3-5-3. Checking the Drainage
Be careful since the fan will start
when you short the pin on the indoor
control board.
After wiring (refer to 4. ELECTRICAL WIRING.) and drain
piping are completed, use the following procedure to check
that the water will drain smoothly. For this, prepare a bucket
and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour about 1,200 cc of water into the drain pan to
check drainage. (Fig. 3-12)
(3) Short the check pin (CHK) on the indoor control board
and operate the drain pump. Check the water flow
through the transparent drain pipe and see if there is any
leakage.
(4) When the check of drainage is complete, open the check
pin (CHK) and remount the tube cover.
(5) Checkpoint after installation
After installation of indoor and outdoor units, panels and
electrical wiring, check the following items.
Checkpoint
Symptom
Check
Remark
1
Make sure whether indoor and outdoor units
are correctly installed.
Fall, vibration, noise
2 Make sure whether gas leakage is tested.
No cooling, no heating
3
Make sure whether insulation is completed.
(Refrigerant piping and drain piping)
Water leakage
4
Make sure whether drain water is running
smoothly.
Water leakage
5
Make sure whether the power voltage
matches the nameplate.
Inoperative, burnout
6
Make sure whether there is miswiring or
incorrect connection.
Inoperative, burnout
7
Make sure whether the ground construction
is completed.
Ground leakage
8
Make sure whether the wire gauge is
followed by the recommended specifications.
Inoperative, burnout
9
Make sure whether the air intake and air
outlet of the indoor and outdoor units are
sealed by obstacles.
No cooling, no heating
Fig. 3-12
Drainage check
Over 100 mm
Plastic container
for water intake
Water (Approx. 1,200 cc)
Drain pan outlet