5
- 4
1. Simple Settings Function
5
VRF SYSTEMS Indoor Unit
List of Simple Setting Items
Item code
Item
Setting data
No.
Description
Filter sign ON time
(fi lter life time)
0000
Not displayed
0001
150 hours
0002
2,500 hours
0003
5,000 hours
0004
10,000 hours
0005
Use the fi lter clogging sensor.
Degree of fi lter fouling
0000
Standard (setting at time of shipping)
0001
Highly fouled
(Filter sign ON time is reduced to one-half the set time.)
Central control
address
0001
Central control address 1
0002
Central control address 2
0003
Central control address 3
0064
Central control address 64
0099
No central control address set (setting at time of shipping)
Operating mode
priority change
0000
Normal (setting at time of shipping)
0001
Priority
Fan speed when
heating thermostat is
OFF
Compressor ON
Compressor OFF
0000
Lo 1 min., LL 3min.
LL
0001
Lo
LL
0002
LL
LL
0004
Lo 1 min., LL 3min.
Lo
0005
Lo
Lo
0006
LL
Lo
Heating intake
temperature shift
0000
No shift
0001
Shifts intake temperature 1°C down.
0002
Shifts intake temperature 2°C down.
0003
Shifts intake temperature 3°C down.
0004
Shifts intake temperature 4°C down.
0005
Shifts intake temperature 5°C down.
0006
Shifts intake temperature 6°C down.
Electric heater
installation
0000
No heater
0001
Heater installed
Humidifying when
heater thermostat is
OFF
0000
No (setting at time of shipping)
0001
Yes
Permit/prohibit
automatic
heating/cooling
0000
Permit
0001
Prohibit
Cool-only
0000
Normal
0001
Cool only (Set “1” for item code OD.)
NOTE
• In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a
vaporizing humidifier is used.
• Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
• Do not change any setting data that does not appear in this list.
SM830232-00̲欧州向けVRF Indoor̲201404.indb 4
SM830232-00̲欧州向けVRF Indoor̲201404.indb 4
2014/04/25 11:11:12
2014/04/25 11:11:12
Содержание S-22MU1E5A
Страница 7: ...MEMO 1 2...
Страница 20: ...3 1 VRF SYSTEMS Indoor Unit 3 3 OUTDOOR UNIT REPAIR PROCEDURES Refer to the Service Manual of Outdoor Unit...
Страница 21: ...MEMO 3 2...
Страница 23: ...MEMO 4 2...
Страница 49: ...MEMO 6 2...
Страница 53: ...201404...