protector OLP 4 Faulty indoor unit PCB main Abnormality Judgment Continue for 60 seconds ...

Страница 104: ...onditions When tank connection is set to ON the temperatures detected by the tank temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 105: ...cation Abnormality H76 Malfunction Decision Conditions During standby and operation of cooling and heating indoor control panel error occur Malfunction Caused 4 Faulty connector connection 5 Faulty control panel 6 Faulty indoor unit PCB main ...

Страница 106: ...is normal Malfunction Caused 1 Faulty outdoor unit PCB main 2 Faulty indoor unit PCB main 3 Indoor outdoor signal transmission error due to wrong wiring 4 Indoor outdoor signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units 5 Indoor outdoor signal transmission error due to disturbed power supply waveform Abnormality Judgment Continue for 1 m...

Страница 107: ...ion Conditions During operation of tank booster heater and tank booster heater OLP open circuit Malfunction Caused 1 Faulty connector connection 2 Faulty tank booster heater overload protector OLP 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 60 seconds ...

Страница 108: ...tween Indoor and Outdoor H95 Malfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused 1 Insufficient power supply 2 Faulty outdoor unit PCB noise filter main ...

Страница 109: ...ssure 4 0 MPa and above is detected by outdoor high pressure sensor Malfunction Caused 1 Faulty water pump 2 Insufficient water flow rate in system 3 Water leak in system 4 2 3 way closed 5 Clogged expansion valve or strainer 6 Excessive refrigerant 7 Faulty outdoor high pressure sensor 8 Faulty outdoor unit PCB main ...

Страница 110: ...door refrigerant liquid temperature 0 C Malfunction Caused 1 Faulty water pump 2 Insufficient water flow rate in system 3 Water leak in system 4 2 way valve partially closed 5 Clogged expansion valve or strainer 6 Refrigerant shortage refrigerant leakage 7 Faulty indoor refrigerant liquid temperature sensor 8 Faulty indoor unit PCB main ...

Страница 111: ...tected by outdoor high pressure switch Malfunction Caused 1 Faulty water pump 2 Insufficient water flow rate in system 3 Water leak in system 4 3 way valve closed 5 Clogged expansion valve or strainer 6 Excessive refrigerant 7 Faulty outdoor high pressure sensor and switch 8 Faulty outdoor unit PCB Abnormality Judgment Continue 4 times in 20 minutes ...

Страница 112: ... compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused 1 Compressor terminal disconnect 2 Faulty outdoor unit PCB main 3 Faulty compressor Abnormality Judgment Continue 4 times in 20 minutes ...

Страница 113: ...l fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused 1 Operation stop due to short circuit inside the fan motor winding 2 Operation stop due to breaking of wire inside the fan motor 3 Operation stop due to breaking of fan motor lead wires 4 Operation stop due to fan motor Hall IC malfunction 5 Operation error due to faulty outdoor unit PCB Abnormality Judgment Continue 2 times in 3...

Страница 114: ...itions During operation of cooling and heating when outdoor current above 27 9A is detected by the current transformer CT in the outdoor unit PCB Malfunction Caused 1 Excessive refrigerant 2 Faulty outdoor unit PCB main Abnormality Judgment Continue 3 times in 20 minutes ...

Страница 115: ...ve 112 C is detected by the compressor tank temperature sensor Malfunction Caused 1 Faulty compressor tank temperature sensor 2 2 3 way valve closed 3 Refrigerant shortage refrigerant leakage 4 Clogged expansion valve or strainer 5 Faulty outdoor unit PCB main 6 Faulty compressor Abnormality Judgment Continue 4 times in 30 minutes ...

Страница 116: ...onditions During operation of cooling and heating when temperature 95 C is detected by the outdoor IPM temperature sensor Malfunction Caused 1 Faulty outdoor unit fan motor 2 Faulty outdoor unit PCB main Abnormality Judgment Continue 3 times in 30 minutes ...

Страница 117: ...of cooling and heating when outdoor DC current is above 40 1 5 0A for UD07 09CE OR 44 7 5 0A for UD12 16CE is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB main Malfunction Caused 1 Faulty outdoor unit PCB main 2 Faulty compressor Abnormality Judgment Continue for 7 times ...

Страница 118: ...A I 1 65A 3 During operation of heating indoor refrigerant liquid temperature water inlet temperature 5 C Malfunction Caused 1 Faulty water inlet or indoor refrigerant liquid temperature sensors 2 2 3 way valve closed 3 Refrigerant shortage refrigerant leakage 4 Clogged expansion valve or strainer 5 Faulty outdoor unit PCB main 6 Poor compression of compressor Abnormality Judgment Continue 2 times...

Страница 119: ... During heating operation when the indoor pipe temperature of thermostat ON indoor unit 0 C Malfunction Caused 1 Faulty sensor 2 Faulty connector connection 3 Faulty outdoor unit PCB noise filter main 4 Faulty four way valve Abnormality Judgment Continue 4 times in 30 minutes ...

Страница 120: ...l F27 Malfunction Decision Conditions During compressor stop and outdoor high pressure switch is remain opened Malfunction Caused 1 Faulty connector connection 2 Faulty switch 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 1 minute ...

Страница 121: ... During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 122: ...s During startup and operation of cooling and heating the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 123: ... During startup and operation of cooling and heating the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 124: ...ng operation of cooling and heating when the PFC protection circuitry in the outdoor unit PCB main senses abnormal high DC voltage level Malfunction Caused 1 Power supply surge 2 Compressor windings not uniform 3 Faulty outdoor unit PCB main Abnormality Judgment Continue 4 times in 10 minutes ...

Страница 125: ... During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 126: ... During startup and operation of cooling and heating the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 127: ... During startup and operation of cooling and heating the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors Malfunction Caused 1 Faulty connector connection 2 Faulty sensor 3 Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds ...

Страница 128: ...rmer CT open circuit is detected by checking the compressor running frequency rated frequency and CT detected input current 0 65A for continuously 20 seconds Malfunction Caused 1 CT defective 2 Faulty outdoor unit PCB 3 Compressor defective low compression Abnormality Judgment Continue 3 times in 20 seconds ...

Страница 129: ... above is detected by outdoor high pressure sensor Malfunction Caused 1 Dust accumulation in the outdoor unit heat exchanger 2 Air short circuit at outdoor unit 3 2 way valve closed 4 Faulty outdoor unit fan motor 5 Clogged expansion valve or strainer 6 Excessive refrigerant 7 Faulty outdoor high pressure sensor 8 Faulty outdoor unit PCB main ...

Страница 130: ...w for take out front plate Before removing the front plate of indoor unit always switch off all power supply i e indoor unit power supply heater power supply and boiler tank power supply 1 Remove the 2 mounting screws which located at bottom of the front plate and 1 mounting screw at the front of the plate 2 Gently pull the lower section of the front plate towards you to remove the front plate fro...

Страница 131: ...131 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...

Страница 132: ...132 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...

Страница 133: ...133 18 7 To Remove Pressure Relief Valve Flow Switch Water Pump and Bottle Complete When reinstall the water pipe use grease or water at the joining ...

Страница 134: ...134 When reinstall the water pipe use grease or water at the joining When reinstall the water pipe use grease or water at the joining ...

Страница 135: ... 1 WH SDF07C3E5 WH UD07CE5 A WH SDF07C3E5 1 WH UD07CE5 A 1 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 136: ...136 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 137: ...5 A WH SDF09C3E5 1 WH UD09CE5 A 1 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 138: ...138 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 139: ...5 A WH SDF12C6E5 1 WH UD12CE5 A 1 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 140: ...140 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 141: ...5 A WH SDF14C6E5 1 WH UD14CE5 A 1 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 142: ...142 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 143: ...5 A WH SDF16C6E5 1 WH UD16CE5 A 1 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 144: ...144 Heating Characteristics at Different Piping Length Condition Outdoor air temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7m ...

Страница 145: ...00 5 20 3 14 5 00 3 33 7 6 10 2 16 5 90 2 36 5 85 2 63 5 80 2 90 5 80 3 06 5 80 3 22 2 6 80 1 87 6 70 2 16 6 70 2 38 6 60 2 64 6 30 2 90 6 00 3 16 7 9 00 1 93 9 00 2 20 9 00 2 45 9 00 2 81 8 95 3 23 8 90 3 87 25 9 00 1 07 9 00 1 27 8 40 1 40 8 00 1 59 7 80 1 81 7 50 2 03 HC Heating Capacity kW IP Power Input kW LWC Leaving Water Condenser Temperature C Tamb Ambient Temperature C 19 2 3 WH SDF12C6E...

