Fig. 3-11

3-5-2.  

Installing the Drain Pipe

CAUTION

 

Do not apply force to the drain port when connecting the 

drain pipe. Install and fix it near the indoor unit as close 

as possible.

 

Do not use adhesive when connecting the drain port pipe 

and the drain hose.

(1) How to Install the Drain Pipe

 1)  First insert the supplied hose band into the drain port 

pipe. Then make sure the head of the screw is facing 

toward a technical engineer when placing the screw of 

the hose band at an upward angle.

 2)  Insert the soft PVC socket of the supplied drain hose 

to the drain port pipe. Do not use adhesive when 

connecting the drain hose to the drain port pipe. 

Insert it until the tip of the drain hose contacts the circular 

projection rib of the drain port pipe.

 3)  Move the hose band so that the center position of the 

hose band can be placed approx. 30 mm away from the 

external plate of the indoor unit. (Fig. 3-11)

 4)  Screw the drain hose tightly facing the screw of the hose 

band upward. (Torque: 2.5 N·m - 3.4 N·m) (If the screw 

is tightened beneath the drain hose, the troubles will be 

generated.) Pay attention not to make hose band overlap 

the circular projection rib and the sealed circulation 

projection of the drain port pipe.

 5)  Apply approx. 2 

g

 of adhesive on both sides of the drain 

hose without connection of the hard PVC socket and the 

hard PVC joint (VP25) in the local supply.

 6)  Connect the drain hose and the hard PVC joint so that 

the adhesive area of both sides can be overlapped. 

Wipe off the protrusion-adhesive with a soft cloth.

Drain port

Do not use adhesive here.

*   Drain port may possibly be damaged if 

PVC adhesive is used.

*   After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe.

Do not make hose band overlap the circular projection 
rib and the sealed circulation projection of the drain 
port pipe. (Torque: 2.5 N·m - 3.4 N·m)

Note:

Be sure to tightly insert the hard PVC 
pipe joint (including elbow) minimum 
20 mm or more.

57 mm

20 mm or more

Drain insulator (supplied)

*   However, do not use the hard PVC 

pipe joint allowable more than 55 mm 
insertion.

Packing (supplied)

Approx. 5 mm

Approx. 30 mm

Adhere with PVC adhesive.

*  

Apply approx. 2 

g

 of adhesive on both sides of the 

drain hose without connection of the hard PVC 
socket and the hard PVC joint (VP25) in the local 
supply. Wipe off the protrusion-adhesive with a soft 
cloth.

Hard PVC pipe 

(VP25 field supplied)

Hard PVC socket 

Hose band (supplied)

Soft PVC socket

Drain hose

(supplied)

Circular 
projection rib

Sealed 
circulation 
projection 
rib

Indoor unit

Indoor unit

Sealed circulation 
projection rib

Circular projection rib

(Drainage check section 
on drain port, transparent)

Pana̲indoor̲all.indb   10

Pana̲indoor̲all.indb   10

2013/12/16   15:15:15

2013/12/16   15:15:15

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание S-36MU1E5A

Страница 1: ...ocedere con l installazione Prestare particolare attenzione alla sezione IMPORTANTE all inizio della pagina NEDERLANDS Lees de installatie instructies zorgvuldig door voor u begint met de installatie U moet vooral het gedeelte waar BELANGRIJK boven staat heel goed lezen PORTUGUÊS Leia cuidadosamente as instruções de instalação antes de prosseguir com a instalação Em particular é necessário ler as ...

Страница 2: ...ntal injury or death Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard Provide a power outlet to be used exclusively for each unit Provide a power outlet exclusively for each unit and full disconnection means having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring rules To prevent po...

Страница 3: ...p the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced WARNING This product must not be modified or disassembled under any circumstances Modified or disassembled unit may cause fire electric shock or injury Do not clean inside the indoor and outdoor units by users Engage authorized dealer or specialist for cleaning In c...

Страница 4: ...Connecting Tubing Between Indoor and Outdoor Units 5 3 Insulating the Refrigerant Tubing 5 4 Taping the Tubes 5 5 Finishing the Installation 6 HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH SPEC WIRED REMOTE CONTROLLER OPTIONAL PART 18 NOTE Refer to the Operating Instructions attached to the optional Timer Remote Controller or optional High spec Wired Re mote Controller 7 HOW TO INSTALL THE CE...

