19
© Panasonic Electric Works SUNX Co., Ltd. 2011 MJE-SFBHC No.0024-49V
Functional Descriptions
<Minimum sensing object>
Floating blanking function
Ineffective
Effective
1 beam channel
2 beam channels
3 beam channels
SF4B-F
+
SF4B-F
<V2>
ø14mm
ø24mm
ø34mm
ø44mm
SF4B-H
+
SF4B-H
<V2>
ø25mm
ø45mm
ø65mm
ø85mm
SF4B-A
+
SF4B-A
<V2>
ø45mm
ø85mm
ø125mm
ø165mm
3-2-3 Auxiliary Output Switching Function
This function changes the operation state of the auxiliary output (AUX4) of
SF-C14EX
. It is useful
when desired to make an indicator to operate or inform the operation state of the
SF4B
/
SF4B<V2>
series to PLC.
The following settings are selectable.
This function enables to set auxiliary output of the
SF4B
/
SF4B<V2>
series.
Setting
mode
Auxiliary output setting of the
SF4B
/
SF4B<V2>
series
Operation of the auxiliary output corresponding to
SF4B
/
SF4B<V2>
series state
Emission
halt
State of sensing area when emitting
Lockout
Unshielded
Shielded
Unstable
light-receiving
condition
Others
0
Negative logic of the control out-
put (OSSD 1 / 2) (factory setting)
ON
OFF when OSSD is ON
ON when OSSD is OFF
ON
1
Positive logic of the control
output (OSSD 1 / 2)
OFF
ON when OSSD is ON
OFF when OSSD is OFF
OFF
2
ON when emitting
OFF
ON
OFF
3
OFF when emitting
ON
OFF
ON
4
OFF under unstable light
receiving condition (Note 1)
(Note 3)
OFF
ON
(Note 3)
(Note 3)
5
ON under unstable light
receiving condition (Note 1)
(Note 3)
ON
OFF
(Note 3)
(Note 3)
6
ON during muting
OFF (Note 4)
7
OFF during muting
ON (Note 4)
8
ON in light receiving condition
(Note 2)
OFF
ON
OFF
OFF
9
OFF in light receiving condition
(Note 2)
ON
OFF
ON
ON
Y*&+=&&$&+&| |}}
under unstable light-receiving condition does not work.
2) By the setting of ON / OFF in light receiving condition, light-receiving / light interrupted condition is output regardless of
*&+=&&$&
<e.g.>
*&+*&"&-
tion, the safety output 1 / 2 are in ON sate, however, the auxiliary output becomes OFF since the
SF4B
/
SF4B<V2>
series has been detecting the obstacle.
3) The state of the auxiliary output remains the same even if the
SF4B
/
SF4B<V2>
series state changes.
4) When using in combination with
SF-C14EX
, the muting function cannot be set on
SF4B
/
SF4B<V2>
series side.
Thus, the state of the auxiliary output remains the same regardless of the
SF4B
/
SF4B<V2>
series state.
@=&&+&%|}}
when an obstacle exists in the sensing range regardless of the incident light intensity.
Do not use the auxiliary output for the purpose of stopping the machine in which the
SF4B
/
SF4B<V2> series
is installed. Failure to do so could result in death or serious injury.