1-32

1

1

 

NOTE

<Type E1>

(1) Refer to “Recommended Wire Length and Wire 

Diameter for Power Supply System” for the explanation 

of “A”, “B”, “C” and “D” in the above diagrams.

(2) The basic connection diagram of the indoor unit 

shows the 7P terminal board, so the terminal boards 

in your equipment may differ from the diagram.

(3) Refrigerant Circuit (R.C.) address should be set 

before turning the power on.

(4) Regarding R.C. address setting, refer to the installation

instructions supplied with the outdoor unit. Auto address
setting can be executed by remote controller automatically.
Refer to the installation instructions supplied with the
remote controller (optional).

Power 

supply

Inter-unit 

control 

wiring

L

N

U1

U2

R1

R2

7P terminal board

Type E1

Remote 

control 

wiring

L2

L1

U2

U1

L3

N

A

L1

L2

L3

N

U2

U1

L

N

1
2

2

1

D

B

L

N

2

1

C

Power supply*

220 – 240 V  ~50/60 Hz

Remote 

controller

WHT 

BLK

* Regarding S-250PE1E8, the power supply is 

220-240V, 50Hz only.

Ground

Ground

Ground

Outdoor unit (3-phase)

INV unit

Power supply

380 – 415 V, 3N, ~ 50/60 Hz

Indoor 

unit

CAUTION

(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug

(CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units

except any one of the outdoor units. (When shipping: In shorted condition.)

(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 1-5)

(3) Use shielded wires for inter-unit control wiring (c) and 

ground the shield on both sides, otherwise misoperation 

from noise my occur. (Fig. 1-6)

Connect wiring as shown in Wiring System Diagram.”

Outdoor unit

Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Prohibited

Prohibited

Indoor unit

Fig. 1-5

Fig. 1-6

Shielded wire

Ground

Ground

(4) Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 

5 or 3 *1.5 mm

2

 flexible cord. Type designation 60245 IEC 57 (H05RN-F, GP85PCP etc.) or heavier cord.

Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to 

CENELEC (HAR) rating specifications) or use the cables based on IEC standard. (60245 IEC57, 60245 

IEC66)

Loose wiring may cause the terminal to overheat or result in unit malfunction.

A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.

When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal”

and fasten the wire securely with the fixing screw of the terminal plate.

WARNING

Fig. 1-8

Fig. 1-7

How to connect wiring to the terminal

 For stranded wiring

(1)

(2)

(3)

(4)

Cut the wire end with cutting pliers, then strip the 
insulation to expose the stranded wiring about 
10 mm and tightly twist the wire ends. (Fig. 1-7)
Using a Phillips head screwdriver, remove the 
terminal screw(s) on the terminal plate.
Using a ring connector fastener or pliers, securely 
clamp each stripped wire end with a ring pressure 
terminal.
Place the ring pressure terminal, and replace and 
tighten the removed terminal screw using a 
screwdriver. (Fig. 1-8)

Insulation tape

8mm

Insulation tape

Shield mesh

Shield mesh

Fig. 1-9

Fig. 1-10

Fig. 1-11

Fig. 1-12

 Examples of shield wires

(1)
(2)

(3)
(4)

Remove cable coat not to scratch braided shield. (Fig. 1-9) 
Unbraid the braided shield carefully and twist the 
unbraided shield wires tightly together. Insulate the shield 
wires by covering them with an insulation tube or wrapping 
insulation tape around them. (Fig. 1-10)
Remove coat of signal wire. (Fig. 1-11)
Attach ring pressure terminals to the signal wires and 
the shield wires insulated in Step (2). (Fig. 1-12)

Screw and 

Special washer

Ring 

pressure 

terminal

Terminal plate

Ring pressure 

terminal

Screw

Special 

washer

Wire

Wire

Ring 

pressure 

terminal

Strip 10 mm

Stranded wire

Wiring sample

Outdoor Unit

1.

Earth

Use this screw when connecting to  

ground for the Inter-unit control wiring.

Power Supply

Inter-unit Control Wiring

2.

Earth

Use this screw when connecting to  

ground for the Inter-unit control wiring.

Power Supply

Inter-unit Control Wiring

3.

Earth

Use this screw when connecting to 

ground for the Inter-unit control wiring.

Clamper * 

(Field supply)

*  First remove the attached resin fixture. 

Then lead the clamper (field supply) through 

the screw hole and fix the power supply wire.

Power Supply

Inter-unit Control Wiring

Indoor Unit

<Type E1>

<Type E2>

Use this screw when connecting 

to ground the shield for the 

Inter-unit control wiring.

Remote Control 

Wiring

Power 

Supply

Functional ground screw (External Electronic 

Expansion Valve Kit and Schedule Timer)

Inter-unit 

Control Wiring

Use this screw when connecting the shield for 

the Inter-unit control wiring to ground.

Power 

Supply

Inter-unit 

Control Wiring

Remote 

Control Wiring

Functional ground screw

Sec1.indd   32

2014/11/07   10:27:56

Содержание U-200PE1E8

Страница 1: ...SM830194 04 TECHNICAL DATA SERVICE MANUAL Outdoor Unit Indoor Unit S 200PE1E8A S 200PE1E8 S 250PE1E8 Type E1 S 200PE2E5 S 250PE2E5 Type E2 U 200PE1E8 U 250PE1E8 SM830194 11CE SM830194 04_Single_BigPAC...

Страница 2: ...e increase because of the need for effective use of floor space individual control and energy conservation by curtailing heat and carrying power etc Most importantly the multi air conditioner system i...

Страница 3: ...E INSTALLATION SITE 1 55 1 68 1 76 1 78 4 Dimensions of Air Discharge Chamber 6 Dimensions of Snow proof Duct 7 HOW TO INSTALL THE OUTDOOR UNIT 9 HOW TO INSTALL THE INDOOR UNIT 1 56 1 4 Dimensional Da...

Страница 4: ...wer than indoor unit 30 98 Refrigerant tube outer diameter Liquid tube Gas tube m ft m ft m ft mm in mm in mm in mm in mm in kg Refrigerant amount at shipment DIMENSIONS WEIGHT Unit dimensions Height...

Страница 5: ...00 328 5 30 16 98 Outdoor unit is higher than indoor unit 30 98 Outdoor unit is lower than indoor unit 30 98 Refrigerant tube outer diameter Liquid tube mm in Gas tube mm in kg Refrigerant amount at s...

Страница 6: ...amperes A Max Running amperes kW Power input W W C O P A Max Starting amperes FEATURES Controls Thermostat control Timer Fan speeds Indoor Outdoor Airflow direction Indoor Air filter Remote controlle...

Страница 7: ...0 77 ORG YEL YEL BLK BLK PNK 0 87 2 87 5 98 Safety device Operating temperature Open C Close C VAC F Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Valve body Heat exchanger Coi...

Страница 8: ...0 ORG YEL 2 21 YEL BLK 10 33 BLK PNK 12 90 Safety device Operating temperature Open C Close C VAC F Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Valve body Heat exchanger Coil...

Страница 9: ...h Coil resistance Ambient temperature 20 C Safety device Operating temperature Open C Close C VAC F Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Valve body Heat exchanger Coil...

Страница 10: ...OFF 4 15 0 0 15 3 15 0 3 MPa ON Fan mm Number diameter m3 h Air circulation Fan speeds Max Fan motor Model No Source No of pole W Nominal output Safety device Operating temperature Open C Close C VAC...

Страница 11: ...OFF MPa ON Fan mm Number diameter m3 h Air circulation Fan speeds Max Fan motor Model No Source No of pole W Nominal output Safety device Operating temperature Open C Close C VAC F Heat exchanger Coi...

Страница 12: ...mistor Discharge gas sensor TH5 Resistance k 60 C 12 4 5 90 C 4 6 5 70 C 8 7 5 100 C 3 4 7 75 C 7 4 5 110 C 2 5 7 80 C 6 3 5 120 C 1 9 7 85 C 5 3 5 130 C 1 5 7 Relay Comp Magnetic Contactor VAC Coil r...

Страница 13: ...nsor TH5 Resistance k Relay Comp Magnetic Contactor VAC Coil rated VAC A Contact rating Coil resistance at 20 C Sol Control Valve 4 way valve 4 way valve Electro magnetic coil Thermal cut off temperat...

Страница 14: ...bolt 26 3 5 Holes all around 28 3 5 Holes all around 10 100P 1000 106 44 1070 1310 67 67 1200 Suspension bolt pitch 113 236 364 364 1334 60 43 320 100 50 178 23 209 344 1230 41 Refrigerant liquid lin...

