D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed setting.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follow.
* When COMP is ON
1
→
2
→
3
(Shift to 4 when COMP is OFF)
* When COMP is OFF
4
→
5
→
4
←→
5
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
8.1.8. Outdoor Fan Motor Operation
•
6 pole induction, 1 speed 780 rpm (XE9DK), 810 rpm (XE12DK).
•
It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
23
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
Содержание SUPER DELUXE CS-XE9DKE
Страница 10: ...4 Dimensions 10 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 11: ...11 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 12: ...5 Refrigeration Cycle Diagram 12 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 13: ...6 Block Diagram 13 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 14: ...7 Wiring Diagram 14 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 89: ...13 Technical Data 89 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 90: ...90 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 102: ...102 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 103: ...How to use electronic circuit diagram 103 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 104: ...18 1 Remote Control 104 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 105: ...18 2 Print Pattern Indoor Unit Printed Circuit Board Main 105 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...
Страница 107: ...18 5 Print Pattern Outdoor Unit Printed Circuit Board Main 107 CS XE9DKE CU XE9DKE CS XE12DKE CU XE12DKE...