2
- 5
VRF SYSTEMS Indoor Unit
2
3. Automatic Fan Speed Control
3. Automatic Fan Speed Control
①
The indoor fan mode is controlled as shown below during the automatic fan mode.
②
The fan mode does not change for 3 minutes during cooling operation and 1 minute during heating
operation once it is changed.
③
The values in the parenthesis are when the remote controller sensor is enabled.
+3
+2
+1
(deg)
Indoor fan mode HH
H
L
HH
H
Cooling
Set temp.
Set temp.
(-1)-2
(-2)-4
(deg)
Indoor fan mode
HH
H
L
HH
H
Heating
SM830232-00̲欧州向けVRF Indoor̲201404.indb 5
SM830232-00̲欧州向けVRF Indoor̲201404.indb 5
2014/04/04 14:25:44
2014/04/04 14:25:44