Страница 5: ...ose Packing 1 Drain insulator 1 Clamper 3 Operating Instructions 1 Installation Instructions 1 Use M10 for suspension bolts Field supply for suspension bolts and nuts 1 3 Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigerant tubing 2 Foamed polyethylene insulation for copper...

Страница 6: ...ct a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length L from the outdoor unit as detailed in the installation manual packed with the outdoor unit allow room f...

Страница 7: ... The diagram and table Fig 3 3 and Table 3 2 show the relationship between the positions of the suspension fitting unit and panel Use the nut field supply and washer supplied for upper and lower position of the suspension lug Table 3 2 Unit mm Length Type A B C D E 22 28 36 45 56 60 73 90 121 171 256 180 130 106 140 160 121 171 319 180 130 Hole in anchor Hole in plug Concrete Insert Suspension bol...

Страница 8: ... shown in Fig 3 5 Use 1 nut and 1 washer for the upper side and 2 nuts and 1 washer for the lower side so that the unit will not fall off the suspension lugs 4 Adjust so that the distance between the unit and the ceiling bottom is 12 to 17 mm Tighten the nuts on the upper side and lower side of the suspension lug 5 Remove the protective polyethylene used to protect the fan parts during transport 6...

Страница 9: ... leakage Fig 3 6 2 Limitations of Drain Pipe Connection CAUTION Do not install the drain pipe with an upward gradient from the drain port connection This will cause the drain water to flow backward and leak when the unit is not operating Fig 3 7 Do not install an air bleeder as this may cause water to spray from the drain pipe outlet Fig 3 7 Do not provide U trap or bell shaped trap in the middle ...

Страница 10: ...f the hard PVC socket and the hard PVC joint VP25 in the local supply 6 Connect the drain hose and the hard PVC joint so that the adhesive area of both sides can be overlapped Wipe off the protrusion adhesive with a soft cloth Drain port Do not use adhesive here Drain port may possibly be damaged if PVC adhesive is used After checking the drainage wrap the supplied packing and drain pipe insulator...

Страница 11: ...heck the following items Checkpoint Symptom Check Remark 1 Make sure whether indoor and outdoor units are correctly installed Fall vibration noise 2 Make sure whether gas leakage is tested No cooling no heating 3 Make sure whether insulation is completed Refrigerant piping and drain piping Water leakage 4 Make sure whether drain water is running smoothly Water leakage 5 Make sure whether the power...

Страница 12: ...ed it must be replaced by a repair shop designated by the manufacturer because special purpose tools are required 4 2 Recommended Wire Length and Wire Diameter for Power Supply System Indoor unit Type B Power supply Time delay fuse or circuit capacity 2 5 mm2 U1 Max 130 m 10 16 A Control wiring C Inter unit between outdoor and indoor units control wiring D Remote control wiring E Control wiring fo...

Страница 13: ...er supply Unit control line Remote control line U1 Type U2 U1 R2 R1 L N R2 R1 R2 R1 R2 R1 2 1 2 1 U2 U1 L N U2 U1 L N U2 U1 L N 2 1 2 1 2 1 D E C B L N L N L N L N 2 1 B B B C D D C 2 1 L1 L2 L3 N 2 1 L1 L2 L3 N C L1 L2 L3 N L1 L2 L3 N U2 U1 Power supply 220 230 240V 50 60 Hz Power supply 220 230 240V 50 60 Hz Power supply 220 230 240V 50 60 Hz Power supply 220 230 240V 50 60 Hz Remote controller ...

Страница 14: ...ndoor unit Indoor unit Indoor unit Indoor unit NO Branch point 5 Use shielded wires for inter unit control wiring c and ground the shield on both sides otherwise misoperation from noise may occur Fig 4 6 Connect wiring as shown in Section 4 3 Wiring System Diagrams Fig 4 6 6 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 or 3 1 5 mm2 flexible cor...

Страница 15: ...using a screwdriver Fig 4 8 Examples of shield wires 1 Remove cable coat not to scratch braided shield Fig 4 9 2 Unbraid the braided shield carefully and twist the unbraided shield wires tightly together Insulate the shield wires by covering them with an insulation tube or wrapping insulation tape around them Fig 4 10 3 Remove coat of signal wire Fig 4 11 4 Attach ring pressure terminals to the si...

Страница 16: ...g gas leaks Fig 5 4 Apply refrigerant lubricant Fig 5 4 3 For proper connection align the union tube and flare tube straight with each other then screw on the flare nut lightly at first to obtain a smooth match Fig 5 5 Flare nut Union Fig 5 5 Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to the liquid tubing side valve using a flare Cautions During...

Страница 17: ...ent space to access the valves and to allow the panels to be attached and removed Taping the flare nuts Wind the white insulation tape around the flare nuts at the gas tube connections Then cover up the tubing connections with the flare insulator and fill the gap at the union with the supplied black insulation tape Finally fasten the insulator at both ends with the supplied vinyl clamps Fig 5 8 Fl...

Страница 18: ... 4 Way Cassette Type U1 Type Accessories Ceiling panel 1 Washer head screws 4 M5 40 ø18 Installation notes 1 Screws 4 4 12 7 1 Preparation for Ceiling Panel Installation 1 Checking the unit position 1 Check that the ceiling hole is within this range 860 mm 860 mm to 910 mm 910 mm 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling ...

Страница 19: ... corner with the correct positions on the unit When removing the ceiling panel push the temporary latches outward while holding the ceiling panel Fig 7 4 Fig 7 4 2 Align the panel installation holes and the unit screw holes 3 Tighten the supplied washer head screws at the 4 panel installation locations so that the panel is attached tightly to the unit Fig 7 5 Fig 7 5 4 Check that the panel is atta...

Страница 20: ...nd change the directions according to customer s requests When attaching the air intake grille be careful that the flap lead wire does not become caught Be sure to attach the safety cord that prevents the air intake grille from dropping off to the ceiling panel unit as shown in the figure below With this ceiling panel the directions of the air intake grille lattices when installing multiple units ...

Страница 21: ...se steps 1 Open the electrical component box cover then check the indoor unit control PCB 2 Connect the jumper connector 2P yellow which was supplied with the accessory to the correct connector pin on the indoor unit control PCB according to the setting number which was confirmed in Table for DC Fan Motor Tap Settings Setting No 3 Then connect the jumper connector to the connector pin TP3 2P yello...

Страница 22: ...ttons to select the desired setting data Flap position 1 2 3 4 5 Fig 7 11 Setting data refer to Fig 7 11 Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to position 5 and stay When the flap position is set to 4 or 5 and the unit is in the cooling or dry mo...

Страница 23: ...apy water rinse it in clean water and dry it How to remove the filter 4 Way Cassette Type U1 1 Use a screwdriver to remove the bolt screw on each side for the two latches Be sure to reattach the two bolt screws after cleaning 2 Slide the latches of the air intake grille in the direction of the inside to open the grille 3 The air intake grille opens downward CAUTION When cleaning the air filter nev...

Страница 24: ...mes rotates because of drying heat exchanger due to settings Wind direction changes while operating Wind direction setting cannot be made Wind direction cannot be changed When air discharge temperature is low or during defrost operation horizontal wind flow is made automatically Flap position is occasionally set up individually When wind direction is changed flap operates several times and stops a...

Страница 25: ...f the inspection mark and the letters E F H L P in combination with the numbers appear on the LCD of the remote controller Tips for Energy Saving Avoid Do not block the air intake and outlet of the unit If either is obstructed the unit will not work well and may be damaged Do not let direct sunlight into the room Use sunshades blinds or curtains If the walls and ceiling of the room are warmed by t...

Страница 26: ...26 NOTE Pana indoor all indb 26 Pana indoor all indb 26 2013 12 16 15 15 24 2013 12 16 15 15 24 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 27: ...F616390 DC1213 0 Printed in China Pana indoor all indb b Pana indoor all indb b 2013 12 16 15 18 07 2013 12 16 15 18 07 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Отзывы: