33
AHU Kit – Installation Instructions – 09/2021
Product description
3
System lineup – PACi NX systems
Capacity
(kW)
Refrigerant
Outdoor unit
1
AHU Kit
PACi NX Standard
PACi NX Elite
Single-phase
units
Three-phase
units
Single-phase
units
Three-phase
units
3.6
R32
U-36PZ3E5
–
U-36PZH3E5
–
PAW-280PAH3M
2
5.0
R32
U-50PZ3E5
–
U-50PZH3E5
–
6.0
R32
U-60PZ3E5A
–
U-60PZH3E5
–
7.1
R32
U-71PZ3E5A
–
U-71PZH3E5
U-71PZH3E8
10.0
R32
U-100PZ3E5
U-100PZ3E8
U-100PZH3E5
U-100PZH3E8
12.5
R32
U-125PZ3E5
U-125PZ3E8
U-125PZH3E5
U-125PZH3E8
14.0
R32
U-140PZ3E5
U-140PZ3E8
U-140PZH3E5
U-140PZH3E8
1
With PACi NX systems, only 1-to-1 installations are allowed (e.g. 1 x PACi NX outdoor unit + 1 x PAW-280PAH3M). Com
-
binations with more than 1 outdoor unit or more than 1 AHU Kit are not possible.
2
Mixed installation with standard indoor units is not allowed.
3.4 System Overview
System Overview – ECOi systems
Single-connection system
B
A
C
I
K
H
G
M
J
L
F
E
D
A AHU Kit enclosure (complete)
B AHU system (field supplied)
C Remote controller (integrated in AHU Kit enclosure)
D Outdoor unit
E Liquid piping (field supplied)
F Gas piping (field supplied)
G Electronic expansion valve
H Thermistor for liquid pipe
I
Thermistor for gas pipe
J Thermistor for suction air
K Thermistor for discharge air
L Inter-unit wiring
M Magnetic relay for operating the blower (field sup
-
plied)
NX
31.08.2021, cH
New drawing inserted as per ii_AHUkit21_EN_
v3_2021.08.11pa.pdf