AHU Kit – Installation Instructions – 09/2021
General information and safety notes
1
[m
c
]
[A
min
]
[m
c
]
[A
min
]
[m
c
]
[A
min
]
Line 1 Line 2 Line 3
Line 1 Line 2 Line 3
Line 1 Line 2 Line 3
1.22
2.5
3.0
12.8
3.5
7.9
11.7
105.1
5.8
21.5
32.1
288.6
1.3
2.6
3.2
14.5
3.6
8.3
12.4
111.2
5.9
22.3
33.2
298.7
1.4
2.8
3.4
16.8
3.7
8.8
13.1
117.5
6.0
23.0
34.4
308.9
1.5
3.0
3.7
19.3
3.8
9.3
13.8
123.9
6.1
23.8
35.5
319.3
1.6
3.2
3.9
22.0
3.9
9.8
14.6
130.5
6.2
24.6
36.7
329.8
1.7
3.4
4.2
24.8
4.0
10.3
15.3
137.3
6.3
25.4
37.9
340.6
1.8
3.6
4.4
27.8
4.1
10.8
16.1
144.2
6.4
26.2
39.1
351.5
1.9
3.8
4.6
31.0
4.2
11.3
16.9
151.4
6.5
27.0
40.3
362.5
2.0
4.0
4.9
34.3
4.3
11.9
17.7
158.7
6.6
27.9
41.6
373.8
2.1
4.2
5.1
37.8
4.4
12.4
18.5
166.1
6.7
28.7
42.8
385.2
2.2
4.4
5.4
41.5
4.5
13.0
19.4
173.8
6.8
29.6
44.1
396.8
2.3
4.6
5.6
45.4
4.6
13.6
20.2
181.6
6.9
30.4
45.4
408.5
2.4
4.8
5.8
49.4
4.7
14.1
21.1
189.5
7.0
31.3
46.8
420.4
2.5
5.0
6.1
53.6
4.8
14.8
22.0
197.7
7.1
32.2
48.1
432.5
2.6
5.2
6.5
58.0
4.9
15.4
22.9
206.0
7.2
33.1
49.5
444.8
2.7
5.4
7.0
62.6
5.0
16.0
23.9
214.5
7.3
34.1
50.9
457.3
2.8
5.6
7.5
67.3
5.1
16.7
24.8
223.2
7.4
35.0
52.3
469.9
2.9
5.8
8.1
72.2
5.2
17.3
25.8
232.0
7.5
35.9
53.7
482.7
3.0
6.0
8.6
77.2
5.3
18.0
26.8
241.0
7.6
36.9
55.1
495.6
3.1
6.2
9.2
82.5
5.4
18.7
27.9
250.2
7.7
37.9
56.6
508.7
3.2
6.6
9.8
87.9
5.5
19.4
28.9
259.6
7.8
38.9
58.1
522.0
3.3
7.0
10.4
93.4
5.6
20.1
29.9
269.1
7.9
39.9
59.6
535.5
3.4
7.4
11.1
99.2
5.7
20.8
31.0
278.8
PACi outdoor units
[m
c
]
Refrigerant charge amount (i.e. total of refrigerant at shipment and refrigerant charge amount in
the field), specified in kilogrammes (kg)
[m
max
]
Maximum refrigerant charge amount, specified in kilogrammes (kg)
[m
c
] ≤ 1.22
Can be installed
1.22 < [m
c
] ≤ [m
max
]
Installation possible within the hatched range
[m
c
] > [m
max
]
Cannot be installed