1.Spray with nitrogen gas during brazing (Strictly abide by).
2.Use the deoxidized phosphorus copper pipes that are clean both inside and outside.
After the piping construction work, conduct the air-tight test as below:
1.Install and insulate the bulb according to the instruction. Make it sure minimum 5K superheat in all conditions.
Install angle of Bulb
Pipe diameter less than
φ
25.4(1 inch)
:
upper position
Pipe diameter more than
φ
25.4(1inch)
:
Lower postion 45°
(
4 o'clock position
)
15
Page
2.The superheat degree will become less in winter season, adjust the expansion valve to make sure minimum 5K
superheat degree.
Expansion valve
Since the unit is composed of highly-precise components, any contaminants mingled into will damage the unit, with gas leakage,
capacity reduction, even abrasion and burn.
The bulb package installation method is as shown in the
figure. The bulb needs to be installed horizontally.
The quality of the design and construction work of refrigerant piping has great impact on the performance and reliability of Condensing unit. Observe precautions
given below in the case of design and construction work.
The compressor is cooled by liquid injection, if the refrigerant charge volume is not enough, the cooling effect will be decreased due to gas bubble in liquid line, it
will result in high temperature of compressor. Do not operate the unit under lack of refrigerant conditions.
Air-tight Test
(
After piping construction work, before heat insulation work
)
Size of refrigerant piping
Do not contaminate the unit with dust, metallic powder, oxidized scale, etc.
Refrigerant Piping Work
R22
2.8MPa
1.4MPa
R404A
2.84MPa
1.75MPa
Suction Line
5/8"
(
φ
15.88
)
3/4"
(
φ
19.05
)
3.When cutting or deburring a copper pipe, do not allow chips to contaminate the pipe. The customer should install the
suction filter on the suction line by themselves.
Refrigerant
High Pressure Side
Low Pressure Side
The sizes of piping by unit models are given as below. However, note that an optimal size shall be decided by calculating the loss of pressure in piping and the
flow rates of a refrigerant so that cooling capacity and oil return would not be affected.
Model
OCU-R Series, OCU-NR Series
Other Model
Liquid Line
3/8"
(
φ
9.53
)
3/8"
(
φ
9.53
)
45°
Insulation
Material
Metal Fixture