Страница 15: ...joint gas tube 25 4 mm Brazing Power supply outlet Drain port O D 32 mm Duct connection for suction Duct connection for discharge 1170 Suspension bolt pitch 28 3 5 Holes all around 1200 Suspension bo...

Страница 16: ...the remaining 3 holes Mounting hole 4 R6 5 anchor bolt M10 Refrigerant tubing liquid tube flared connection 9 52 Refrigerant tubing gas tube flared connection 19 05 Refrigerant tubing port Electrical...

Страница 17: ...Bottom removable connection port Refrigerant tubing connection port Remark There are two types of supplied tubings The one tubing port 19 05 flare process is connected to the flared connection of the...

Страница 18: ...umulator Gas line service valve Check valve 4 way valve Liquid line service valve Freeze prevention coil Attached to the heat exchanger Strainer Heat exchanger Strainer Distributor Accumulator Cooling...

Страница 19: ...er Heat exchanger Strainer Distributor Heat exchanger Strainer Distributor Heat exchanger Distributor Accumulator Compressor Accumulator Gas line service valve 4 way valve Liquid line service valve St...

Страница 20: ...C DB 15 C DB 15 C DB 20 C DB Indoor air intake temp 32 C DB 18 C DB 30 C DB 16 C DB Temperature Minimum Minimum Maximum Maximum 1 6 Operating Range Temperature Cooling Heating Outdoor air intake temp...

Страница 21: ...Rated capacity ratio for heating 1 The graphs of the characteristics show the value under the following conditions Equivalent tubing length 7 5m Difference of elevation 0m Wind speed High 2 marking in...

Страница 22: ...63 250 10 20 30 40 50 60 70 80 90 125 NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 63 MODEL SOUND LEVEL CONDITION Sound pressure level dB 0dB 0 0002 bar Approximate minimum audible limit for continuous noise F...

Страница 23: ...limit for continuous noise Overall Frequency at center of sound pressure band Hz Octave Band Level dB 0dB 0 0002 bar Standard Quiet mode REMARKS NOTE 1 Value obtained in the actual place where the uni...

Страница 24: ...essure band Hz Octave Band Level dB 0dB 0 0002 bar U 250PE1E8 72 dB A Cooling MODEL SOUND POWER LEVEL REMARKS NOTE 1 Value obtained in the actual place where the unit is installed may be slightly high...

Страница 25: ...please refer to your LOCAL ELECTRICAL CODES before beginning You must ensure that installation complies with all relevant rules and regulations To prevent malfunction of the air conditioner caused by...

Страница 26: ...ructions supplied with the outdoor unit Auto address setting can be executed by remote controller automatically Refer to the installation instructions supplied with the remote controller optional L2 L...

Страница 27: ...t Branch point More than 2m required Fig 1 3 Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit NO Branch point 5 Use shielded wires for inter unit control wiring c and ground the shield on...

Страница 28: ...right bottom on the outdoor main control PCB from all outdoor units except any one of the outdoor units When shipping In shorted condition 2 Do not install the inter unit control wiring in a way that...

Страница 29: ...nd the shield wires insulated in Step 2 Fig 1 12 Screw and Special washer Ring pressure terminal Terminal plate Ring pressure terminal Screw Special washer Wire Wire Ring pressure terminal Strip 10 mm...

Страница 30: ...DATA 3 1 Outdoor Units Electric Wiring Diagram Schematic Diagram 3 2 3 2 Indoor Units Electric Wiring Diagram Schematic Diagram 3 4 High Static Pressure Ducted Type SM830194 04_Single_BigPAC indb 1 2...

Страница 31: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 SM830194 04_Single_BigPAC indb 2 2014 10 17 20 32 42...

Страница 32: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 SM830194 04_Single_BigPAC indb 3 2014 10 17 20 32 42...

Страница 33: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram SM830194 04_Single_BigPAC indb 5 2014 10 17 20 32 42...

Страница 34: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram SM830194 04_Single_BigPAC indb 6 2014 10 17 20 32 43...

Страница 35: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram SM830194 04_Single_BigPAC indb 7 2014 10 17 20 32 43...

Страница 36: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram SM830194 04_Single_BigPAC indb 8 2014 10 17 20 32 44...

Страница 37: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram SM830194 04_Single_BigPAC indb 9 2014 10 17 20 32 44...

Страница 38: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram SM830194 04_Single_BigPAC indb 10 2014 10 17 20 32 44...

Отзывы: