![background image](http://html1.mh-extra.com/html/panasonic/u-200pe1e8/u-200pe1e8_technical-data-and-service-manual_3757413007.webp)
1-9
1
1
1
(A) Indoor Units
High Static Pressure Ducted Type S-200PE1E8A
MODEL No.
Source
Controller P.C.B. Ass'y
Fan (Number...diameter)
mm
Fan motor
W
Model...Nominal output
Power source
rpm
No. of pole...r.p.m. (230V, High)
Coil resistance
(Ambient temperature 20°C)
Ω
BRN – WHT
WHT – VLT
VLT – ORG
: 6.159
: 1.08
: 0.77
ORG – YEL
YEL – BLK
BLK – PNK
: 0.87
: 2.87
: 5.98
Safety device
Operating temperature
Open °C
Close °C
VAC, µF
Run capacitor
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Ω
Valve body
Heat exchanger
Coil
mm
Rows...fin pitch
m
Face area
2
S-200PE1E8A
220 - 230 - 240V, single-phase, 50Hz
CR-UXRP71B-P (Microprocessor)
Centrifugal (2...ø250)
KFC4X-401B3P...400W
220 - 230 - 240V, single-phase, 50Hz
4P...1,211
130 ± 5
(115 ± 5)
450 VAC, 5.0 µF
–
–
–
Aluminium plate fin / Copper tube
3...2.0
0.655
Sec1.indd 9