AHU Kit – Installation Instructions – 09/2021
Electrical Wiring
5
Wiring system diagram – ECO G systems
U2
U1
R2
R1
L
N
2
1
D
B
L
N
2
1
A
L
N
C
L
N
3
4
1
2
Remote
controller
WHT
BLK
Power supply
220 – 240V ~50/60Hz
Power supply
220 – 240V ~50/60Hz
Ground
Ground
Ground
AHU Kit
Outdoor unit
Recommended wire lengths and diameters
AHU Kit
Type
(B) Power supply
Time delay fuse or circuit breaker
PAW-160/280/560MAH2(M/L)
2.5 mm
2
(AWG#13)
10 – 16 A
Max. 150 m
Control wiring
(C) Inter-unit control wiring
(between outdoor unit and AHU Kit)
(D) Remote control wiring
(E) Control wiring for group
control 1
0.75 mm
2
(AWG# 18)
Use shielded wiring
or
2.0 mm
2
(AWG# 14)
Use shielded wiring
0.75 mm
2
(AWG# 18)
Use shielded wiring
0.75 mm2
(AWG# 18)
Use shielded wiring
Max. 1,000 m
Max. 2,000 m
Max. 500 m
Max. 200 m (total)
Wiring system diagram – PACi systems and PAH2 generation AHU Kits
For single-phase outdoor units
U2
U1
R2
R1
L
N
2
1
D
B
L
N
2
1
A
L
N
C
L
N
U1
U2
Remote
controller
WHT
BLK
Power supply
220 – 240V ~50/60Hz
Power supply
220 – 240V ~50/60Hz
Ground
Ground
Ground
AHU Kit
Outdoor unit
INV unit
For three-phase outdoor units
U2
U1
R2
R1
L
N
2
1
D
B
L
N
2
1
A
L1
L2
C
L1
L2
U1
U2
L3
N
L3
N
Remote
controller
WHT
BLK
Power supply
220 – 240V ~50/60Hz
Power supply
380 – 415V 3N ~50/60Hz
Ground
Ground
Ground
AHU Kit
Outdoor unit
INV unit
01.09.2021, cH
New drawing inserted as per ii_AHUkit21_EN_
v3_2021.08.11pa.pdf
06.08.2021, cH
I assume, that the text with Strikethrough format-
ting is not relevant for ECO G and can therefore be
deleted. Correct?
06.08.2021, JW
Keep the group control. It would be even possib-
le with GHP.
01.09.2021, cH
New drawings (x2) inserted as per ii_AHUkit21_EN_
v3_2021.08.11pa.pdf