VRF SYSTEMS Indoor Unit
7
VRF SYSTEMS Indoor Unit
1. Test Run
<Procedure of CZ-RTC3>
1
Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select "4. Test run" on the LCD display and press
the
button.
Change the display from OFF to ON by pressing
the
or
button. Then press the
button.
Fig. 1
3
Press the
button. “TEST” will be displayed
on the LCD display.
4
Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
[
] Confirm
Test run
Change
20:30 (THU)
Test run
ON
CZ-RTC3
TEST
START
[
]
20:30 (THU)
TEST
20:30 (THU)
COOL
MODE
7-1. Test Run
Regarding the detailed settings for the test run, refer to the service manual for each outdoor unit.
If operating the high-spec wired remote controller (CZ-RTC3) is necessary, follow the procedure
described below.
SM830232-00̲欧州向けVRF Indoor̲201404.indb 2
SM830232-00̲欧州向けVRF Indoor̲201404.indb 2
2014/04/17 15:00:41
2014/04/17 15:00:41
Содержание S-22MU1E5A
Страница 7: ...MEMO 1 2...
Страница 20: ...3 1 VRF SYSTEMS Indoor Unit 3 3 OUTDOOR UNIT REPAIR PROCEDURES Refer to the Service Manual of Outdoor Unit...
Страница 21: ...MEMO 3 2...
Страница 23: ...MEMO 4 2...
Страница 49: ...MEMO 6 2...
Страница 53: ...201404...