1-9. ELECTRICAL WIRING

General Precautions on Wiring 

(1)

(4)

(5)
(6)

(7)

(8)

Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following 
the wiring diagram.

(2)

(3)

This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current
Device (RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.
Earth Leakage Circuit Breaker (ELCB) must be incorporated in the fixed wiring in accordance with the wiring regulations. 
The Earth Leakage Circuit Breaker (ELCB) must be an approved 10-16 A, having a contact separation in all poles.
To prevent possible hazards from insulation failure, the unit must be grounded.

Each wiring connection must be done in accordance with the wiring system diagram. 
Wrong wiring may cause the unit to misoperate or become damaged.
Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any 
damage or misoperation that occurs as a result of such unauthorized changes.
Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL
CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:

The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.

(9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop designated by the manufacturer,

because special-purpose tools are required.

Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit (3-Phase)

(A) Power supply

Time delay 

fuse or circuit 

capacity

Wire size

Max. length

U-200PE1E8

14 mm

2

116 m

15 A

U-250PE1E8

14 mm

2

96 m

20 A

Indoor unit

(B) Power supply

Time delay fuse or 

circuit capacity

2.5 mm

2

S-200PE1E8

E1

E2

S-200PE1E8A

S-250PE2E5

S-200PE2E5

S-250PE1E8

10/16 A

Max. 50/30 m

Max. 50/30 m

Max. 30 m

10/16 A

10-16 A

Control wiring

(C) Inter-unit control wiring

(between outdoor and indoor units)

(D) Remote control wiring

0.75 mm

2

 (AWG #18)

0.75 mm

2

 (AWG #18)

Use shielded wiring*

1

Max. 500 m*

2

Max. 1,000 m

NOTE

*1  With ring-type wire terminal.
*2  When the type “E1” is used with maximum length of 500 m for group control, and if the remote controller for the group control 

is wireless, the maximum length will be 400 m.

WARNING

Sec1.indd   29

2014/11/07   10:27:55

Содержание U-200PE1E8

Страница 1: ...SM830194 04 TECHNICAL DATA SERVICE MANUAL Outdoor Unit Indoor Unit S 200PE1E8A S 200PE1E8 S 250PE1E8 Type E1 S 200PE2E5 S 250PE2E5 Type E2 U 200PE1E8 U 250PE1E8 SM830194 11CE SM830194 04_Single_BigPAC...

Страница 2: ...e increase because of the need for effective use of floor space individual control and energy conservation by curtailing heat and carrying power etc Most importantly the multi air conditioner system i...

Страница 3: ...E INSTALLATION SITE 1 55 1 68 1 76 1 78 4 Dimensions of Air Discharge Chamber 6 Dimensions of Snow proof Duct 7 HOW TO INSTALL THE OUTDOOR UNIT 9 HOW TO INSTALL THE INDOOR UNIT 1 56 1 4 Dimensional Da...

Страница 4: ...wer than indoor unit 30 98 Refrigerant tube outer diameter Liquid tube Gas tube m ft m ft m ft mm in mm in mm in mm in mm in kg Refrigerant amount at shipment DIMENSIONS WEIGHT Unit dimensions Height...

Страница 5: ...00 328 5 30 16 98 Outdoor unit is higher than indoor unit 30 98 Outdoor unit is lower than indoor unit 30 98 Refrigerant tube outer diameter Liquid tube mm in Gas tube mm in kg Refrigerant amount at s...

Страница 6: ...amperes A Max Running amperes kW Power input W W C O P A Max Starting amperes FEATURES Controls Thermostat control Timer Fan speeds Indoor Outdoor Airflow direction Indoor Air filter Remote controlle...

Страница 7: ...0 77 ORG YEL YEL BLK BLK PNK 0 87 2 87 5 98 Safety device Operating temperature Open C Close C VAC F Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Valve body Heat exchanger Coi...

Страница 8: ...0 ORG YEL 2 21 YEL BLK 10 33 BLK PNK 12 90 Safety device Operating temperature Open C Close C VAC F Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Valve body Heat exchanger Coil...

Страница 9: ...h Coil resistance Ambient temperature 20 C Safety device Operating temperature Open C Close C VAC F Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Valve body Heat exchanger Coil...

Страница 10: ...OFF 4 15 0 0 15 3 15 0 3 MPa ON Fan mm Number diameter m3 h Air circulation Fan speeds Max Fan motor Model No Source No of pole W Nominal output Safety device Operating temperature Open C Close C VAC...

Страница 11: ...OFF MPa ON Fan mm Number diameter m3 h Air circulation Fan speeds Max Fan motor Model No Source No of pole W Nominal output Safety device Operating temperature Open C Close C VAC F Heat exchanger Coi...

Страница 12: ...mistor Discharge gas sensor TH5 Resistance k 60 C 12 4 5 90 C 4 6 5 70 C 8 7 5 100 C 3 4 7 75 C 7 4 5 110 C 2 5 7 80 C 6 3 5 120 C 1 9 7 85 C 5 3 5 130 C 1 5 7 Relay Comp Magnetic Contactor VAC Coil r...

Страница 13: ...nsor TH5 Resistance k Relay Comp Magnetic Contactor VAC Coil rated VAC A Contact rating Coil resistance at 20 C Sol Control Valve 4 way valve 4 way valve Electro magnetic coil Thermal cut off temperat...

Страница 14: ...bolt 26 3 5 Holes all around 28 3 5 Holes all around 10 100P 1000 106 44 1070 1310 67 67 1200 Suspension bolt pitch 113 236 364 364 1334 60 43 320 100 50 178 23 209 344 1230 41 Refrigerant liquid lin...

Страница 15: ...joint gas tube 25 4 mm Brazing Power supply outlet Drain port O D 32 mm Duct connection for suction Duct connection for discharge 1170 Suspension bolt pitch 28 3 5 Holes all around 1200 Suspension bo...

Страница 16: ...the remaining 3 holes Mounting hole 4 R6 5 anchor bolt M10 Refrigerant tubing liquid tube flared connection 9 52 Refrigerant tubing gas tube flared connection 19 05 Refrigerant tubing port Electrical...

Страница 17: ...Bottom removable connection port Refrigerant tubing connection port Remark There are two types of supplied tubings The one tubing port 19 05 flare process is connected to the flared connection of the...

Страница 18: ...umulator Gas line service valve Check valve 4 way valve Liquid line service valve Freeze prevention coil Attached to the heat exchanger Strainer Heat exchanger Strainer Distributor Accumulator Cooling...

Страница 19: ...er Heat exchanger Strainer Distributor Heat exchanger Strainer Distributor Heat exchanger Distributor Accumulator Compressor Accumulator Gas line service valve 4 way valve Liquid line service valve St...

Страница 20: ...C DB 15 C DB 15 C DB 20 C DB Indoor air intake temp 32 C DB 18 C DB 30 C DB 16 C DB Temperature Minimum Minimum Maximum Maximum 1 6 Operating Range Temperature Cooling Heating Outdoor air intake temp...

Страница 21: ...Rated capacity ratio for heating 1 The graphs of the characteristics show the value under the following conditions Equivalent tubing length 7 5m Difference of elevation 0m Wind speed High 2 marking in...

Страница 22: ...63 250 10 20 30 40 50 60 70 80 90 125 NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 63 MODEL SOUND LEVEL CONDITION Sound pressure level dB 0dB 0 0002 bar Approximate minimum audible limit for continuous noise F...

Страница 23: ...limit for continuous noise Overall Frequency at center of sound pressure band Hz Octave Band Level dB 0dB 0 0002 bar Standard Quiet mode REMARKS NOTE 1 Value obtained in the actual place where the uni...

Страница 24: ...essure band Hz Octave Band Level dB 0dB 0 0002 bar U 250PE1E8 72 dB A Cooling MODEL SOUND POWER LEVEL REMARKS NOTE 1 Value obtained in the actual place where the unit is installed may be slightly high...

Страница 25: ...please refer to your LOCAL ELECTRICAL CODES before beginning You must ensure that installation complies with all relevant rules and regulations To prevent malfunction of the air conditioner caused by...

Страница 26: ...ructions supplied with the outdoor unit Auto address setting can be executed by remote controller automatically Refer to the installation instructions supplied with the remote controller optional L2 L...

Страница 27: ...t Branch point More than 2m required Fig 1 3 Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit NO Branch point 5 Use shielded wires for inter unit control wiring c and ground the shield on...

Страница 28: ...right bottom on the outdoor main control PCB from all outdoor units except any one of the outdoor units When shipping In shorted condition 2 Do not install the inter unit control wiring in a way that...

Страница 29: ...nd the shield wires insulated in Step 2 Fig 1 12 Screw and Special washer Ring pressure terminal Terminal plate Ring pressure terminal Screw Special washer Wire Wire Ring pressure terminal Strip 10 mm...

Страница 30: ...DATA 3 1 Outdoor Units Electric Wiring Diagram Schematic Diagram 3 2 3 2 Indoor Units Electric Wiring Diagram Schematic Diagram 3 4 High Static Pressure Ducted Type SM830194 04_Single_BigPAC indb 1 2...

Страница 31: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 SM830194 04_Single_BigPAC indb 2 2014 10 17 20 32 42...

Страница 32: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 SM830194 04_Single_BigPAC indb 3 2014 10 17 20 32 42...

Страница 33: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram SM830194 04_Single_BigPAC indb 5 2014 10 17 20 32 42...

Страница 34: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram SM830194 04_Single_BigPAC indb 6 2014 10 17 20 32 43...

Страница 35: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram SM830194 04_Single_BigPAC indb 7 2014 10 17 20 32 43...

Страница 36: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram SM830194 04_Single_BigPAC indb 8 2014 10 17 20 32 44...

Страница 37: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram SM830194 04_Single_BigPAC indb 9 2014 10 17 20 32 44...

Страница 38: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram SM830194 04_Single_BigPAC indb 10 2014 10 17 20 32 44...

Отзывы: