12
VT ratio setting mode
Factory setting / Display
・
Enter VT ratio using
<kW/kWh>,< A >,< V >,<CHARGE>
.
・
If the VT is 440/110, set to
“4.00”.
(
1.00
~
99.99
)
↓
<SET>
Current for time measurement setting mode
Factory setting / Display
・
Enter current for time measurement using
<kW/kWh>,< A >,< V >
.
・
If you measure the current over 50.0%F.S, set to
“50.0”.
(
1.0
~
100.0
)
↓
<SET>
Cutoff current setting mode
Factory setting / Display
・
Enter cutoff current using
<kW/kWh> ,< A >,< V >
.
・
If you don’t measure the current under 10.0%F.S,
set to
“10.0”.
(
1.0
~
50.0
)
↓
<SET>
Unit for pulse output setting mode
Factory setting / Display
・
Press
<kW/kWh>
to change unit for pulse output.
・
Unit is selected from
0.001
→
0.01
→
0.1
→
1
→
10
→
100
→
ALARM.
↓
<SET>
Alarm value setting mode
Factory setting / Display
・
Enter power for alarm using
<kW/kWh>,< A >,< V >,<CHARGE>,<TIME>,<COUNT>
.
*It is only when
“ALARM” is selected on unit for pulse
output setting mode.
(
0
~
9999.99kWh
)
↓
<SET>
Electricity charge setting mode
Factory setting / Display
・
Press <COUNT> to change
JPY
→$→
EUR
→
CNY
→
CHG
→
CO2.
・
Enter the rate per 1kWh using
<kW/kWh>,< A >,< V >,<CHARGE>
.
↓
<SET>
Normal display