1-9-1. How to Set on PC Board
1. Turn off the power breaker to halt the supply of electricity to the PC board.
2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor
unit control PCB is placed. (Fig. 1-9-1)
3. Set the On/Off switches in the Off position which are now set in the On position.
Select the positions of the Select SW001 switches respectively to make the desired external static pressure
settings referring to the Table 1-9-1.
Table 1-9-1 External static pressure SW setting
External static pressure
at the time of rated
airflow volume
SW001
TP6
TP3
TP1
ON
1
2
3
1
ON
2
3
180
150Pa
100Pa
60Pa
224
200Pa
130Pa
75Pa
200
180Pa
120Pa
75Pa
1
2
ON
3
Table 1-9-2 Setting the external static pressure
Indoor unit
Item code
180
External static pressure of the rated air
flow volume
150 Pa
200 Pa
100 Pa
130 Pa
60 Pa
200
224
180 Pa
120 Pa
75 Pa
75 Pa
NOTE:
Failure to set this parameter may result in decreased
airflo
w
and condensation.
(CZ-RTC4)
How to set the external static pressure
Indoor Unit control PC board
Setting at
shipment
ON
Fig. 1-9-1
A
°
°
(1)
(5)
(6)
(2)
(1)
(4)
(1)
(3)
(1)
(4)
(1)
Press and hold down the
,
and
buttons simultaneously for 4 or more seconds.
(
, the Unit No., Item Code and Detailed
Data will blink on the LCD display.)
(2)
The indoor unit numbers in the group control will
be sequentially displayed whenever the Unit Select
button is pressed
.
Only the fan motor for the selected indoor unit will
operate during this time.
(3) Specify the “
” item code by pressing the
/ buttons for the temperature setting buttons
and confirm the values.
(“
” set at shipment )
(4)
Press the
/
buttons for the time to amend
the values for the set data.
See the Table 1-9-2 and Fig.1-9-2 and select a value
“
”, “
” or “
”.
(5) Press the
button.
The display will stop blinking and remain
illuminated.
(6) Press the
button. The fan motor will stop
operating and the LCD display will return to the
normal stop mode.
CZ-RTC4
1-9-2. Operating the Timer Remote Controller
SM830277-00_大洋州向け R32シングル_TD&SM.indb 3
2019/02/27 11:50:36
Содержание S-160PE1R5B
Страница 12: ...MEMO Xi SM830277 00_ R32 _TD SM indb 12 19 02 26 9 34 28...
Страница 136: ...MEMO 2 16 SM830277 00_ R32 _TD SM indb 16 19 02 28 13 25 27...
Страница 138: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 160PZH2R5 SM830277 00_ R32 _TD SM indb 2 19 02 12 9 55 27...
Страница 140: ...3 4 3 3 2 Indoor Units Ducted Type S 160PE1R5B Electric Wiring Diagram SM830277 00_ R32 _TD SM indb 4 19 02 12 9 55 28...
Страница 160: ...4 18 4 4 3 Outdoor Unit HIC Board U 160PZH2R5 ACXA73 2760 SM830277 00_ R32 _TD SM indb 18 19 02 21 11 54 24...
Страница 161: ...4 19 4 U 160PZH2R8 U 180PZH2R8 U 200PZH2R8 U 224PZH2R8 ACXA73 3104 SM830277 00_ R32 _TD SM indb 19 19 02 21 11 54 24...
Страница 164: ...MEMO 4 22 SM830277 00_ R32 _TD SM indb 22 19 02 21 11 54 26...
Страница 202: ...MEMO 5 38 SM830277 00_ R32 _TD SM indb 38 19 02 28 13 37 39...
Страница 274: ...201903 SM830277 00_ R32 _TD SM indb 1 19 02 12 9 03 53...