Страница 146: ... Power Input kW LWC Leaving Water Condenser Temperature C Tamb Ambient Temperature C 19 2 5 WH SDF16C6E5 WH UD16CE5 A WH SDF16C6E5 1 WH UD16CE5 A 1 LWC 30 35 40 45 50 55 Tamb HC IP HC IP HC IP HC IP HC IP HC IP 15 10 60 4 13 10 30 4 42 10 00 4 71 9 70 5 00 8 80 4 98 7 90 4 95 7 11 90 4 07 11 40 4 47 10 80 4 87 10 30 5 26 9 60 5 13 9 00 4 99 2 13 50 3 78 13 00 4 00 12 40 4 22 11 90 4 44 10 80 4 50 ...

Страница 147: ...SDF09C3E5 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 WH SDF07C3E5 1 WH SDF09C3E5 1 WH SDF12C6E5 1 WH SDF14C6E5 1 WH SDF16C6E5 1 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 148: ...A34K1014 CWA34K1020 18 SOUND PROOF MATERIAL 1 CWG302595 CWG302702 19 THERMOSTAT 2 CWA151065 O 20 ELECTRONIC CONTROLLER MAIN 1 CWA73C6703 CWA73C6704 CWA73C6705 CWA73C6706 CWA73C6707 O 21 TERMINAL BOARD ASS Y 1 CWA28K1217 O 25 TERMINAL BOARD ASS Y 1 CWA28K1229 O 26 TERMINAL BOARD ASS Y 1 CWA28K1230 O 27 ELECTRO MAGNETIC SWITCH 1 K6C1AYY00004 O 28 TERMINAL BOARD ASS Y 1 CWA28K1231 O 29 RESIDUAL CURRE...

Страница 149: ...149 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...

Страница 150: ...150 ...

Страница 151: ...151 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 152: ... 28 CABINET REAR PLATE COMPLETE 1 CWE02C1058 29 CONTROL BOARD CASING 1 CWH10K1100 32 TERMINAL BOARD ASS Y 1 CWA28K1198 O 34 ELECTRONIC CONTROLLER CAPACITOR 1 CWA746184 O 38 ELECTRONIC CONTROLLER NF 1 CWA745745 O 44 ELECTRONIC CONTROLLER MAIN 1 CWA73C4833R CWA73C4834R O 46 REACTOR 2 G0C592J00005 O 48 TERMINAL COVER 1 CWH171039A 49 NUT TERMINAL COVER 1 CWH7080300J 50 FAN MOTOR BRACKET 1 CWD54K1052 5...

Страница 153: ... WH UD07CE5 A 1 WH UD09CE5 A WH UD09CE5 A 1 REMARK 81 ACCESSORY COMPLETE 1 CWH82C1535 82 ACCESSORY CO DRAIN ELBOW 1 CWG87C900 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 154: ...154 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...

Страница 155: ...155 ...

Страница 156: ...156 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 157: ...SENSOR COMP TEMP COIL 1 CWA50C2730 O 26 SENSOR COMP DISCHARGE 1 CWA50C2576 27 SENSOR COMPLETE TOP 1 CWA50C2629 O 27a SENSOR COMP DEF 1 CWA50C2577 O 28 CABINET REAR PLATE COMPLETE 1 CWE02C1059 29 CONTROL BOARD CASING 1 CWH10K1049 31 TERMINAL BOARD ASS Y 1 CWA28K1213 O 36 ELECTRONIC CONTROLLER 1 CWA746169 O 38 ELECTRONIC CONTROLLER NF 1 CWA745446 O 44 ELECTRONIC CONTROLLER MAIN 1 CWA73C4835R CWA73C4...

Страница 158: ...UD14CE5 A 1 WH UD16CE5 A WH UD16CE5 A 1 REMARK 70 EXPANSION VALVE 1 CWB051028 72 ELECTRO MAGNETIC SWITCH 1 K6C1AYY00003 O Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock PAPAMY Printed in Malaysia FB0412 0 ...

Отзывы: