Use of an earth leakage breaker other than the one with designated capacity may disable the safety
shutdown and cause electrical shock or fire.
Protection cannot be made by a current leak relay.
●
Make it sure to conduct the earthing of the unit!
●
Use the circuit exclusively for the unit (do not share the circuit with other products).
●
Do not allow wiring to come closer to high temperature areas (compressor, condenser, discharge pipe)
and the edge of metals.
The figure below shows the allowable voltage for the unit. Ensure that voltage falls within this range.
Testing point is on the power source terminal of the unit
●
In case of electricity recovery after power interruptions, if all the devices including the condensing unit start up
simultaneously, which, in turn,may cause the failure of electrical components.
If the capacity of power supply or wiring is not enough, the start failure may occur due to low starting voltage.
(when starting voltage less than 187V (220V power source) or 323V(380 power source)
In this case do not allow device to start up simultaneously. (Use the time relay to set the start sequence)
Page #
Allowable power-supply voltage
Electrical Wiring Work
Prevention of electrical shock and fire
Electrical work shall be done by qualified technicians with enough electrical knowledge.
Ensure to install an earth leakage breaker with the designated capacity